18
Maytag Co.
113395 - 6
4. Multiple Dryer (Common) Venting
IMPORTANT:
For extended ductwork runs, the cross-sectional area of the ductwork can only be
increased to an extent. When the ductwork approaches the maximum limits as noted
in this manual, a professional heating, ventilating, and air-conditioning (HVAC) firm
should be
consulted for proper venting information.
If it is not feasible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be
channeled into a “common main duct.” The individual ducts should enter the bottom or side of the main
duct at an angle not more than 45º in the direction of airflow. The main duct
should be
tapered, with the
diameter increasing before each individual duct is added.
IMPORTANT:
No more than 4 dryers for the MDG-120 and only 3 for the MD-170
should be
connected to 1 main common duct.
The
illustration below
shows the minimum cross-sectional area for multiple dryer round or square venting.
These figures
must be
increased if the main duct run from the last dryer to where it exhausts to the
outdoors is longer than 12 feet (3.656 meters) or has more than 1 elbow in it.
A = MDG-120 14-inch (35.56 cm)
MDG-170 18-inch (45.72 cm)
MDS-170 20-inch (50.8 cm)
B = 20 feet (6.10 meters)
Multiple Dryer Venting with 14-inch (35.56 cm) Diameter
2,150 cfm (60.88 cmm) Exhaust Connections at Common Duct
NUMBER OF DRYERS
3
2
1
MINIMUM CROSS-
SECTIONAL AREA
SQ IN
707
531
315
SQ CM
4561
3426
2032
MINIMUM ROUND
DUCT DIAMETER
IN
30
26
20
CM
76
66
51
MDS-170
NUMBER OF DRYERS
3
2
1
MINIMUM CROSS-
SECTIONAL AREA
SQ IN
615
455
255
SQ CM
3967
2935
1645
MINIMUM ROUND
DUCT DIAMETER
IN
28
24
18
CM
71
61
46
MDG-170
NUMBER OF DRYERS
4
3
2
1
MINIMUM CROSS-
SECTIONAL AREA
SQ IN
455
380
255
115
SQ CM
2935
2452
1645
742
MINIMUM ROUND
DUCT DIAMETER
IN
24
22
18
14
CM
60
55
45
35
MDG-120
Multiple Dryer Venting with 18-inch (45.72 cm) Diameter
3,700 cfm (104.77 cmm) Exhaust Connections at Common Duct
Multiple Dryer Venting with 20-inch (50.8 cm) Diameter
4,400 cfm (124.59 cmm) Exhaust Connections at Common Duct
NOTE 1
Opening from combustible materials
must be
2-inches (5.08 cm) larger than the
duct (all the way around). The duct
must be
centered within this opening.
NOTE 2
Distance
should be
2 times the diameter of the duct to the nearest obstruction.