EXA Modulating Valve Series

Figure 4: EXA Modulating Valve Series Adjustment Controls

Button 1

Button 2

LED 

© 2019 Maxitrol

To enter into the low fire setting mode, press and hold Button 

#2 until the LED light blinks red. Release. The valve is now in 

the low fire setting mode. buttons #1 and #2 are used to set the 

desired low fire setting.

To decrease gas flow slowly, press button #2. Each button press 

will decrease gas flow by the minimum available step size. To 

decrease  gas  flow  rapidly,  hold  button  #2.  Holding  the  button 

down allows the valve to auto step and eliminates the need to 

repeatedly press the button. 

To increase gas flow slowly, press button #1. Each button press 

will increase gas flow by the minimum available step size. To 

increase  gas  flow  rapidly,  hold  button  #1.  Holding  the  button 

down allows the valve to auto step and eliminates the need to 

repeatedly press the button. 

To save the low fire setting, simultaneously hold Buttons #1 and 

#2 until the blinking LED turns OFF.

NOTE:

    Controls  left  in  any  setting  mode  will  default  to  the 

current settings and return to normal operating mode 

after 5 minutes of inactivity.

LOW FIRE SETTING - BUTTON #2

The EXA STAR modulating valve series has two (2) buttons and 

a  communication  LED  for  the  user  interface. The  buttons  are 

used to set the valve for high and low fire settings (see figure 4). 

1.  High Fire Setting (LED will be solid red)

2.  Low Fire Setting (LED will be blinking red)
3.  Operating Mode (LED will be OFF)

CONNECTIONS

VALVE SETTING

Step 1:  Remove 2 screws holding cover. 

Step 2:  Switch power and control signal off.

Step 3:  Connect switched OFF 24V (AC/DC) power source to 

terminals 3 and 4. Note polarity when using a DC power 

source or if one leg of an AC transformer secondary is 

externally grounded or is sharing power with another 

half-wave device (see figure 2, page 2).

Step 4:  Set DIP switches to match available control signal

 

(see table 3, page 2). 

Step 5:  Connect control signal to terminals 1  and 2. 

 

Observe polarity. Note that the return, or signal     

 

ground, must be connected to terminal 2 (see figure    

2, page 2).

Step 6:  Switch power and control signal ON.

Step 7:  Set valve (see “

Valve Setting

” in section below).

Step 8:  Replace cover.

To enter the high fire setting mode, press and hold Button #1 

until the LED lights solid red. Release. The valve is now in the 

high fire setting mode. Buttons #1 and #2 are used to set desired 

high fire setting.

To  increase  gas  flow  slowly,  press  button  #1.  Each  button 

press  will  increase  gas  flow  by  the  minimum  available 

step  size.  To  increase  gas  flow  rapidly,  hold  button  #1. 

Holding  the  button  down  allows  the  valve  to  auto  step 

and  eliminates  the  need  to  repeatedly  press  the  button.  

 

To decrease gas flow slowly, press button #2. Each button press 

will decrease gas flow by the minimum available step size. To 

decrease  gas  flow  rapidly,  hold  button  #2.  Holding  the  button 

down allows the valve to auto step and eliminates the need to 

repeatedly press the button. 

To save the high fire setting, simultaneously hold buttons #1 and 

#2 until the LED turns OFF.

NOTE:

    Controls  left  in  any  setting  mode  will  default  to  the 

current settings and return to normal operating mode 

after 5 minutes of inactivity.

HIGH FIRE SETTING - BUTTON #1