IM 743-1

7

Installation

The Modbus Communication Module can be factory or field installed.  Use the appropriate chiller
selection software program in McQuayTools to include the Modbus Communication Module with
the unit.
For field installation, the Modbus Communication Module kit may be ordered through McQuayTools
or through McQuay Parts.  The Modbus Communication Module kit includes the Modbus
Communication Module (RS-485 serial network board) and this installation manual.  The Modbus
Communication Module from McQuay Parts is also sold separately (i.e. just the module itself).  See
Replaceable Parts List for part numbers.

Mounting

!

CAUTION

Electrostatic discharge hazard.

Can cause equipment damage.

This equipment contains sensitive electronic components that may be damaged by electrostatic
discharge from your hands. Before you handle the Modbus Communication Module, touch a grounded
object, such as the metal enclosure, in order to discharge the electrostatic potential in your body.

Mounting a Modbus Communication Module

To mount a Modbus Communication Module:

1.

 

Remove power from the MicroTech II Chiller Unit Controller.

2.

 

Locate the Serial Card slot on the MicroTech II Chiller Unit Controller (see Figure 3.)

3.

 

Remove the cover from the Serial Card slot if it hasn’t already been removed.  Use a small
screwdriver to pry the cover off from one end.

4.

 

Remove the plastic knockout in the cover.

5.

 

Figure 4 shows the Serial Card slot that details how the 8-pin plug mates to the 8-pin header on
the Modbus Communication Module.

6.

 

Grasp the Modbus Communication Module, with the network connector on the underside.  The 8-
pin header on the Modbus Communication Module must mate to the 8-pin plug in the MicroTech
II Chiller Unit Controller. The plug has a guide on each end to direct the Modbus Communication
Module into the mating guide on the header.

Note:  

Since it is impossible to see the connectors mate, this operation relies more on feeling
the Modbus Communication Module into the connector than seeing the connectors
mate.

7.

 

Insert the Modbus Communication Module, pointing up, into the slot, rolling it into a level
position as you move it into the slot.

8.

 

Keeping the Modbus Communication Module 

level

, move it into the slot until you feel the

connectors line up.  The correct position seems to be level, toward the left side of the slot, and
down slightly from the top.

9.

 

When you feel the connectors align, press the Modbus Communication Module into the
connector.  Verify that it is firmly seated in the connector.

10.

 

Replace the cover on the Serial Card slot.  Slip the cover over the network connector plug.

11.

 

Connect the Modbus Communication Module to the network.

Summary of Contents for IM 743

Page 1: ...Cooled Global Scroll ACZ Air Cooled Scroll Condensing Unit WGZ Water Cooled Global Scroll AGS Air Cooled Global Screw WGS Water Cooled Global Screw NOTICE Use this manual to physically install the com...

Page 2: ...to the Network 11 Network Topology 11 Addressing and Establishing Communications 11 Network Address and Baud Rate 11 Configuring the Unit Controller 11 Service Information 13 Test Procedures 13 Repla...

Page 3: ...ir Cooled Scroll Chiller Installation Operation and Maintenance Manual www mcquay com IOMM WGZ McQuay International MicroTech II Water Cooled Scroll Chiller Installation Manual www mcquay com IOMM WPV...

Page 4: ...hange any information contained herein without prior notice The user is responsible for determining whether this software is appropriate for his or her application The following are trademarks or regi...

Page 5: ...ules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment Operation of this equipment in a residential are...

Page 6: ...jor Components RS 485 Network Connetor 8 Pin Header Modbus Connector RS 485 Network Connector This connector connects the Modbus Communication Module to the RS 485 network Pin Function 1 Reference 2 I...

Page 7: ...rom the Serial Card slot if it hasn t already been removed Use a small screwdriver to pry the cover off from one end 4 Remove the plastic knockout in the cover 5 Figure 4 shows the Serial Card slot th...

Page 8: ...e of the network cable to Pin 2 of the connector plug b Connect the other wire to Pin 3 of the connector plug c No wire is connected to the remaining pin Figure 3 Serial Card Slot Location on Unit Con...

Page 9: ...IM 743 1 9 Figure 5 Network Cable Routing and Connections Figure 6 Network Connection Detail Net w ork Cab le Pin 3 Pin 2...

Page 10: ...the slot 10 Keeping the Modbus Communication Module level move it into the slot until you feel the connectors line up The correct position seems to be level toward the left side of the slot and down s...

Page 11: ...a MicroTech II Chiller Unit Controller is set in the unit controller keypad display The Modbus network address and data transmission rate Baud Rate is only available in the keypad display when the pr...

Page 12: ...d via the network or with the keypad display The appropriate Operation Manual provides default values and keypad operation The MicroTech II Chiller Modbus Protocol Information Document ED 15063 provid...

Page 13: ...ll does not respond contact the McQuay Controls Customer Support group at 866 4MCQUAY 866 462 7829 Replaceable Parts List Network Connection Plug Generic Replacement Parts If you lose this terminal bl...