Table of ConTenTs

1

Series 44 Installation Instructions

and field service checklist

© 2008 Maxitrol Company, All Rights Reserved

SyStem ComponentS 

Amplifiers

A1044U

A1044 Amplifier

A1044U (replaces all A1044L1, suitable re-

placement for A1044 [C,D,E,H]) (includes 0, 

10, or 20 second low fire start capability.)

A1044UF (replacement for A1044FL1)

A1044UG (replacement for A1044G[L1])

A1044 (min. 40° to 80° F/ max. 80° to 140° F) 

A1044C (min. 20° to 60° F/ max. 80° to 140° F) 

A1044D (min. 20° to 60° F/ max. 35° to 75° F) 

A1044E (min. 20° to 60° F/ max. 60° to 120° F)

A1044G (min. 40º to 80º F / max. 160º to 210º F)

A1044H (min. 40º to 80º F / max. 100º to 160º F)

note:

   Amplifier and Discharge Tempera

-

ture Sensor must have same temperature 

range to be compatible.

Discharge Temperature Sensors: use with Mixing Tube

Sensors compatible with A1044U:

TS144 (min. 40° to 80° F/max. 80° to 140° F)

TS144C (min. 20° to 60° F/max. 80° to 140° F)

TS144D (min. 20° to 60° F/max. 35° to 75° F)

TS144E (min. 20° to 60° F/max. 60° to 120° F)

TS144H (min. 40º to 80º F / max. 100º to 160º F)

Sensors compatible with A1044UF:

TS144F (min. 40º to 80º F / max. 60º to 95º F)

Sensors compatible with A1044UG:

TS144G (min. 40º to 80º F / max. 160º to 210º F)

Mixing Tubes: used with sensors

MT1-9 or MT2-9 (9” length)

MT1-12 or MT2-12 (12” length)

MT1-23 or MT2-23 (23” length)

MT1-28 or MT2-28 (28” length)

MT1-57 (57” length)

Valves

M411 (3/8” & 1/2” pipe size)

M511 (1/2” & 3/4” pipe size)

M611 (3/4” & 1” pipe size)

MR212D (1”, 1¼”, 1½  pipe size)

MR212E (1½” & 2” pipe size)

MR212G (2½” & 3” pipe size)

MR212J (4” flanged)

MR212D-2, E-2, G-2 & J-2 (same pipe 

sizes as MR212D-J except used for 2-

speed blower or dual fuel operation)

note:

 M (Modulator) valve requires an 

upstream pressure regulator for low fire & 

high fire settings. MR (Modulator/Regula

-

tor) valve requires no upstream pressure 

regulator up to 5 psi inlet.

Selectrastat (Senses and Selects)

T244 (55° to 90° F) 

T244A (40° to 80° F)

or optional pair to replace 

Selectrastat

Space temperature Selector

TD244 (wall mount 55° to 90° F)

TD244A (wall mount 40° to 80° F)

TD244P (panel mount 55° to 90° F)

TD244AP (panel  mount 40° to 80° F)

Space temperature Sensor

TS244 (55° to 90° F)

TS244A (40° to 80° F) 

note: 

Space Temperature 

Selector and Space Tem

-

perature Sensor must have 

same temperature range to be 

compatible.

Summary of Contents for Selectra

Page 1: ...x 80 to140 F TS144C min 20 to60 F max 80 to140 F TS144D min 20 to60 F max 35 to75 F TS144E min 20 to60 F max 60 to120 F TS144H min 40 to80 F max 100 to160 F Sensors compatible with A1044UF TS144F min...

Page 2: ...w fire start duration A discharge air temperature sensor and mixing tube is a means of limiting the minimum and maximum discharge air temperature The amplifier supplies output voltage to the modulatin...

Page 3: ...l Rights Reserved Selectrastat Temperature Selector Space Temperature Sensor Mixing Tube TS144 attaches internally Space Temperature Selector dimensions same Space Temperature Selector dimensions same...

Page 4: ...ifier location only Amplifier Install in any convenient location that is protected from the weather and contaminated atmosphere Selectrastat Thiscomponentselectsandsensesspacetempera ture Removecovert...

Page 5: ...es outlined in PRELIMINARY CIRCUIT ANALYSIS Sections IV 14 Move TS144 to location where average temperature can be sensed 15 If proper temperatures are not observed refer to Discharge Air Temperature...

Page 6: ...ner flames and or burner pressure as Test Po tentiometer is turned through full range Note From 0 5 volts heater should be at by pass or low 5 15 volts heater should respond with various input rates b...

Page 7: ...the oscillation stabilizing the flame DO NOT adjust unless necessary because decreasing the sen sitivity will increase the temperature DROOP of the system Low Fire Start Time Adjustment On A1044U F G...

Page 8: ...in space temperature and counterclockwise for a decrease in temperature Each increment on adjustment C is approximately 2 5 degrees A1044U model adjusted from silver side After an adjustment has been...

Reviews: