Overload bypass:
When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bypass disable
(default)
Bypass enable
25
Record Fault code
Record enable
Record disable (default)
26
Bulk charging voltage
(C.V voltage)
24V model default setting: 28.2V
48V model default setting: 56.4V
If self-defined is selected in program 5, this program can be
set up. Setting range is from 24.0V to 29.2V for 24V model and
48.0V to 58.4V for 48V model. Increment of each click is 0.1V.
27
Floating charging voltage
24V model default to 27.0V
48V model default setting: 54.0V
If self-defined is selected in program 5, this program can be
set up. Setting range is from 24.0V to 29.2V for 24V model,
48.0V to 58.4V for 48V model. Increment of each click is 0.1V.
29
Low DC cut-off voltage
24V model default setting: 21.0V
48V model default setting: 42.0V
If self-defined is selected in program 5, this program can be
set up. Setting range is from 20.0V to 24.0V for 24V model,
40.0V to 48.0V for 48V model. Increment of each click is 0.1V.
Low DC cut-off voltage will be fixed to setting value no matter
what percentage of load is connected.
31
Solar power balance:
When enabled, solar input
power will be automatically
adjusted according to
connected load power.
(Only available for 5KVA
model)
Solar power balance
enable (Default):
If selected, solar input power will
be automatically adjusted
according to the following formula:
Max. input solar power = Max.
battery charging power +
Connected load power.
Solar power balance
disable:
If selected, the solar input power
will be the same to max. battery
charging power no matter how
much loads are connected. The
max. battery charging power will
be based on the setting current in
program 02.
(Max. solar power = Max. battery
charging power)
32
Bulk charging time
(C.V stage)
(Only available for 5KVA
model)
Automatically (Default):
If selected, inverter will judge this
charging time automatically.
5 min
The setting range is from 5 min to
900 min. Increment of each click is
5 min.