Installation and Operating Instructions for 
EAS

®

-Sm/Zr Switch Gear 

Type 010.000.2

 

 

(B.0100002.GB) 

 

 

 

Page 5 of 6 
 
 
10/03/2005 CB/KR/TH 

 

Chr. Mayr GmbH + Co. KG  Telephone 08341/804-241 
Eichenstraße 1 

Fax 08341/804-422 

D-87665 Mauerstetten 

http://www.mayr.de 

Germany 

eMail: [email protected] 

 

 

 

 

 

Antriebstechnik 

 

 

 

Installation / Connection examples 

(continuation)

 

 

Installation of a smoothing choke 

 

The  installation  of  a  smoothing  choke  in  the  coil  circuit  is 
necessary, when the standard cable of the clutch is lengthened. 
Reason: it is possible that the max. adjustable torque may not be 
achieved  due  to  the  cable  lengthening.  The  connection  is  to  be 
provided in direct proximity of the control unit and at the terminal 
Ku2. 
The  smoothing  choke  belongs  to  the  delivery  range  and  can  be 
used for all sizes. 
Technical data:  135 mH, 2 Amp. LxBxH 85x90x95 mm 
Repeat order under:  Art. No.0802841.  

 

Ku1

Ku2

Smoothing choke

C

lu

tc

h

Shielded connecting lead

Coil connection

EAS -Sm/Zr Control unit 

®

//

//

®

 

 
Connection signalling relay and clutch 

 

2

1

2

2

2

4

Signalling relay 2

overtemperature

250 VAC/10A

1

4

1

1

1

2

Signalling relay 1

overload

250 VAC/10A

K

u

1

K

u

2

Coil

clutch

96VDC

 

 
Connection of EAS

®

-Sm/Zr-clutches 

 

Please  observe!  The  EAS

®

-Sm/Zr-control  unit  is 

adjusted to the corresponding size of the clutch at the 
factory.
  In  case  other  sizes  are  connected 
malfunctions  can  be  caused.  Therefore,  compare  the 
sizes of the control unit and clutch.  

 

Comparision table: 

 

EAS

®

-Sm/Zr- 

EAS

®

-Sm/Zr- 

control unit 

clutch 

 
Size/Type/Power 

connected with

 

Size/Type/Power 

 

0/010.000.2/36 Watt 

0/400.03x.x/36 Watt 

1/010.000.2/46 Watt 

1/400.03x.x/46 Watt 

2/010.000.2/57 Watt 

2/400.03x.x/57 Watt 

3/010.000.2/73 Watt 

3/400.03x.x/73 Watt 

4/010.000.2/105 Watt 

4/400.03x.x/105 Watt 

 

0/010.000.2/30 Watt 

0/400.00x.x/30 Watt 

1/010.000.2/40 Watt 

1/400.00x.x/40 Watt 

2/010.000.2/45 Watt 

2/400.00x.x/45 Watt 

3/010.000.2/65 Watt 

3/400.00x.x/65 Watt 

4/010.000.2/120 Watt 

4/400.00x.x/120 Watt 

5/010.000.2/155 Watt 

5/400.00x.x/155 Watt 

 

0/010.000.2/55 Watt 

0/400.01x.x/55 Watt 

1/010.000.2/60 Watt 

1/400.01x.x/60 Watt 

2/010.000.2/80 Watt 

2/400.01x.x/80 Watt 

3/010.000.2/105 Watt 

3/400.01x.x/105 Watt 

4/010.000.2/145 Watt 

4/400.01x.x/145 Watt 

5/010.000.2/256 Watt 

5/400.01x.x/256 Watt 

 

Note: 
Adjustment of the EAS

®

-Sm/Zr-control unit to a different clutch 

size can only be made at the factory! 
 

 

Technical data 

 

Input voltage 

230 VAC, ±10 %, 50-60 Hz 

Current consumption 

max. 4 Amp./100 % duty cycle 

Idle power consumption 

< 4 Watt 

Coil

NOM

-voltage 

96 VDC 

Coil

NOM

-power 

max. 256 Watt 

Coil

NOM

-current 

factory  setting  accordingly 
to 

mayr

®

-EAS

®

-Sm/Zr-clutch 

size    

Coil overexcitation 

2x  I

NOM, 

current  limitation  is 

adapted  to  the  respective  coil 
size. 

Torque adjustment      

25  %  up  to  100  %  of  the  coil 
current (current stabilization) 

Engaging time t

k

 

5 seconds ±30 % 

Protection 

IP 20 

Ambient temperature 

0 °C up to +50 °C 

Storage temperature 

-20 °C up to +70 °C 

Conductor cross section 

             2,5 mm

2  

/ AWG 30-12 

Weight 

1,5 kg / 3,31 lb 

Fuse protection 
Mains fuse 

F1/F2, (4 AMT, 5x20 mm) 

Load fuse 

F3,  the  current  is  adapted  to 
the  mayr

®

-clutch  size.  Always 

use the same spare fuses.  

Overvoltage category   

II (two), EN 50178 - 04/1998 

Overvoltage protection 

For 

the 

installation 

overvoltage  category  III,  a 
suitable 

overvoltage 

protection 

is 

required 

between  the  input  voltage 
and  the  EAS

®

-Sm/Zr  control 

unit. 

 
Temperature monitoring of the EAS

®

-Sm/Zr control unit 

A  fitted  temperature  switch  prevent  the  overheating  of  the  control 
unit.     

 

Switch OFF 

with >80 °C operating temperature the coil voltage 
gets switched off. 

New start 

only  possible,  when  the  EAS

®

-Sm/Zr  control  unit 

cooled down below 40 °C. 

Reset 

by switching the input voltage OFF and ON. 

 
Temperature monitoring of the clutch coil 
The  temperature  monitoring  of  the  coil  can  only  be  made  with  a 
fitted PTC resistor. The PTC resistor is connected to the terminals 
P1/P2. 

 

Pre-warning  with >+130 °C operating temperature  
 

The coil voltage gets not switched-off yet.   

Switch OFF 

with >+135 °C operating temperature 

 

The coil voltage is switched off.       

New start 

only  possible,  when  the  coil  temperature  cooled 
down below +120 °C. 

Reset 

by „Start“clutch is energised. 

 
Short circuit proof coil connection 
In  case  of  a  short  circuit  between  the  coil  connections  Ku1  and 
Ku2  the  coil  voltage  is  switched  off.  Reset  of  the  short  circuit 
monitoring is made by switching-off the input voltage and removing 
the short circuit. 

 

 

Attention!  Mass  short  circuits  are  not  protected.  
Connections  Ku1  or  Ku2  against  earthed  metal 
components  cause  mass  shorts  and,  therefore,  failures 
of the units. A residual current circuit breaker protection 
against  personal  injury  and  damage  to  machinery  is 
required  by  the  customer,  which,  however,  does  not 
provide a protection against failure of the control unit.    

 

 