background image

6-7

07/02

COMMERCIAL MULTI LOAD DRYERS - MDG30, MC2, PC2, PNA, and MNA

IMPORTANT VENTING REMINDERS

1.

Duct work size and installation  

should be

 done by a qualified professional.

2.

The dryer 

must be

 exhausted to the outdoors.

3.

Duct work 

should be

 routed as short as  possible to the outdoors with as few elbows as possible.

4.

Avoid 90

°

 turns, use 30

°

 or 45

°

 turns instead. Long radius turns offer reistance to airflow.

5.

The size of the duct work 

should be

 a minimum 

of 10 inches if vented vertically and 8 inches if vented horizontally.

6.

The inside duct work 

should be

 as smooth as possible with no projections from sheet metal screws.

Ducts 

should overlap

 the duct to which it is to be connected.

7.

All

 duct joints 

should be

 taped to prevent moisture and lint form escaping into the building.

8.

Inspection or clean out doors 

should be

 installed at strategic points in the duct work for periodic inspection and

cleaning.

9.

Where ever the duct passes through combustible materials, the opening must be 2 inches larger (all the way around)
than the duct. The duct must be centered within this opening.

10. The outside of the duct work must be protected from the weather. A 90

°

 elbow 

should be

 used for horizontal run

and when vertically through a roof by using a 180

°

 turn to point the opening downward. The distance between the

exhaust duct and the nearest obstruction (i.e., roof or ground) 

must be

 twice the diameter of the duct.

11.

DO NOT

 use screens or caps on the outside of the exhaust duct work.

12. Exhaust back pressure measured by a manometer at the dryer exhaust duct area 

must not

 exceed 0.3 inches of

water  column (W. C.).

13. WARNING - DRYER 

MUST NEVER BE

 OPERATED WITH OUT THE LINT FILTER and SCREEN IN PLACE.

14. Exhaust duct work outlets 

should not be

 located in an area directly where the makeup air openings are located.

15. Make-up air opening must be a minimum of one square foot for each dryer. Common make-up openings are

acceptable.

Summary of Contents for MDG30PCCWW

Page 1: ...lbs 250 Kg Uncrated 500 lbs 227 Kg Gas Inlet 1 2 I D ELECTRICAL REQUIREMENTS 120 volts 60 Hz single phase some 240 volts 50 Hz models available for export Individual branch circuit serving only the dr...

Page 2: ...ich it is connected ALL duct work joints must be taped to prevent moisture and lint from escaping into the building Additionally inspection doors should be installed at strategic points in the exhaust...

Page 3: ...single 8 inch venting is used the duct work to the outlet cannot exceed 30 feet refer to Illus A below This calculation of 30 feet compensates or allows for the use of a maximum of only one 1 elbow RE...

Page 4: ...ard outside outlet Illus B VERTICAL SINGLE DRYER VENTING NOTE A OPENING MUST BE TWO 2 INCHES LARGER THAN THE DUCT ALL THE WAY AROUND THE DUCT MUST BE CENTERED WITHIN THIS OPENING If the length of the...

Page 5: ...cted to one 1 main common duct run The main common duct may be any shapes so long as the minimum cross section area is provided The main duct should be tapered with the diameter in creasing before eac...

Page 6: ...mum of three 3 elbows including the two 2 elbows creating the 180 turned down ward outside outlet protection IMPORTANT No more than four 4 dryers maximum should be connected to one 1 main common duct...

Page 7: ...he duct work for periodic inspection and cleaning 9 Where ever the duct passes through combustible materials the opening must be 2 inches larger all the way around than the duct The duct must be cente...

Page 8: ...air openings are acceptable IMPORTANT Makeup air must be provided from a source free of contaminating fumes such as dry cleaning fumes Make up air contaminated by dry cleaning solvent fumes will resu...

Reviews: