background image

i-32V5 

Air/water inverter heat pumps with axial fansi

11

4.5 

SPECIFIC R32 GAS WARNINGS

The R32 refrigerant gas:

• 

is odourless;

• 

is flammable, but only if there are naked flames;

• 

it may cause an explosion, but only if a given concentration in air is reached.

It is good practice to follow these guidelines:

• 

do not smoke near the unit;

• 

affix a no smoking sign near the unit;

• 

keep the room where the unit is installed well ventilated;

• 

do not drill or burn the unit;

• 

do not place the unit near sources of ignition, such as open flames, electric heaters, etc;

• 

every extraordinary maintenance or repair on the unit must be performed by skilled technicians or qualified personnel;

• 

a gas leak test must be performed after installation.

4.6 

R32 GAS CHARGE

The procedures described below may only be performed by skilled technicians or qualified personnel:

• 

ensure the R32 is not contaminated by any other types of refrigerant;

• 

keep the gas cylinder in an upright position when charging;

• 

apply the appropriate label on the unit after charging;

• 

do not charge more refrigerant gas than needed;

• 

when charging is completed, perform leak tests before the operating test;

• 

once all the above operations have been completed, a second leak test should be performed.

4.7 

R32 GAS DISPOSAL

The procedures described below may only be performed by skilled technicians or qualified personnel:

• 

Do not discharge the gas in area where there is a risk of explosive mixtures forming with air. The gas should be disposed of in a suitable flare 

with flashback arrestor. Contact the supplier if operating instructions are considered necessary.

4.8 

SAFETY RULES FOR R32 GAS TRANSPORT AND STORAGE

Before opening the unit’s packaging, ensure there are no gas leaks in the environment with an appropriate gas detector. Check that there are 

no ignition sources near the unit.

No smoking near the unit.

Transport and storage must be performed in accordance with the national regulations in force. Specifically, according to ADR provisions, the total 

maximum quantity by transport unit in terms of net mass for flammable gases is 333 kg.

5. INSTALLATION

CAUTION: All the operation described below must be done by QUALIFIED PERSONNEL ONLY. Before any operation on the 

unit, make sure that power supply is disconnected. Also ensure, that the power supply cannot be accidentaly switched back 

on until all the operations are over, by means of appropriate locks.

5.1 

GENERAL

When installing or intervening on the chiller unit, it is necessary to strictly follow the rules listed in this manual, to observe all the indications on 

the unit and however to take all possible precautions. Failure to comply with the rules reported on this manual can create dangerous situations.

After receiving the unit, immediately check its integrity. The unit left the factory in perfect condition; any damage must be 

immediately reported to the carrier and recorded on the Delivery Note before signing it.

The company must be informed, within 8 days, of the extent of the damage. The Customer should prepare a written statement of any severe 

damage.

CAUTION:The units are designed for outdoor installation. The outside temperature must never exceed 46°C. Beyond this 

value, the unit is no longer covered by the current regulations in the field of safety of pressure equipment.

CAUTION: The installation place must be without any fire risks. Therefore, all the necessary measures should be adopted 

in order to prevent the risk of fire at the installation place. The appliance must not be placed near naked flames and heat 

sources. The wall of the buildings near the unit must have an adequate fire resistance class, in order to contain any fire that 

may develop inside the rooms. However, it is recommended to place a fire extinguisher near the unit.

CAUTION: The unit must be installed so as to allow free movement for repair and maintenance operations. The warranty 

does not cover costs for platforms or other lifting equipment needed for any interventions.

Name:

R32

HAZARDS IDENTIFICATION

Main hazards:

Asphyxia� on.

Specifi c hazards:

Quick evapora� on could cause it to freeze.

FIRST AID MEASURES

General informa� on:

Do not administer to people who are unconscious.

Inhala� on:

Immediately remove to fresh air.

Use oxygen or ar� fi cial respira� on as required.

The use of adrenaline or similar drugs should be avoided.

Eye contact:

Carefully rinse with plenty of water for at least 15 minutes and get medical a� en� on.

Skin contact:

Wash immediately with plenty of water for at least 15 minutes. Apply a sterile gauze.

Immediately remove contaminated clothing.

FIRE FIGHTING MEASURES

Ex� nguishing media:

Water spray, dry powder.

Specifi c hazards:

Breakage or explosion of vessel.

Specifi c methods:

Cool down the containers with a water spray from a safe posi� on. Stop the product leakage if possible. Use water spray, 

if possible, to abate the fumes. Move the vessels away from the area of the fi re if this can be done without posing any 

risks.

ACCIDENTAL RELEASE MEASURES

Personal precau� ons:

Try to stop the leak.

Evacuate personnel to safety areas.

Ven� late appropriately.

Eliminate the igni� on sources.

Use personal protec� ve equipment.

Environmental precau� ons:

Try to stop the leak.

Cleaning methods:

Ven� late the area

HANDLING AND STORAGE

Handling:

technical measures/precau� ons:

Allow effi  cient air exchange and/or suc� on the work environments.

Advice for safe use:

Do not breath in fumes or aerosol.

Storage:

Close carefully and store in a cool, dry and well ven� lated area.

