Electrical Connection:
1.
Loosen the twelve pcs of M6 hexagon bolts of Tank Cover at torque value 7 N-m.
2.
The thread of entry hole of Tank is 3/4” NPT. Connect the Tank to suitable conduit.
3.
Inset the wire from outside through the conduit and the entry hole of Tank, and then connect to wire connectors.
4.
Connect the branch circuit wires as following:
Brown-wire connects to Line (WALL SWITCH)
White-wire connects to Neutral
Green-wire connects to Ground
Black-wire connects to Line
5.
Connecting converter connector
6.
Re-attach the Tank Cover and tight it by eight pcs of M6 hexagon bolts of Tank Cover at torque value 7 N-m.
7.
Check the tightness of conduit and Tank Cover.
Installation & Operation
Ceiling Mount:
Expansion bolts
(Washers included) M10
Operating Instructions MaxLite Hazardous Location Linear Light