MCDonald 120912GRP Installation Instructions Manual Download Page 4

A.Y. McDonald Mfg. Co.

2 HP Grinder Pumps

3210-676  2/21

800.292.2737  |  [email protected]  |  aymcdonald.com

4

INSTALLATION

 

The pump is provided with a leg kit in case a rail lift out system is not used. A minimum of 

3” clearance must be maintained between the pump and the basin bottom. If the feet are 

to be used, install the rubber threaded feet and lock with nut to ensure 3” clearance under 

pump for proper clearance of solids to enter pump inlet.
Assemble discharge piping or hose assembly to the pump. Discharge piping should be 

as short as possible. Both a check valve and a shut off valve are required for each pump 

being used. The check valve is used to prevent backflow into the sump. Excessive backflow 

can cause flooding and/or damage to the pump. The shut-off valve is used to stop system 

flow during pump or check valve servicing. If pump is installed with a discharge hose 

rather than a moveable fitting assembly, make sure the discharge pipe has a 1/8” hole 

approximately 5” from tend nearest volute and oriented towards the pump body.

ELECTRICAL CONNECTIONS

 

Breaker Recommendations:

 

25 AMP

 (208V-230V Single Phase): 

20AMP

 (208V-230V Three 

Phase): 

15AMP

 (460V Three Phase). The quick connect cord assembly mounted to the pump 

must not be modified in any way except for shortening to a specific application. Any supply 

cables connections between the pump and the control panel must be made in accordance 

with the National Electric Code or the Canadian Electric Code and all applicable state, 

province and local electric codes. It is recommended that a junction box, be mounted 

outside the sump or be of at least Nema 4 (EEMAC-4) construction if located within the wet 

well. The Ground Wire of pump is marked with an “E” for earth ground and is a Blue-Green 

Color. 

DO NOT USE THE POWER OR CONTROL CABLES TO LIFT PUMP!

Check winding resistance of pump power cable before installation. The OHM readings should 

be approximately: Single Phase Models: Black to White or across blades -1.3ohms; Three Phase 

Models: Black to White – 1.3ohms; Red to White – 3.7ohms; Black to Red – 2.4ohms.

THREE PHASE GRINDER INSTALLATION:

 Check proper rotation. Improper motor rotation can 

result in poor pump performance and pump failure. The power leads are the red, black and 

white wires. There should be approximately an equal ohm resistance between these leads 

of approximately 1.6ohms for 230 Volt connection and 6.2 ohms for 460Volt. The bluegreen 

color lead is the ground wire. Once the leads are connected to the power terminals then 

you are ready to check the rotation. Momentarily apply power to the pump with it laying on 

its side and impeller clear from obstruction. Observe “kickback” as it should always be in 

counter-clockwise direction as viewed from top of the motor housing or opposite to impeller 

rotation. If rotation is incorrect when power is supplied, then reverse two of the leads at the 

power terminal and try again. This should correct the rotation. Once pump is in operation 

the amperage of each leg of the power connection should be checked and recorded on 

the start up sheet. They should be close to the same value for each leg (within 5% of the 

average leg to leg value). If they are not, try advancing the connections to balance the 

readings, but do not lose proper rotation.

If  additional  cord  is  required,  consult  a  qualified  electrician  for  proper  wire  size.  On 

single phase models, the type of inwinding overload protector used is referred to as an 

inherent overheating protector and operates on the combined effect of temperature and 

current. This means that the overload protector will trip out and shut the pump off if the 

winding becomes too hot, or the load current passing through them becomes too high. 

It will then automatically reset and start the pump up after the motor cools to a safe 

temperature. All three phase models are not automatically protected. They do have on 

winding thermal sensors accessed through the sensor cord (Black and Green wires) that 

need to be connected to an approved protection and or alarm circuitry in the panel for 

winding thermal protection. 

Thermal protection shall not be used as a motor overload 

device. A separate motor overload device must be provided in accordance with NEC 

codes.

 In the event of an overload, the source of this condition should be determined 

and rectified immediately. DO NOT LET THE PUMP CONTINUE TO RUN IF AN OVERLOAD 

CONDITION OCCURS. Full load amps are 15 amps for 230 Volt single phase; 17amps for 

208 Volt single phase; 11.0, 9.0, & 4.5 amps for 208V, 230V, & 460V three phase models. 

OPTIONAL MOISTURE SENSOR

 A detector is installed in the pump seal chamber which 

will detect any moisture present. It is recommended that this detector (Black & White 

wires) be connected in series to an alarm device or the motor starter coil to alert the 

operator that a moisture detect has occurred. In the event of a moisture detect, check 

the individual moisture sensor probe leads for continuity and the junction box/control box 

for moisture content. This situation may induce a false signal in the moisture detecting 

circuit. Normal resistance between leads is 33,000 OHMS indicating normal connection. 

When the resistance drops well below 33,000 OHMS, then moisture is present and the 

pump seals should be serviced. If none of the above tests prove conclusive, the pump(s) 

should be pulled and the source of the failure identified and repaired. 

IF A MOISTURE 

DETECT HAS OCCURRED, SCHEDULE MAINTENANCE AS SOON AS POSSIBLE.
SERVICE

Lubrication:

 Anytime the pump is removed from operation, the cooling oil in the motor 

housing should be checked visually for oil level and contamination.

