maxxess eMAX-LP4502 Installation Manual And Specification Download Page 1

 

 

 

 

eMAX-LP4502 

INTELLIGENT CONTROLLER 

 

Installation Guide and Specifications 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
This device complies with FCC Part 15, Class A Specifications. 
The device meets CE Specifications, and is RoHS Certified.  

This device is UL 294 Recognized.

  

February 2019

 

 

 

 

 

 

 

 

ber, 2011

 

Summary of Contents for eMAX-LP4502

Page 1: ...IGENT CONTROLLER Installation Guide and Specifications This device complies with FCC Part 15 Class A Specifications The device meets CE Specifications and is RoHS Certified This device is UL 294 Recognized February 2019 ...

Page 2: ...ation Memory 7 5 Input Power Cabinet Tamper UPS Fault Wiring 8 6 Communication Wiring 8 7 Reader Wiring 8 8 Input Circuit Wiring 10 9 Relay Circuit Wiring 11 10 Memory Backup Battery 11 11 IT Security 11 12 Status LEDs 12 13 Specifications 13 14 Warranty and Liability 15 Appendix A Configuring the eMAX EP Controllers 16 Change History Original Document Original February 2019 ...

Page 3: ... Stripe Clock Data F 2F Protocol standard or supervised or 2 wire RS 485 device signaling such as OSDP and also provides tri state LED control and buzzer control one wire LED mode only Each Reader Port if configured for 2 wire RS 485 OSDP Readers can support two 2 multi dropped Readers in an IN OUT Reader configuration resulting in the support for up to four 4 Readers The eMAX LP4502 provides four...

Page 4: ...1 READER 2 TR TR GND TB2 TR TR GND TB3 IN3 IN4 TB4 IN1 IN2 TB5 TB6 IN5 IN6 TB7 IN7 IN8 TB1 GND FLT GND VIN GND TMP RESET S2 BT1 3V BR CR2330 1 S1 ON 2 3 4 J6 J2 J8 J9 J5 IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 K 1 K 2 K 3 K 4 OUTPUT STATUS LEDs INPUT STATUS LEDs J7 PASS 12V 1 2 3 4 5 R1 R2 D16 STATUS LEDs BATTERY BR CR2330 REPLACE ANNUALLY S2 RESET SWITCH S1 DIP SWITCHES STATUS LEDs J2 ETHERNET JACK EARTH...

Page 5: ...e note 1 TB3 1 SIO Port 2 GND TB9 4 BZR Reader Buzzer TB3 2 2 wire RS 485 TR A See note 1 TB9 5 LED Reader LED TB3 3 TR B See note 1 TB9 6 VO Reader Power TB4 1 Input 2 IN2 TB10 1 Out 1 NO Normally Open Contact TB4 2 IN2 TB10 2 C Common TB4 3 Input 1 IN1 TB10 3 NC Normally Closed Contact TB4 4 IN1 TB10 4 Out 2 NO Normally Open Contact TB5 1 Input 4 IN4 TB10 5 C Common TB5 2 IN4 TB10 6 NC Normally ...

Page 6: ...Port 0 J5 OFF Port 2 RS 485 EOL Terminator is Off ON Port 2 RS 485 EOL Terminator is On J7 Reader Power Select See Note 2 12V 12 Vdc at Reader Ports PASS VIN Pass Through to Reader Ports J6 N A Micro USB port 2 0 J8 N A microSD Card J9 OFF Port 1 RS 485 EOL Terminator is Off ON Port 1 RS 485 EOL Terminator is On Note 2 Install jumper J7 in the 12V position ONLY if the input voltage VIN is greater ...

Page 7: ... address 0 Alternate Host Port Disabled Refer to online HELP in the Maxxess host software for important details on encryption NOTE See Appendix A for details on configuring the eMAX LP controller s IP address 4 Bulk Erase Configuration Memory The Bulk Erase Function can be used for the following purposes Erase all configuration and cardholder database sanitize board less 3rd Party Applications Upd...

Page 8: ...TR TR GND TB3 TR TR GND TB2 Port 1 To Serial I O Devices Port 2 To Serial I O Devices IMPORTANT NOTE Install the termination jumper ONLY on the panel at each end of the RS 485 bus Failure to do so will compromise the proper operation of the communication channel 7 Reader Wiring Each Reader Port of the eMAX LP4502 supports a reader with TTL Wiegand D1 D0 TTL Magnetic Stripe Clock Data F 2F standard...

Page 9: ...ED BZR D1 CLK TR D0 DAT TR GND TB8 or TB9 Typical D1 D0 Clock Data Reader Typical 2 Wire RS 485 Device OSDP Reader for Example Inputs on supervised F 2F readers may be unsupervised or supervised supervised shown 1 VO LED BZR D1 CLK TR D0 DAT TR GND 12 Vdc D1 GROUND DO GREEN LED F 2F Reader TB8 or TB9 VO LED BZR D1 CLK TR D0 DAT TR GND 12 Vdc D1 GROUND DO GREEN LED F 2F Reader NORMALLY CLOSED CONTA...

Page 10: ...two resistors be added to the circuit to facilitate proper reporting The standard supervised circuit requires 1k ohm 1 resistors and should be located as close to the sensor as possible Custom end of line EOL resistances may be configured via the host software NOTE Grounded and foreign voltage states are not a requirement of UL 294 and therefore not verified by UL The input circuit wiring configur...

Page 11: ...M and the real time clock are backed up by a lithium battery when input power is removed This battery should be replaced annually If data in the static RAM is determined to be corrupt after power up all data including flash memory is considered invalid and is erased All configuration data must be re downloaded Remove the insulator from the battery holder after installation Battery type BR2330 or C...

Page 12: ...4 External SIO Communication Activity Port 1 5 External SIO Communication Activity Port 2 R1 Reader 1 Clock Data or D1 D0 Mode Flashes when Data is Received Either Input F 2F Mode Flashes when Data Acknowledgment is Received RS 485 Mode Flashes when Transmitting Data R2 Reader 2 Clock Data or D1 D0 Mode Flashes when Data is Received Either Input F 2F Mode Flashes when Data Acknowledgment is Receiv...

Page 13: ...ght unsupervised supervised standard EOL 1k 1k ohm 1 watt Two unsupervised dedicated for cabinet tamper and UPS fault monitoring Output Four relays Form C with dry contacts Normally open contact NO 5 A 30 Vdc resistive Normally closed contact NC 3 A 30 Vdc resistive Reader Interface Power 12 Vdc 10 regulated 300 mA maximum each reader jumper selectable input voltage VIN must be greater than 20 Vdc...

Page 14: ...ut 1 twisted pair 30 ohms maximum typically 22 AWG 1000 ft 304 8 m Environmental Temperature 55 to 85 C storage 0 to 70 C operating Humidity 5 to 95 RHNC Mechanical Dimension 8 in 203 2 mm W x 6 in 152 4 mm L x 1 in 25 mm H Weight 10 65 oz 302 g nominal board only UL294 6th edition Performance Levels Feature Level Standby Power I Endurance IV Line Security I Destructive Attack I These specificatio...

Page 15: ...ranties implied or otherwise and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returned units are repaired or replaced from a stock of reconditioned units Returns must be accompanied by a return authorization number RMA obtained from customer service and prepaid postage and insurance Liability The Interface should only be used to con...

Page 16: ...____ _____ Gateway IP _____ ______ ______ _____ Connecting to the eMAX LP controller 1 Connect the device to a computer using a standard network cable 2 Set the computer s IP to a Statis IP Address of 192 168 6 10 3 At the eMAX LP Controller be sure to turn dipswitch 1 to the ON position This enables the use of the DEFAULT Login credentials and will time out in 5 minutes 4 Connect to the device fr...

Page 17: ...n will then appear Click on the Click Here to Login the following screens appears Log in using username admin and password password The following message will appear if you FAILED to turn Switch 1 to ON or if 5 minutes have elapsed since turning switch 1 to ON ...

Page 18: ...the controller will post a message suggesting a new user be added click OK When a new user is added it disables the default admin user It is strongly recommended that a new user account be added during this configuration process Browse to the Users link and add a user If the new user details are ever lost the controller dipswitch S1 may be used to re enable the default user Click on the Network pa...

Page 19: ...e the required IP Address Subnet Mask Default Gateway as applicable for the eMAX LP4502 If using Redundant host communication you will need to configure the Interface 2 NIC2 parameters To SAVE Click on Accept button then select the Apply Settings button ...

Page 20: ...The first check box is telling you that the Dip Switch settings must be reset to off The 2nd check box is telling you that no special User Accounts were defined If you wish to proceed check both of the check boxes then click on the Yes box to proceed You should see a message that The Board is Restarting And a selection box to CLOSE the window ...