Keep in original containers. Incompa� ble products: explosive, fl ammable materials, organic peroxide

EXPOSURE CONTROLS/PERSONAL PROTECTION

Control parameters:

OEL – data not available.

DNEL: Derived no eff ect level (workers)

long-term – systemic eff ects, inhala� on = 7035 mg/m3.

PNEC: Predicted no-eff ect concentra� on

water (fresh water) = 0,142 mg/l

aqua� c, intermi� ent releases = 1,42 mg/l

sediment, fresh water = 0,534 mg/kg dry weight

Respiratory protec� on:

Not required.

Eye protec� on:

Safety goggles.

Hand protec� on:

Latex gloves

Hygienic measures:

No smoking

PHYSICAL AND CHIMICAL PROPERTIES

Colour:

Colourless.

Odour:

Ethereal. Hard to perceive at low concentra� ons.

Boiling point:

-51,7 °C at atm press 

Flash point:

648 °C

Rela� ve gas density (air=1)

Rela� ve liquid density (water=1)

1,8

1,1

Solubility in water:

280000 mg/l.

STABILITY AND REACTIVITY

Stability:

Stable under normal condi� ons.

Materials to avoid:

Decomposi� on products

hazardous:

Air, oxidizing agents, humidity.

Under normal storage and use condi� ons, hazardous decomposi� on products should not be generated..

TOXICOLOGICAL INFORMATION

Acute toxicity:

Local eff ects:

Long term toxicity:

LD/LC50/inHALATION/4 hours/on rat = 1107000 mg/m3.

No known eff ect.

No kown eff ect.

ENVIRONMENTAL INFORMATION

Global warming poten� al

GWP (R744=1):

675

Ozone Deple� on Poten� al ODP 

(R11=1):

0

Disposal considera� on:

Refer to the supplier’s gas retrieval program. Avoid direct release into the atmosphere.

Summary of Contents for i-32V504

Page 1: ...ny installation based on the explanations and or on the technical specifications provided in this manual It is besides forbidden the reproduction under any form of the texts of the figures contained i...

Page 2: ...i 32V5 Air Water heat pumps wih axial fans 2...

Page 3: ...09 2020 Updated images chap 5 5 added chap 5 2 and 9 2 updated chap 5 3 5 4 5 7 5 9 9 10 11 1 update refrigerante charges and SCOP values for sizes 04 16 16T 13 02 05 2020 Info deleted ch 5 3 expansio...

Page 4: ...MINIMUM TECHNICAL CLEARANCES 13 5 5 DIMENSIONS 15 5 5 1 Model i 32V5 04 06 08 SL08 15 5 5 2 Model i 32V5 10 10T 12 SL12 12T SL12T 16 5 5 3 Model i 32V5 14 14T 16 SL16 16T SL16T 18T 17 5 6 ACCESSING TH...

Page 5: ...corrosion method 31 9 2 CLEANING OF EXTERNAL SURFACES 32 9 3 EXTRAORDINARY MAINTENANCE 32 10 DECOMMISSIONING 32 10 1 RESIDUAL RISKS 32 11 TECHNICAL DATA 37 11 1 STANDARD UNIT TECHNICAL SHEET 37 11 2 S...

Page 6: ...ncompatible Therefore make sure to use the supplied manual for the installed unit It is recommended to follow the instructions contained in this manual especially those concerning safety and routine m...

Page 7: ...aning and maintenance which the user is expected to carry out on the unit cannot be done by children without supervision Direct interaction with the unit by persons with electrically controlled medica...

Page 8: ...on imposes on operators working in installations operating with greenhouse gases to hold a certificate issued or recognised by the competent authority certifying that they have passed an examination a...

Page 9: ...necessary use a respiratory protection mask and a eye protection gog gles 4 3 SAFETY SIGNS The unit features the following safety signs which must be complied with Generic hazard Dangerous electric vo...

Page 10: ...e cient air exchange and or suc on the work environments Advice for safe use Do not breath in fumes or aerosol Storage Close carefully and store in a cool dry and well ven lated area Keep in original...

Page 11: ...formed in accordance with the national regulations in force Specifically according to ADR provisions the total maximum quantity by transport unit in terms of net mass for flammable gases is 333 kg 5 I...

Page 12: ...close the panels by fixing them with screws 5 2 TRANSPORT AND STORAGE TEMPERATURE LIMITS Minimum storage temperature C 10 C Maximum storage temperature C 50 C 5 3 LIFTING AND HANDLING The handling mus...

Page 13: ...must not be smooth to avoid water ice deposit as potential sources of danger Unit installation place must be free from foliage dust etc which could clog or cover the coil Installation in areas subject...

Page 14: ...32V504 mm 500 i 32V506 mm 500 i 32V508 i 32V5SL08 mm 500 i 32V510 i 32V510T mm 500 i 32V512 i 32V5SL12 i 32V512T i 32V5SL12T mm 500 i 32V514 i 32V514T mm 500 i 32V516 i 32V5SL16 i 32V516T i 32V5SL16T...

Page 15: ...g to the power and sound pressure data reported in the technical data chapter and the sound emission limits according to the installation area of the unit with reference to the DPCM of 14 11 1997 An a...

