IOM 1210-1 • MAGNITUDE
®
MODEL WMC CHILLERS
38 www.DaikinApplied.com
o
peraTIon
MODES Setpoints
Figure 44: MODES Setpoint Screen
NOTE:
Grayed out setpoints do not apply to this model chiller.
Table 10: MODES Setpoint Settings
Description
No .
Default
Range
Password
Comments
Compr # 2 Stage Sequence #
14
1
1,2, … (# of
Compressors)
M
Sets sequence number for # 2 compressor. If set to 1, it is always
first to start. If set to 2, it is always second to start. (Note 1)
Compr # 2 Staging Mode
13
Normal
Normal, Efficiency,
Pump, Standby
M
Normal uses standard sequencing, Efficiency starts one
compressor on each unit, Pump starts all compressors on one
chiller first, Standby uses this compressor only if another fails
Compr #1 Stage Sequence #
12
1
1,2, … (# of
Compressors)
M
Sets sequence number for # 1 compressor. If set to 1, it is always
first to start. If set to 2, it is always second to start. (Note 1)
Compr #1 Staging Mode
11
Normal
Normal, Efficiency,
Pump, Standby
M
Normal uses standard sequencing, Efficiency starts one
compressor on each unit, Pump starts all compressors on one
chiller first, Standby uses this compressor only if another fails
Maximum Compressors ON
10
1
1-8
M
Total number of compressors allowed to run at one time
BAS Network Protocol
9
MODBUS
None, Local, BACnet,
LonWorks, MODBUS,
Remote
M
Sets BAS Standard Protocol to be used, or LOCAL if none
Condenser Pump
6
Pump #1
Only
Pump #1 Only, Pump
#2 Only, Auto Lead, #1
Primary, #2 Primary
M
Pump #1 Only, Pump #2 Only, use only these pumps AUTO,
balance hours between #1 and #2 #1 Primary, #2 Primary, if
primary fails, use other
Evaporator Pump
5
Pump #1
Only
Pump #1 Only, Pump
#2 Only, Auto Lead, #1
Primary, #2 Primary
M
Pump #1 Only, Pump #2 Only, use only these pumps AUTO,
balance hours between #1 and #2 #1 Primary, #2 Primary, if
primary fails, use other
Control Source
3
Switches
Switches, Local, BAS
O
Sets control source. See
"Unit Enabling/Disabling" on page 20
.
Unit Enable
1
OFF
OFF, AUTO
O
OFF, everything is off. AUTO, Evap pump on, comp, cond pump
and tower on as required to meet LWT
NOTES:
1. If both compressors have the same sequence number, they will automatically balance starts and run-hours.
2. Setpoints 11 through 14 display compressor staging strategy.