Checking Oil:

 

To check oil in the motor housing, set pump upright. Remove plug from 

motor housing. With a flashlight, visually inspect the oil in the motor housing to make sure 

it is clean and clear, light amber in color and free from suspended particles. Milky white 

oil indicates the presence of water. Oil level should be just above the motor when pump is 

in the vertical position.

Testing Oil: 

 Place pump on it’s side, remove plug from motor housing and drain oil into 

a clean, dry container. Check oil for contamination using an oil tester with a range to 30 

Kilovolts breakdown. If oil is found to be clean and uncontaminated (measuring above 

15KV. Breakdown), refill the motor housing. (See Replacing Oil below) If oil is found to be 

dirty or contaminated, the pump must be carefully inspected for leaks at the shaft seals, 

cord assemblies, O-rings, and plugs before refilling with oil. To locate the leak, perform 

a pressure test. After leak is repaired, dispose of old oil properly, and refill with new oil.

Replacing Motor Housing Oil:

 

 

Drain all oil from motor housing and dispose of properly 

per local and environmental standards. Set unit upright and refill with new cooling oil. Fill 

to just above motor (approximately 66oz) as an air space must remain in the top of the 

motor housing to compensate for oil expansion. Apply pipe thread compound to threads on 

plug and insert and tighten into housing.

Replacing Seal Chamber Oil:

 

Drain all oil from seal chamber and dispose of properly per 

local and environmental standards. Set unit on its side, with plug upward, and refill with 

new oil. (approximately 13oz) Apply pipe thread compound to threads on plug and insert 

and tighten into housing.

WARNING!

 Do not overfill oil. Over filling of oil can create excessive and dangerous hydraulic 

pressure which can destroy the pump and create a hazard. Overfilling oil voids warranty.

DIELECTRIC COOLING OIL:

 BP – Enerpar SE100: Conoco – Pale Paraffin 22; Mobile – 

D.T.E. Oil Light; G&G Oil – Circulating 22; Imperial Oil – Voltesso-35; Shell Canada – 

Transformer-10; Texaco – Diala-oil-AX; Woxo – Premium 100.

Pressure Test for pumps that have not been disassembled:

 If the pump has been 

disassembled, the oil should be drained before a pressure test. Remove plug from motor 

housing. Apply pipe sealant to a pressure gauge assembly and tighten into hole. Pressurize 

motor housing to 10 P.S.I. Use soap solution around the sealed areas and inspect joints for 

“air bubbles”. If, after five minutes, the pressure is holding constant, and no signs of leaks 

are observed, slowly bleed the pressure and remove the gauge assembly. Replace oil. If the 

pressure does not hole, then the leak must be located and repaired.

CAUTION!

 Pressure builds up extremely fast. Too much pressure will damage seal.

Pressure Test for pumps that have not been disassembled:

 The pressure test may be 

done with the oil at its  normal level. Remove plug from motor housing. Apply pipe sealant 

to a pressure gauge assembly and tighten into hole. Pressurize motor housing to 10 P.S.I. 

Use soap solution around the sealed areas above the oil level and inspect joints for “air 

bubbles”. For sealed areas below the oil level, leaks will seep oil. If, after five minutes, the 

pressure is holding constant, and no signs of leaks are observed, slowly bleed the pressure 

and remove the gauge assembly. Replace oil. If the pressure does not hole, then the leak 

must be located and repaired.

Seal Chamber Pressure Test:

 Set unit on its side with fill plug downward, remove plug 

and drain all oil from seal chamber. Apply pipe sealant to pressure gauge assembly and 

tighten into hole in seal plate.
Pressurize seal chamber to 10 P.S.I. and check for leaks as outlined above.

User Guide

Summary of Contents for 120912GRP

Page 1: ...ld com aymcdonald com 1 120912GRP 120212GRP Installation Instructions IMPORTANT NOTICE READ CAREFULLY READ ALL INSTRUCTIONS IN THIS MANUAL BEFORE OPERATING PUMP PLEASE FILL OUT THE START UP REPORT ON...

Page 2: ...nated as necessary prior to shipment to insure that employees will not be exposed to health hazards in handling said material All applicable laws and regulations shall apply Bronze brass and bronze br...

Page 3: ...h a 3 year from the date of manufacturing warranty against defects in material or workmanship In addition your pump must be installed in accordance with the installation instructions If you have a cla...

Page 4: ...AL MOISTURE SENSOR A detector is installed in the pump seal chamber which will detect any moisture present It is recommended that this detector Black White wires be connected in series to an alarm dev...

Page 5: ...ion of discharge pipe with flexible connector 14 Turn to automatic position 15 Check for leaks around basin inlet and outlets Pump will not turn off 2a Float movement restricted 2b Switch will not act...

Page 6: ...SEAL MOTOR 3450 RPM 60 HZ NEMA L 1 PHASE PART CONSTRUCTION SIZE SHAFT SEAL SINGLE SEAL CARBON CERAMIC BUNA N ELASTOMER 300 SERIES STAINLESS STEEL SHAFT SEAL DOUBLE SEAL TANDEM DOUBLE MECHANICAL UPPER...

Page 7: ...PACITOR KIT 6190 021 OR WARRANTY IS VOID Date Installed Does impeller turn freely by hand YES NO Condition of cord jacket Good Fair Poor Was equipment stored How long Liquid being pumped Debris in bot...

Page 8: ...4800 Chavenelle Road Dubuque IA 52002 1 800 AY CARES aymcdonald com aymcdonaldu com WITHOUT YOU THERE IS NO US 292 2737...

Reviews: