IOM 686
AGZ 030A through 065A
85
2. Remove power from the controller by placing CB1 to the OFF position. Disconnect at least one
wire from the power input terminals of the Output Board. The resistance should not be less than
3000 ohms.
If the resistance is greater than the acceptable value, go to step 3.
If the resistance is less than the acceptable value, the Output Board is defective.
3. Check the discrete wiring and connections between the Output board and the Controller. Aux/Out
terminal strip and the field wiring terminal strip.
Note: The MCB Aux/Out connector plug terminals displace wire insulation to make contact
with the conductor. If a faulty Aux/Out connections is suspected, try pressing down on the
wire in the terminals with a small screwdriver.
LED Lit, Output not Energized
If the LED of a suspect output is lit but the load connected to it is not energized, and everything is
intact between the MCB and the coil side of the relay, perform the following procedure to isolate the
problem:
1. Verify that 24 or 120 Vac power is present at the suspect output’s screw terminal on the Output
Board.
2. Remove power from the controller by opening CB1. Pull the 5-amp fuse on the contact side of
the relay and check it for continuity with an ohmmeter.
If the fuse is not bad, reinstall it and go to step 3.
If the fuse is bad, replace it and inspect the load and associated wiring before restoring power.
Note that a fuse from an unused output can be substituted for the bad fuse.
3. Remove power from the controller by opening CB1. Swap the suspect relay with a known good
relay. Try to choose a relay that will not affect unit operation. Restore power by closing CB1.
If the output load energizes, the suspect relay is bad. Replace the relay.
If the output load does not energize (when LED is lit again), check the load circuit wiring and
components.
Output Energized, LED not Lit
If the LED of a suspect output is not lit, but the load connected to it is energized, either the Solid-State
relay or the MOV is bad. The Solid-State relay contacts and the MOV, which are in parallel, can both
fail closed. Perform the following procedure to isolate the problem:
1. Remove power from the controller by opening CB1. Pull the Solid-State relay from the suspect
output’s socket.
2. Restore power by closing CB1.
If the output load remains energized when there is no relay in the socket, the output’s MOV has
failed and the Output Board must be replaced.
If the output load de-energizes, the relay that was pulled is defective.
Contact Chatter
Contact chatter is very rapid opening and closing of contacts. It is usually caused by low voltage at the
electromechanical relay or contactor coil. If contact chatter is occurring on a relay or contactor
connected to one of the Output Board Solid-State relays, it is also possible that a faulty connection
exists on the power supply terminals of the Aux/Out plug connector on the MCB. In very rare
instances, contact chatter can be caused by a faulty Solid-State relay. Perform the following procedure
to isolate the problem.
1. Verify that the voltage at the load’s power supply and at the Solid-State relay contacts is adequate.
2. Remove power from the controller by opening CB1. Swap the suspect relay with a known good
relay. Try to choose a relay that will not affect unit operation. Restore power by closing CB1.
If the chatter does not stop, go to step 3.
If the chatter stops, the suspect relay is defective. Replace the relay.
Summary of Contents for AGZ 030A
Page 21: ...IOM 686 AGZ 030A through 065A 21 Figure 10 Single point Connection with FanTrol...
Page 22: ...22 AGZ 030A through 065A IOM 686 Figure 11 Single point Connection with SpeedTrol...
Page 23: ...20 WKURXJK LJXUH 8QLW RQWURO 6FKHPDWLF 817...
Page 24: ...24 AGZ 030A through 065A IOM 686 Figure 13 Staging Schematic UNT...
Page 25: ...IOM 686 AGZ 030A through 065A 25 Figure 14 MicroTech Controller Schematic...
Page 26: ...26 AGZ 030A through 065A IOM 686 Figure 15 Unit Control Schematic MicroTech...
Page 27: ...IOM 686 AGZ 030A through 065A 27 Figure 16 Staging Schematic MicroTech...
Page 87: ...IOM 686 AGZ 030A through 065A 87 Notes...
Page 88: ...13600 Industrial Park Boulevard P O Box 1551 Minneapolis MN 55440 USA 612 553 5330...