INTRODUCTION / DESCRIPTION 

 

The model IPT is a board level pressure controller to be mounted in a machine enclosure.  The control 
signal can be 4 to 20 madc or 0 to 10 vdc.  The IPT incorporates an inlet valve, an exhaust valve, and a 
pressure sensor all on a common manifold mounted directly to the printed circuit board.  The IPT 
operates by comparing the actual pressure, as measured by the pressure sensor, to the set point 
reference input signal.  If the actual pressure is less than the set point, the inlet valve is opened to 
increase the pressure.  If the actual pressure is greater than the set point, the exhaust valve is opened to 
decrease the pressure. 
 
The device can be mounted in any orientation without need for recalibration.  Mounting options include: 
mounting on standoffs through mounting holes provided; mounting on DIN 35 rail using mounting clips 
provided; or mounting in a customer supplied DIN 35 Modular Circuit Housings.

 

 

INSTALLATION 

 

Mount the unit in an electrical enclosure where the ambient temperature is 0 to 40

º

C.  The unit can be 

installed in an electrical enclosure on a DIN 35 rail by installing the two mounting clips and pressing the 
unit (mounting clips down) onto the rail until it snaps into place. 
 
The IPT should be located as close as possible to the clutch or brake being controlled.  Long, oversized 
air lines connecting the IPT to the clutch or brake must be avoided, since they reduce system response.  
Also, avoid the use of undersized fittings that will limit air flow and cause excessive pressure drop 
downstream of the IPT. 
 
The air inlet, output, and exhaust air line connections to the IPT are made through 1/8 NPT ports on the 
manifold.  The exhaust port can have a muffler installed, or can be plumbed out of the electrical 
enclosure.  The inlet port incorporates a 40-micron filter screen for large contaminates, but the air supply 
to the unit must be filtered, dry and free of oil.  Input pressure must be greater than the maximum required 
output pressure and less than  
150 psi.  Input air pressure above 150 psi can damage the unit.

 

 
 
 
 
 