McQuay ALZ

304 C – 02/06 D – pag. 10/16 

The single compressor board has been designed so as to support two connected terminals, allowing therefore 
data access from two different points; it can also work without any connected terminal, ensuring this way a total 
safety to the data. 
 

Second tandem board 

It represents an expansion of the main board. The connection areas are the following (clockwise): 

• 

analog inputs (

B4

 and 

B5

) for the probes connection (relative to the second circuit) 

• 

24V terminal (with D.C.) for the supply of any pressure probe 

• 

digital inputs (from 

ID8

 to 

ID11

) for safety connections (relative to the second circuit) 

• 

digital relay outputs to manage any controlled device 

• 

the 

Y2 GND

 analog output for the connection of the optional boards for the management of condensation fans 

(ON/OFF regulation mode or with continuous rotation speed variation) 

• 

the flat cable for the connection to the single compressor main board 

• 

P1

 pin-strip relative to the Y2 analog output (to be normally left open, except in particular situations – see 

parameters F3 and F4). 

 

User Interface (Terminal) 

The terminal allows the access to the data of the unit. On the terminal there are 5 LED indicators to indicate the 
status of the unit, the status of the compressors (ON/OFF) and the timer for compressors/pump after 100 
operating hours. An internal buzzer signals any maloperating in the unit. 

Display -

 The display consists of 3 digits, with the automatic display of the decimal point between -19.9 and + 

19.9°C; outside this measurement range, the value is automatically displayed without decimal (although in its 
inside the machine is always operating by taking into account the decimal part). During the normal operation, the 
displayed value corresponds to the temperature being read by the probe B1, that is the evaporator water in-let 
temperature. 

Status of the unit - 

The User is informed of the status of the unit by means of five LED indicators on the terminal 

display and two LED indicators (yellow and green) placed on the main board. 

Summary of Contents for ALZ "B"

Page 1: ...ooled motocondensing unit ALZ B 011 1 038 2 ALP B 011 1 038 2 Cooling capacity from 40 to 145 kW 50Hz Refrigerant HFC 407C Scroll Compressors Installation and maintenance manual 304 C 02 06 D Date Jun...

Page 2: ...Repeated check the safety devices and continous cycling of control components must be analyzed and corrected before being reset The simple design of the refrigeration circuit totally eliminates potent...

Page 3: ...Min C Max C Min C Max C Min C Max C Min C Max C 011 1 8 20 4 15 4 8 15 42 013 1 8 20 4 15 4 8 15 42 017 1 8 20 4 15 4 8 14 42 020 1 8 20 4 15 4 8 12 40 022 2 8 20 4 15 4 8 15 42 025 2 8 20 4 15 4 8 1...

Page 4: ...ap heat recovery cond 2 kW 100 4 116 1 123 9 143 9 151 3 Heating capacity 2 kW 132 4 152 4 166 3 189 6 200 9 Power input heat recovery cond 2 kW 35 8 41 5 47 9 51 2 55 4 Desuperheaters heating capacit...

Page 5: ...placed on the unit base that must to be removed only after the final destination In case the unit has to be moved again a similar solution is necessary Handling and lifting Care should be taken to avo...

Page 6: ...from the obstacle fig 4 For other installation solutions consult McQuay technicians Acoustic protection The low noise levels of the ALZ units means that they meet most of the most restrictive regulati...

Page 7: ...of fan speed Full alarm management Can be linked up to serial line for supervisory telemaintenance control Can be linked up to an external terminal unit Controlled devices Compressor Condensation fans...

Page 8: ...EO high supply voltage OFF OFF OFF OFF OFF OFF EP eeprom boot OFF OFF OFF OFF OFF OFF Cn discon remote terminal Ht high temperature ON Electrical features Power supply Voltage supply range 24V 15 10 5...

Page 9: ...D7 for alarm connection jumper connector for expansion board connection digital relay outputs to manage any controlled device the Y1 GND analog output for the connection of the optional boards for the...

Page 10: ...or main board P1 pin strip relative to the Y2 analog output to be normally left open except in particular situations see parameters F3 and F4 User Interface Terminal The terminal allows the access to...

Page 11: ...alue blinks on display the alarm code appears on the LCD alternatively with the temperature value After the alarms have been cleared either with automatic reset or by pressing the and keys simultaneou...

Page 12: ...de password which is different from the USER one to prevent any unauthorized access to the data Setting the password 00 flashes on the display Pressing the t and u buttons will allow you to stop the b...

Page 13: ...isplays values Buzzer sound after 5 password for USER parameters stores parameters in eeprom stores parameters in eeprom silences the buzzer PRG SEL Normal operating condition after 5 password for FAC...

Page 14: ...a Check the actual unit line voltage to be sure it is the same you can read on the compressor nameplate within 10 and that phase voltage unbalance does not exceed 3 Verify that adeguate power supply a...

Page 15: ...304 C 02 06 D pag 15 16 ALZ ALP B Unit dimensions Fans Arrangement ALZ ALP B 011 1 020 1 ALZ ALP B 022 2 033 2 ALZ ALP B 036 2 038 2 2780 011 1 020 1 3530 022 2 033 2 4280 036 2 038 2...

Page 16: ...hanges in design and construction at any time without notice thus the cover picture is not binding McQuay Italia S P A S S Nettunense km 12 300 00040 Cecchina Roma Italia Tel 06 937311 Fax 06 9374014...

Reviews: