Performance Data
M
WM-J_(ii)
36
Model:
M
WM09JR –
M
LC09CR
Heating Mode
ID DB
°C
OUTDOOR WB °C
-9 -6 -5 6 12 15 18
TC SC TC SC TC SC TC SC TC SC TC SC TC SC
15
1.595 1.595 1.805 1.805 1.875 1.875 2.646 2.646 3.066 3.066 3.276 3.276 3.486 3.486
17
1.553 1.553 1.775 1.775 1.828 1.828 2.642 2.642 2.996 2.996 3.202 3.202 3.409 3.409
19
1.511 1.511 1.744 1.744 1.781 1.781 2.639 2.639 2.926 2.926 3.128 3.128 3.331 3.331
21
1.469 1.469 1.701 1.701 1.733 1.733 2.586 2.586 2.856 2.856 3.054 3.054 3.253 3.253
23
1.427 1.427 1.644 1.644 1.686 1.686 2.482 2.482 2.786 2.786 2.981 2.981 3.175 3.175
25
1.386 1.386 1.587 1.587 1.639 1.639 2.378 2.378 2.716 2.716 2.907 2.907 3.097 3.097
27
1.344 1.344 1.530 1.530 1.592 1.592 2.274 2.274 2.647 2.647 2.833 2.833 3.019 3.019
FROST REGION
Part Number: 00061210C0909
Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling Capacity (kW)
SHC: Sensible Heat Capacity (kW)
PI: Power Input
Notes:
1. Ratings shown are gross capacities which do not include a deduction for indoor fan motor heat.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 0 °C to 46°C without pressure trip.