General Data - Heat pump R410A Inverter
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 12°C / 7°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35°C AIR AMBIENT TEMPERATURE.
b) HEATING - 40°C / 45°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7°C AIR AMBIENT TEMPERATURE.
4) POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
56
M5ACV210CR
Btu/h
200000
W
58620
Btu/h
210000
W
61550
COOLING
W
22300
HEATING
W
21800
COOLING
A
44.6
HEATING
A
44.6
V/Ph/Hz
380-415 / 3 / 50
R410A
ELECTRONIC EXPANSION VALVE
HEIGHT
mm/in
1786 / 70.3
WIDTH
mm/in
2093 / 82.4
DEPTH
mm/in
1192 / 46.9
HEIGHT
mm/in
1975 / 77.7
WIDTH
mm/in
2176 / 85.6
DEPTH
mm/in
1242 / 48.9
kg/lb
682 / 1504
dBA
67
COOLING
l/s / m
3
/hr
2.66 ( 9.6 )
HEATING
l/s / m
3
/hr
2.86 ( 10.3 )
PROPELLER / DIRECT
2
HORIZONTAL MULTISTAGE END-SUCTION
MAX. WATER OPER. PRESSURE
kPa / psi
1000 / 145
COOLING
l/s / m
3
/hr
2.66 ( 9.6 )
HEATING
l/s / m
3
/hr
2.86 ( 10.3 )
INSTALLATION PIPE CONNECITON
mm/in
38 / 1 1/2
COOLING m
22.0
HEATING
m
20.0
NOT APPLICABLE
L / ft
3
NOT APPLICABLE
SCROLL
0 - 210000
COOLING
kg/lb
9.5 / 20.9
HEATING
kg/lb
8.5 / 18.7
PIPING
TYPE
COMPRESSOR
HEAD
MATERIAL
REFRIGERANT
STAGE OF CAPACITY CONTROL (Btu/h)
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
POWER SOURCE
CONTROL
CAPACITY/VOLUME
UNIT DIMENSION
PACKING DIMENSION
TANK
NOMINAL WATER FLOW
UNIT WEIGHT
PUMP
TYPE
WATER FLOW RATE
HYDRAULIC KIT
CHARGING MASS
MODEL
TYPE/DRIVE
QUANTITY
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
REFRIGERANT TYPE
EVAPORATOR
CONDENSER FAN
SOUND PRESSURE LEVEL