background image

A.Y. McDonald Mfg. Co.

2 HP Grinder Pumps

3210-676  2/21

800.292.2737  |  [email protected]  |  aymcdonald.com

5

Troubleshooting

PROBLEM

CAUSE

CORRECTION

Pump will not run.

1. Poor electrical connection, blown fuse, tripped 

breaker or other interruption of power, improper power 

supply.
2. Motor or switch inoperative (to isolate cause, go to 

manual operation of pump).
2a. Float movement restricted.
2b. Switch will not activate pump or is defective.

3. Insufficient liquid level.

1. Check all electrical connections for security. Have electrician 

measure current in motor leads. If current is or-20% of locked 

rotor amps, impeller is probably locked. If current is 0, overload may 

be tripped. Remove power, allow pump to cool, then re-check current.

2a. Reposition pump or clean basin as required to provide adequate 

clearance for float.

2b. Disconnect level control. Set ohmmeter for a low range, such as 

100 ohms full scale and connect to level control manually and check 

to see that ohmmeter shows zero ohms for closed switch and full 

scale for open switch. (Float Switch)

3. Make sure liquid level is at least equal to suggested turn-on point.

4. Re-check all sizing calculations to determine proper pump size.

5. Check discharge line for restrictions, including ice if line passes 

through or into cold areas.

6. Remove and examine check valve for proper installation and 

freedom of operation.

7. Open valve.

8.  Check  cutter  for  freedom  of  operation,  security  and  condition. 

Clean cutter and inlet of any obstruction.

9. Loosen union slightly to allow trapped air to escape. Verify that 

turn-off level of switch is set so that the suction is always flooded. 

Clean vent hole.

10. Remove & examine for damage. Replace pump stator if required.

11. Repair fixtures as required to eliminate leakage.

12. Check pump temperature limits & fluid temperature.

13. Replace portion of discharge pipe with flexible connector.

14. Turn to automatic position.

15. Check for leaks around basin inlet and outlets.

Pump will not turn off.

2a. Float movement restricted.
2b. Switch will not activate pump or is defective.

4.  Excessive  inflow  or  pump  not  properly  sized  for 

application.

9. Pump may be air locked.

14. H-O-A switch on panel is in “Hand” position.

Pump hums but does not run.

1. Incorrect voltage.

8. Cutter jammed or loose on shaft, worn or damaged, 

inlet plugged.

Pump delivers insufficient 

capacity.

1. Incorrect voltage.

4.  Excessive  inflow  or  pump  not  properly  sized  for 

application.
5. Discharge restricted.
6. Check valve stuck closed or installed backwards.
7. Shut-off valve closed.

8. Cutter jammed or loose on shaft, worn or damaged, 

inlet plugged.

9. Pump may be airlocked.

10. Pump stator damaged / torn.

Pump cycles too frequently or runs 

periodically  when  fixtures  are  not 

in use.

6. Check valve stuck closed or installed backwards.
11. Fixtures are leaking.
15. Ground water is entering basin.

Pump shuts off and turns on 
independent of switch, (trips 
thermal overload protector). 

CAUTION: 

Pump may start 

unexpectedly. Disconnect power 
supply. 

1. Incorrect voltage.

4.  Excessive  inflow  or  pump  not  properly  sized  for 

application.

8. Cutter jammed, loose on shaft, worn or damaged, 

inlet plugged.
12. Excessive water temperature.

Pump operates noisily or vibrates 
excessively.

4. Operating at too high / low of pressure .
5. Discharge restricted.

8. Cutter broken.

13. Piping attachments to building structure too rigid 
or too loose.

CAUTION! 

Always disconnect the pump from the electrical power source before handling. If the system fails to operate properly, carefully read instructions and 

perform maintenance recommendations. If operating problems persist, the following chart may be of assistance in identifying and correcting them:

MATCH “CAUSE” NUMBER WITH CORRELATING “CORRECTION” NUMBER.

NOTE: All 3 Phase Models Check Proper Rotation - Cause Low Performance, Noise, and Vibration

NOTE: Not all problems and corrections will apply to each pump model.

Summary of Contents for 120912GRP

Page 1: ...ld com aymcdonald com 1 120912GRP 120212GRP Installation Instructions IMPORTANT NOTICE READ CAREFULLY READ ALL INSTRUCTIONS IN THIS MANUAL BEFORE OPERATING PUMP PLEASE FILL OUT THE START UP REPORT ON...

Page 2: ...nated as necessary prior to shipment to insure that employees will not be exposed to health hazards in handling said material All applicable laws and regulations shall apply Bronze brass and bronze br...

Page 3: ...h a 3 year from the date of manufacturing warranty against defects in material or workmanship In addition your pump must be installed in accordance with the installation instructions If you have a cla...

Page 4: ...AL MOISTURE SENSOR A detector is installed in the pump seal chamber which will detect any moisture present It is recommended that this detector Black White wires be connected in series to an alarm dev...

Page 5: ...ion of discharge pipe with flexible connector 14 Turn to automatic position 15 Check for leaks around basin inlet and outlets Pump will not turn off 2a Float movement restricted 2b Switch will not act...

Page 6: ...SEAL MOTOR 3450 RPM 60 HZ NEMA L 1 PHASE PART CONSTRUCTION SIZE SHAFT SEAL SINGLE SEAL CARBON CERAMIC BUNA N ELASTOMER 300 SERIES STAINLESS STEEL SHAFT SEAL DOUBLE SEAL TANDEM DOUBLE MECHANICAL UPPER...

Page 7: ...PACITOR KIT 6190 021 OR WARRANTY IS VOID Date Installed Does impeller turn freely by hand YES NO Condition of cord jacket Good Fair Poor Was equipment stored How long Liquid being pumped Debris in bot...

Page 8: ...4800 Chavenelle Road Dubuque IA 52002 1 800 AY CARES aymcdonald com aymcdonaldu com WITHOUT YOU THERE IS NO US 292 2737...

Reviews: