DIP Switch Position Table

Control 

Signal

SW1

Signal

SW2

Offset

SW3

Characteristic

0-10V

OFF

OFF

OFF

2-10V

OFF

ON

OFF

0-20 mA

ON

OFF

OFF

4-20 mA

ON

ON

OFF

2

© 2019 Maxitrol Company, All Rights Reserved.

EXA Modulating Valve Series

The  PWM  output  will  give  a  feedback  to  correspond  with  the 

current valve position between the programmed minimum and 

maximum  positions.  The  duty  cycle  range  is  always  scaled 

from the programmed minimum to the programmed maximum 

position.

Frequency:  

200 Hz ± 1 Hz

Resolution:

  

9-bit (0.29% duty cycle)

Duty Cycle:

  

3% @ programmed minimum position

   

 

97% @ programmed maximum position

Output  Impedance:  

3.2 kΩ  ±  0.1 kΩ

Output High Voltage:

  

5.0 V nominal

   

 

             5.25 V maximum

NOTE: 

Output  high  level  varies  with  the  load  current  at  the 

PWM output.

Output Low Voltage:

  

0.0 V + 0.01 V

   

 

 

Pin 1: (+) positive polarity

   

 

 

Pin 2: (-) negative polarity

   

 

 

(see Figure 2)

Connection:

  

 

TYCO MTA-100 or EQ.

   

         

 

NOTE: 

Optional  pre-wired  connector  for  control  signal/power/

feedback available. Contact Maxitrol Customer Service 
for details and availablity. 

Table 3: Dip Switch Position Table

Flow Capacity in Btu/h @ 1” Pressure Drop:

Model

Nat Gas

LP

EXA40 (3/8”)

190K

315K

EXA40 (1/2”)

215K

355K

EXA50 (1/2”)

385K

640K

EXA50 (3/4”)

435K

725K

EXA60 (3/4”)

670K

1115K

EXA60 (1”)

780K

1300K

Table 1: Sizing Chart

SPECIFICATIONS CONTINUED

Sizing 

Valve  sizing  and  selection  is  based  on  the  typical  1.0”  w.c. 

pressure drop allowance at maximum flow rate. Using the sizing 

chart (table 1), find the closest flow rate which meets or exceeds 

the appliance’s maximum modulated flow rate. 

POSITION FEEDBACK OUTPUT SPECIFICATION

Figure 2: EXA Modulating Valve Series Connections

Power:
Terminal 4
Terminal 3

Position Feedback:
Pin 1
Pin 2

Control Signal:

Terminal 1
Terminal 2

DIP Switches

(Table 3)

Table 2: Connection Table

© 2019 Maxitrol

Control Signal

The  control  signal  indicates  a  position  within  the  valve’s 

programmed range of modulation. 

NOTE:

    Control  signal  is  polarity  sensitive.  Connect  control 

signal  positive  (+)  to  terminal  1  and  control  signal 

return (-) to terminal 2 (see table 2).

The  control  signal  is  “scaled”  between  the  high  and  low  fire 

setting of the valve. The minimum control signal will correspond 

to the programmed low fire setting, and the maximum control 

signal will correspond to the programmed high fire setting.

Connection Table

Terminal 1

Terminal 2

Terminal 3

Terminal 4

Signal (+)

Signal (-)

Power (+)

Power (-)

DIP Switches

A three (3) position DIP switch is located on the PCB (see Figure 

2). Change the signal type and offset by changing the position 

of  DIP  switches.  (For  DIP  switch  position  and  corresponding 

current/voltage ranges, see Table 3).