10.1. TEST MODE
In Test Mode, manually initiated fire condition is automatically reset in a few seconds by the panel. The Test Mode causes
continuous illumination of the respective zonal Fault LED. Steps taken for entering and quitting the Test Mode are as follows:
- Set the Button Control key to Enable position. The buzzer will sound once.
- Press the Silence Buzzer button, then, keeping the button pressed, press the Silence / Sound Alarm button till Alarm / Buzzer
Silenced, FIRE and GENERAL FAULT LEDs start to illuminate.
This will take about 5 seconds.
- Zone 1 FAULT LED will start to illuminate. Move to the zone required by pressing the Silence / Sound Alarm button.
- After the zone has been selected, press the Reset button till Alarm / Buzzer Silenced, FIRE and General Fault LEDs start to
illuminate again. Continuous illumination of the zonal FAULT LED will indicate that the zone is in Test Mode.
- Set the Button Control key to Disable position. To free the zone from the Test Mode, follow the above steps once again. On
successful quit from the Test Mode, the respective zonal FAULT LED will turn off.
10.2. DISABLE MODE
In Disable Mode, a fire or fault signal from the disabled zone does not cause the panel to signal fire of fault condition. The Disable
Mode causes flashing of the respective zonal FAULT LED. Steps taken for entering and quitting the Disable Mode are as follows:
- Set the Button Control key to Enable position. The buzzer will sound once.
- Press the Silence Buzzer button, then, keeping the button pressed, press the Reset button till Alarm / Buzzer Silenced, FIRE and
General Fault LEDs start to illuminate. This will take about 5 seconds.
- Zone 1 FAULT LED will start to flash. Move to the zone required by pressing the Reset button.
- After the zone has been selected, press the Silence / Sound Alarm button till Alarm / Buzzer Silenced, FIRE and General Fault LEDs
start to illuminate again. Flashing of the zonal FAULT LED will indicate that the zone is in Disable Mode.
- Set the Button Control key to Disable position.
To free the zone from the Disable Mode, follow the above steps once again. On successful quit from the Disable Mode, the
respective zonal FAULT LED will turn off.
Zone Capacity :
Sounder Output :
Auxilary Power Output :
Fault Relay :
Fire Relay :
Fire Zone End of Line Resistor :
Sounder Circuit End of Line Resistor:
Main Supply :
Operating Voltage :
Power Supply :
Battery :
Construction:
Surface :
Mounting :
Standard Colour :
Operating ambient temperature :
Operating ambient humidity:
Size:
2, 4, 6, 8, 16
24 V DC 500 mA automatic fuse protect
24 V DC 500 automatic fuse protect
30 V DC 1A dry contact
30 V DC 1A dry contact
6,8 kΩ
10 kΩ
230 V AC 50 Hz (2A glass fuse protected)
24 V DC
1,5A
2 x 12 V DC 7 Ah
Cabinet; 1,2 mm fascia, 1,5 mm sheet steel
Epoxy
Surface
Grey metal box, white panel face
(-10°C) - (+55°C)
%0 - 95
400 x 300 x 100 mm
10- MENU MODES
11- TECHNICAL SPECIFICATION
Page 7/16
KK-642.042 Rev.No:0 01.11.12 ML-221XX User Manual
Summary of Contents for ML-221XX series
Page 11: ...Page 11 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Annex A Panel Wiring Diagram...
Page 13: ...Page 13 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Annex C1 Panel Serigraphy...
Page 14: ...Page 14 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Annex C2 Panel Serigraphy...
Page 15: ...Page 15 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Annex C3 Panel Serigraphy...
Page 16: ...Page 16 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Annex C4 Panel Serigraphy...