19
32
Bulk charging time
(C.V stage)
(Only available for 5KVA
model)
900 min
The setting range is from 5 min to
900 min. Increment of each click is
5 min.
If “USE” is selected in program 05, this program can be set up.
33
Battery equalization (Only
available for 5KVA model)
Battery equalization
Battery equalization disable
(default)
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.
34
Battery equalization voltage
(Only available for 5KVA
model)
Default setting: 58.4V. Setting range is from 48V ~ 58.4V.
Increment of each click is 0.1V.
35
Battery equalized time
(Only available for 5KVA
model)
60min (default)
Setting range is from 5min to
900min. Increment of each
click is 5min.
36
Battery equalized timeout
(Only available for 5KVA
model)
120min (default)
Setting range is from 5min to
900 min. Increment of each
click is 5 min.
37
Equalization interval
(Only
available for 5KVA model)
30days (default)
Setting range is from 0 to 90
days. Increment of each click
is 1 day
39
Equalization activated
immediately
(Only available
for 5KVA model)
Enable
Disable (default)
If equalization function is enabled in program 33, this program
can be set up. If “Enable” is selected in this program, it’s to
activate battery equalization immediately and LCD main page
will shows “
”. If “Disable” is selected, it will cancel
equalization function until next activated equalization time
arrives based on program 37 setting. At this time, “
” will
not be shown in LCD main page.