93
Installation Clearance
A) For MMC – B/BR series (Single/Multiple Condensing Unit)
When two or more outdoor units are installed in a location, they must be positioned such that one unit will not
be taking the hot discharge air from another.
This also applies when two or more units are installed one above the other. The units must all face the same
direction or opposite direction (back to back), such that hot air short circuit does not occur.
Model
MMC 075B
MMC 100B/BR
MMC 125B/BR
2 X
MMC 075B
2 X
MMC 100B/BR
A (mm)
500
500
500
700
700
B (mm)
300
300
300
300
300
C (mm)
1,200
1,200
1,200
1,500
1,500
Model
2 X
MMC 125B/BR
3 X
MMC 100B/BR
MMC 100B/BR +
2 X MMC 125B/BR
4 X
MMC 100B/BR
4 X
MMC 125B/BR
A (mm)
700
1,000
1,000
1,000
1,000
B (mm)
300
300
300
300
300
C (mm)
1,500
2,000
2,000
2,000
2,000
Summary of Contents for MDB075B
Page 1: ...MDB 2004 Ducted Split Systems Models MDB 075 750B MDB 125 150C MDB 075 500BR MDB 125CR...
Page 38: ...37 Blower Performance Curves MDB 075B BLOWER PERFORMANCE CURVE...
Page 39: ...38 MDB 100B BLOWER PERFORMANCE CURVE...
Page 40: ...39 MDB 125B BLOWER PERFORMANCE CURVE...
Page 41: ...40 MDB 125C BLOWER PERFORMANCE CURVE...
Page 42: ...41 MDB 150B BLOWER PERFORMANCE CURVE...
Page 43: ...42 MDB 150C BLOWER PERFORMANCE CURVE...
Page 44: ...43 MDB 200B BLOWER PERFORMANCE CURVE...
Page 45: ...44 MDB 250B BLOWER PERFORMANCE CURVE...
Page 46: ...45 MDB 300B BLOWER PERFORMANCE CURVE L s...
Page 47: ...46 MDB 350B BLOWER PERFORMANCE CURVE...
Page 48: ...47 MDB 400B BLOWER PERFORMANCE CURVE...
Page 49: ...48 MDB 450B BLOWER PERFORMANCE CURVE...
Page 50: ...49 MDB 500B BLOWER PERFORMANCE CURVE...
Page 51: ...50 MDB 600B BLOWER PERFORMANCE CURVE...
Page 52: ...51 MDB 750B BLOWER PERFORMANCE CURVE...
Page 60: ...59 MODEL MMC 075C CR MODEL MMC 100C...
Page 61: ...60 MODEL MMC 125BR 150C STANDARD VERTICAL DISCHARGE NON CONVERTIBLE...
Page 70: ...69 MODEL INDOOR MDB 600B4 WITH SEQUENTIAL CONTROLLER OUTDOOR MMC 150C x 4...
Page 71: ...70 MODEL INDOOR MDB 750B5 WITH MAGNETIC CONTACTOR OUTDOOR MMC 150C x 5 INDOOR AUXILLARY C1 C1...
Page 72: ...71 Wiring Diagrams Heatpump INDOOR EXPORT MODEL MDB 075 100BR C3 0B MODEL MDB 125CR EXPORT...
Page 73: ...72 MODEL MDB 150 200 250 BR2 EXPORT MODEL MDB 300 350 BR3 EXPORT...
Page 74: ...73 MODEL MDB 400 500 BR4 EXPORT...
Page 84: ...83 Refrigerant Circuit Diagram MODEL MMC 075C 100C...
Page 85: ...84 MODEL MMC 075B 100B 125B 150C...
Page 86: ...85 MODEL MMC 075CR WITH CAPILLARY TUBE EXPANSION SPECIFICATION...
Page 87: ...86 MODEL MMC 100BR 125BR WITH CAPILLARY TUBE EXPANSION SPECIFICATION...
Page 88: ...87 MODEL MMC 075CR WITH THERMAL EXPANSION VALVE SPECIFICATION...
Page 89: ...88 MODEL MMC 100BR 125BR WITH THERMAL EXPANSION VALVE SPECIFICATION...
Page 101: ...100 SEQUENTIAL CONTROLLER BLOCK DIAGRAM...
Page 163: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...