                                                      www.mcohome.com                                        User Manual

 

MCOHome Technology Co., Ltd     

     

 

4

 

 

Detection  temperature  ≥ setting temperature  +  0.5

,  output  turns  off,  and output  icon 

disappears. 

MH7H-EH 

 

Detection  temperature  <  setting  temperature  -  1.5

,  output  turns  on,  and  output  icon 

displays.

 

 

Detection  temperature  ≥  setting  temperature  ,  output  turns  off,  and  output  icon 

disappears.

 

         

 

Manual / Auto mode setting 

        In  normal  display  interface,  touch  S3  button  can  switch  between  Manual  and  Auto  mode. 

Choose the mode you may need and press S2 button to save the setting. 

Auto Mode: 

Device will follow the preset time periods and temperature to control heating   

                      system automatically. 

Manual  Mode: 

Device  will  follow  the  manual  setting  temperature  to  control  the  heating 

system.

 

 

Vacation mode setting 

 

In normal working interface, if vocation mode is not activated, long press S2 button to enter 

vacation  mode  temperature  setting.  The  default  temperature  is  10 

and  setting  range  is 

5-37 

(41-98℉)

. Press S4 or S5 to adjust the value, then press S3 or wait 25 seconds to save 

the  setting  and  return  to  the  normal  working  interface.  In  this  time  vacation  mode  icon 

displays and device will follow the setting.   

 

 

Long press S2 again will end vacation mode and resume to normal work, vacation mode icon 

will be disappeared.   

 

Local Time Setting 

 

In normal working interface, long press S1 to enter into local time setting interface. 

 

In  local  time  setting  interface,  press  S4  or  S5  button  to  set  the  “week,  hour  &  minute” 

parameter, and press S1 button can switch among the “week, hour & minute”. 

 

After finish the local time setting, press S1 or wait 25 seconds without any key operation will 

save the setting and return to normal display. 

 

Auto Mode Time Periods Parameter Setting 

 

In normal working interface, short press S1 to enter into time periods setting. Four time 

periods can be set for each day of the whole week.   

 

Press S2 can switch among “Hours, Minutes, Temperature value”. Press S4 or S5 can change 

the value.   

 

After finished the setting of 4 time periods on Monday, press S1 and follow the same way to 

set periods of next days. 

 

After all periods set, press S1 /S2 or wait 25 seconds without any key operation will save the 

setting and return to normal display. Device will operate in accordance with the new setting. 

The default setting is as follow: 

Summary of Contents for MH7H-WH

Page 1: ...H 5A MH7H EH 16A Self Consumption 1W External Temp Sensor optional NTC R25 15K B25 50 3550K Working Environment 0 50 0 90 RH Non condensation Temperature Setting 5 37 41 99 Adjustable Dimension 86 86...

Page 2: ...ice is well mounted power on and it is ready to operate L N COM NC NO L N Passive com Normal open Normal close L N COM L N Valve NC NO T T T T Sensor Sensor L N T T L N Elec OUT Sensor 1 Passive Wall...

Page 3: ...is 5 37 41 99 Then press S4 or S5 can adjust the value Press S3 or wait 25 seconds without any key operation will save the setting and return back to the normal operation interface Auto Mode The chan...

Page 4: ...o the normal working interface In this time vacation mode icon displays and device will follow the setting Long press S2 again will end vacation mode and resume to normal work vacation mode icon will...

Page 5: ...display the indoor temperature and high temperature protection icon When it is under high temperature protection high temperature protection icon flickers Humidity display operation In normal working...

Page 6: ...o Away heating mode Vacation Users can set these 4 modes via COMMAND_CLASS_THERMOSTAT_MODE And COMMAND_CLASS_BASIC can switch among Heating mode Energy saving heating mode COMMAND_CLASS_THERMOSTAT_SET...

Page 7: ...24 hours P05 EH negative deadband 1 5 3 0 0 10 0 0 18 WH negative deadband 0 5 1 0 0 10 0 0 18 P06 EH positive deadband 0 0 00 0 0 10 0 0 18 WH Temp positive deadband 0 5 1 0 0 10 0 0 18 P07 Anti fre...

Page 8: ...t OC OC OF OC Celsius OF Fahrenheit P18 Restore factory setting Display 53 Password 55 00 99 Change 53 to 55 and press S3 to confirm Please use this procedure only when the network primary controller...