21
2. Technical Gas Data
a. Gas Specifications
Shaded areas are stated in metric equivalents
* Measured at gas valve pressure tap when gas valve is on.
F.N.P.T. = Female National Pipe Thread
b. Natural Gas
Regulation is controlled by each gas valves internal regulator. Incoming supply pressure
must be
consistent between a minimum of 6.0 inches (14.92 mb) and a maximum of 12.0 inches (29.9 mb) water
column (W.C.) pressure.
c. Liquid Propane (L.P.) Gas
Dryers made for use with L.P. gas have the gas valves internal pressure regulator blocked open so that
the gas pressure
must be
regulated upstream of the dryer. The pressure measured at each gas valve
pressure tap
must be
a consistent 10.5 inches (26.1 mb) water column. There is no regulator or
regulation provided in an L.P. dryer. The water column pressure
must be
regulated at the source (L.P.
tank) or an external regulator
must be
added to each dryer.
7<3(2)*$6
1$785$/
/,48,'3523$1(
0DQLIROG3UHVVXUH
LQFKHV:&
PE
LQFKHV:&
PE
,Q/LQH3UHVVXUH
LQFKHV:&
PE
LQFKHV:&
PE
*DV,QOHW6L]H(DFK%DVNHW>7XPEOHU@
´)137
%WXKU,QSXW(DFK%DVNHW>7XPEOHU@
NFDOKU
%WXKU,QSXW7RWDOIRU%RWK%DVNHWV>7XPEOHUV@
NFDOKU