13
6.0
Installation
6.1 A
DJUSTING THE
D
AMPER
R
OD
(F
OR
ERV
S
I
NSTALLED IN
W
ARM
R
EGIONS
)
Refer to Section 4.2 and observe the difference in the damper
position at the right in diagrams Defrost Mode 1 and Defrost Mode 2:
for Defrost Mode 1 the damper is completely closed, whereas
for Defrost Mode 2 the damper is half closed. At the factory, all ERVs
are assembled for defrost Mode 2. Therefore, if your installation
is for an ERV in a warm region (zone D as defined in Section 3),
the rod must be moved to position 1 (see figure 5).
NOTE: Before attempting to change the position of the damper
rod, place the unit on a table for easy access and remove
the recovery core.
6.2 L
OCATING AND
M
OUNTING THE
U
NIT
Choose an
appropriate location
for the unit:
•
Within an area of the house where the temperature is above 10°C /
50°F (basement, attic, furnace room, laundry room, etc.).
•
Away from living areas (dining room, living room, bedroom), if possible.
•
So as to provide easy access to the interior cabinet and to
the control panel on the right hand side of the unit.
•
Close to an exterior wall, so as to limit the length of the insulated
flexible duct to and from the unit.
•
Close to a drain. If no drain is close by, use a pail to collect
run-off.
•
Away from hot chimneys, electrical panel and other fire haz-
ards.
•
Allow for a power source (110 V standard outlet).
Hang the unit to ceiling joists with the 4 chains and
springs provided (see figures 6 and 7).
VD0064
VD0038
figure 6
figure 7
CAUTION
Make sure the unit is level.
CAUTION
This is a delicate operation: to avoid injury proceed carefully and use the appropriate tools.
VO0015
O00 5
1
2
figure 5
I
NSPECT THE
C
ONTENTS OF THE
B
OX
•
Inspect the
exterior of the unit
for shipping damage. Ensure that there is no damage to the door, door
latches, door hinges, dampers, duct collars, cabinet, etc.
•
Inspect the
interior of the unit
for damage. Ensure that the fan motor assembly, recovery core, insulation,
dampers, damper actuator and drain pan are all intact.
•
If the unit was damaged during shipping, contact your local distributor. (Claim must be made within
24 hours after delivery.)
•
Use checklist included with the unit to ensure that no parts are missing.