52
MWM-J_(ii)
Performance Data
Model: M5WM20JR - M5LC20CRJ
Heating Mode
ID DB°C
Outdoor WB°C
-9
-6
-5
6
12
15
18
Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW)
15
3.189
3.189
3.610
3.610
3.750
3.750
5.291
5.291
6.132
6.132
6.553
6.553
6.973
6.973
17
3.106
3.106
3.291
3.291
3.664
3.664
5.285
5.285
6.038
6.038
6.457
6.457
6.876
6.876
19
3.022
3.022
2.973
2.973
3.578
3.578
5.279
5.279
5.944
5.944
6.361
6.361
6.778
6.778
21
2.938
2.938
2.854
2.854
3.493
3.493
5.200
5.200
5.849
5.849
6.265
6.265
6.681
6.681
23
2.855
2.855
2.936
2.936
3.407
3.407
5.048
5.048
5.755
5.755
6.169
6.169
6.584
6.584
25
2.771
2.771
3.017
3.017
3.322
3.322
4.896
4.896
5.661
5.661
6.074
6.074
6.487
6.487
27
2.688
2.688
3.099
3.099
3.236
3.236
4.744
4.744
5.567
5.567
5.978
5.978
6.389
6.389
Remark:
AFR: Air
fl
ow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling Capacity (kW)
SHC: Sensible Heat Capacity (kW)
PI: Power Input
Notes:
1. Ratings shown are gross capacities which do not include a deduction for indoor fan motor heat.
2.
shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 0 °C to 46°C without pressure trip.
Part Number : 0652102C2020