background image

1-7

English

REFRIGERANT PIPING

MAXIMUM PIPE LENGTH AND MAXIMUM
NUMBER OF BENDS

When the pipe length becomes too long, both the capacity
and reliability drop. As the number of bends increases,
system piping resistance to the refrigerant flow increases,
thus lowering the cooling capacity. As a result, compressor
reliability will be affected. Always choose the
shortest path and follow the recommendation as tabulated
below:

PIPING WORKS AND FLARING TECHNIQUE

Do not use contaminated or damaged copper tubing. If any
piping, evaporator or condenser had been exposed or had
been opened for 15 seconds or more, vacuum the system.
Generally, do not remove plastic, rubber plugs and brass
nuts from the valves, fittings, tubings and coils until it is
ready for connection.

If any brazing work is required, ensure that the nitrogen gas
is passed through piping and joints while the brazing work
is being done. This will eliminate soot formation on the
inside walls of the copper tubings.

Cut the pipe stage by stage, advancing the blade of  pipe
cutter slowly. Extra force and deep cut will cause more
distortion of pipe and therefore extra burr.

Remove burrs from cut edges of pipes with a remover as
shown in Fig. R. This will avoid unevenness on the flare
faces which will cause gas leak. Hold the pipe on top position
and burr remover at lower position to prevent metal chips
from entering the pipe.

Insert the flare nuts mounted on the connection parts of both
indoor and outdoor unit, into the copper pipes.
The exact length of pipe protruding from the face of the
flare die is determined by the flaring tool.

Fix the pipe firmly on the flare die. Match the centers of
both the flare die and the flaring punch, and tighten flaring
punch fully.

1/4t

CUTTING COPPER TUBE

Fig. R

Model

10

15

20

 25

Data
Maximum Length (m)

7

10

15

15

Maximum Elevation (m)

5

5

8

8

Maximum No. of Bends (m)

10

10

10

10

20 m

MAX. PIPING LENGTH

MAX. ELEV

A

TION HEIGHT

20 m

MAX. PIPING LENGTH

MAX. ELEV

A

TION HEIGHT

REMOVE BURR

COPPER TUBE

SWAGING BLOCK

Model

30

40

50

60

Data
Maximum Length (m)

20

20

20

20

Maximum Elevation (m)

10

10

10

10

Maximum No. of Bends (m)

10

10

10

8

20 m

20 m

D

A

CCC-0700 (01~16) ENG*

2/1/01, 10:42 AM

7

Summary of Contents for ACC10C

Page 1: ...020C SL20B ALC20B MLC020B CC25C ACC25C MCC025C SL25B ALC25B MLC025B CC30C ACC30C MCC030C SL30C ALC30C MLC030C CC40C ACC40C MCC040C SL40C ALC40C MLC040C CC50C ACC50C MCC050C SL50C ALC50C MLC050C CC60C...

Page 2: ...note on the following important points when installing Do not install the unit where leakage of flammable gas may occur If gas leaks and accumulates at the surrounding of the unit it may cause fire i...

Page 3: ...DIMENSIONS Indoor Unit CC A B C D E F G H I J K L 10 C CR 31 741 702 662 10 765 72 261 411 349 225 261 15 C CR 31 881 842 802 10 905 72 261 411 349 225 261 20 C CR 31 1041 1002 962 10 1065 72 261 411...

Page 4: ...66 92 348 318 129 482 68 5 20B 20BR 840 646 330 297 309 626 46 90 64 177 106 408 378 124 492 78 5 25B 25BR 840 646 330 297 309 626 46 90 64 177 106 408 378 124 492 78 5 2 5 64 5 CC A B C D E F 30C 30C...

Page 5: ...r ance see drawing C Do not put the indoor unit where there is direct sunlight on unit The location is suitable for piping and drainage and it must be have a large distance between a door and unit CEI...

Page 6: ...must not be susceptible to highly concentrated dust oil salt or sulfide gas Outdoor unit SL series Clearance RETURN AIR OBSTACLE OBSTACLE OBSTACLE OBSTACLE SERVICE ACCESS DISCHARGE AIR INSTALLATION O...

Page 7: ...stage by stage advancing the blade of pipe cutter slowly Extra force and deep cut will cause more distortion of pipe and therefore extra burr Remove burrs from cut edges of pipes with a remover as sh...

Page 8: ...TANT These values are for information only they should be checked and selected to comply with the local and or national codes and regulations They are also subjected to the type of installation and si...

Page 9: ...BLE TERMINAL STRIP OUTDOOR UNIT Heat pump units for Heat pump series 10CR 25CR with wire remote control PCB Indoor unit CC 30C Outdoor unit SL 30C Voltage range 220V 240V 1Ph 50Hz Recommended fuse A 2...

Page 10: ...national codes and regulations They are also subjected to the type of installation and size of conductors used Heat pump units for Heat pump series 30CR with wire remote control PCB Indoor unit CC 40...

Page 11: ...l codes and regulations They are also subjected to the type of installation and size of conductors used Heat pump units for Heat pump series 40CR with wire remote control PCB Caution Ensure that the c...

Page 12: ...ed with service port valve for connection to a manometer Remove the caps from the valve and the service port Connect the center manifold gauge with the vacuum pump Connect the manifold gauge to the se...

Page 13: ...hose with refrigerant gas Start the air conditioner unit Open the gas cylinder and low pressure manifold valve When the required refrigerant quantity is pumped in the unit close the low pressure manif...

Page 14: ...hat 1 Condenser fan is running with warm air blowing off the condensing unit 2 Evaporator blower is running and discharge cool air 3 The remote controller incorporates a 3 minute delay in the circuit...

Page 15: ...essor oil is factory precharged It is not necessary to add any oil if the circuit remains sealed 1 All motor pre lubricated and sealed at factory PERIOD At least once every 2 week More frequently if n...

Page 16: ...perfume etc which might have adhered onto the coil This is caused by air humidity after an extended long period of operation The set temperature is too low increase the temperature setting and operat...

Reviews: