1-8
INSTALLATION OF THE OUTDOOR UNIT
• Where a wall or other obstacle is in the path of outdoor unit's intake or exhaust airflow, follow the installation guidelines
below.
5SLY10/15D/DR and 5SLY20C/CR
Wall facing one side
Wall facing two sides
Wall facing three sides
More than 50
Side view
Top view
Top view
More
than 50
Unit: mm
More than 300
More than 150
More than 150
More than 50
More than 100
More than 50
More than 100
REFRIGERANT PIPING
!
CAUTION
Do not install the unit at altitude over 2000m for both indoor and outdoor.
Indoor
5CKY10C/CR
5CKY15C/CR 5CKY20C/CR
Outdoor
5SLY10D/DR
5SLY15D/DR
5SLY20C/CR
Max. allowable length, m
15
15
30
Max. allowable elevation, m
10
10
10
Liquid pipe, mm
O.D. 6.4
O.D. 6.4
O.D. 6.4
Gas pipe size, mm
O.D. 9.5
O.D. 12.7
O.D. 12.7
Additional charge of refrigerant, g/m
20
20
20
(for piping length above 7.5m)
1 5CKYCR-0709 EN
2/5/10, 1:36 PM
8