Page 16: ...ps wih axial fans 16 828 68 186 190 94 156 377 IN OUT 360 330 924 540 150 154 350 A E E 5 5 2 Model i 32V5 10 10T 12 SL12 12T SL12T IN OUT 1 M G E power supply input 1047 134 673 134 403 87 936 109 17...

Page 17: ...ps with axial fansi 17 5 5 3 Model i 32V5 14 14T 16 SL16 16T SL16T 18T IN OUT 1 M G E power supply input 73 1409 237 66145 448 106 1044 155 634 156 404 376 418 E A E IN OUT 5 6 ACCESSING THE INNER PAR...

Page 18: ...0 10T 12 SL12 12T SL12T 1 Remove the cover by undoing the screws number 1 2 3 4 5 6 7 8 2 Undo the screws number 9 10 of the front sheet and then push the panel downwards to remove the tabs Detail A p...

Page 19: ...larger than 1 mm and a dirt separator on the return pipe from the system labelled WATER INLET If the flow switch is manipulated or altered or if the metal filter and dirt separa tor are missing the wa...

Page 20: ...ation which could drip from the pipes of the plumbing system Since these pipes are well insulated a minimum amount of condensation is produced anyway and therefore it is not mandatory to connect a dra...

Page 21: ...advisable to use an external tap to fill the system 5 7 7 Service sleeves In the hydraulic circuit of the unit 2 service sleeves with gap 1 4 G are installed dowstream and upstream of the circulator r...

Page 22: ...Y CYCLE REVERSING VALVE TE OUTDOOR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEM PERATURE PROBE SV FILLING CONNECTION PSH C 1 1 A...

Page 23: ...EVERSING VALVE TE OUTDDOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEMPERATURE PROBE SV FILLING CONNECTION PSH C 1 1 AUTOMAT...

Page 24: ...LE REVERSING VALVE TE OUTDOOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEMPERATURE PROBE SV FILLING CONNECTION PSH C 1 1 AUT...

Page 25: ...CYCLE REVERSING VALVE TE OUTDOOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEM PERATURE PROBE SV FILLING CONNECTION PSH C 1...

Page 26: ...trol panel is connected to the chiller by 4 cables with a cross section of 1 5 mm2 The power cables must be separate from the remote control cables Maximum distance 50 metres ATTENZIONE The remote con...

Page 27: ...tibility specifications however the designer of the electrical system must fulfil appropriate assessments to ensure the absence of interference 5 9 3 User terminal block The connection terminal block...

Page 28: ...5 1 X 5 2 X 16 1 X 16 2 X 15 1 X 17 1 X 19 1 X 19 2 X 20 1 X 20 2 X 22 1 X 22 2 X 15 2 X 17 2 F1 X 1 1 X 1 1 L N L N X 10 2 X 9 2 X 6 2 X 11 2 X 14 2 X 10 1 X 9 1 X 11 1 X 6 1 X 14 1 X 4 1 X 5 2 X 16...

Page 29: ...This must only be done to disconnect the unit from the power supply for long downtimes e g seasonal stops etc Furthermore power is missing the crankcase heaters will not be powered with the risk of br...

Page 30: ...operations CAUTION it is possible that a certain quantity of oil from the compressor is deposited in the pipes of the refrigeration circuit especially by bends In case of maintenance operations in wh...

Page 31: ...ly clean the coil follow the instructions below Remove surface dirt Deposits such as leaves fibres etc should be removed using a vacuum cleaner use a brush or other soft accessory and avoid rubbing ag...

Page 32: ...ust be scrapped and divided according to their nature there is especially a good amount of copper and aluminium in the machine These operations allow easy material recovery and the recycling process t...

Page 33: ...ormed in order to minimize the risk of igni tion Take the following measures before working on the cooling circuit Measure Completed Notes 1 General working environment Inform the following persons of...

Page 34: ...e earth connection 8 Repairs on sealed enclosures When carrying out work on sealed components fully isolate the appliance from the power supply also before removing sealed covers If a power supply is...

Page 35: ...used However it is important that best practice is followed since flammability is a consideration The following pro cedure shall be adhered to remove refrigerant purge the circuit with inert gas evacu...

Page 36: ...with date and signature Refrigerant is flammable The system has been taken out of use The refrigerant has been removed 17 Recovering When removing refrigerant from a system either for servicing or dec...

Page 37: ...5 C 55 C Compressor Type Twin Rotary DC Inverter Number of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 0 45 0 67 0 67 1 Refrigerant circuit 1 1 1 1 Refrigerant Type R32...

Page 38: ...umber of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 1 1 1 1 4 Refrigerant circuits 1 1 1 1 Refrigerant Type R32 R32 R32 R32 Refrigerant charge 7 kg 2 5 2 5 2 5 3 2 Amo...

Page 39: ...of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 1 4 1 4 1 4 1 4 Refrigerant circuits 1 1 1 1 Refrigerant Type R32 R32 R32 R32 Refrigerant charge 7 kg 3 2 3 5 3 5 3 5 Am...

Page 40: ...cative data subject to changes For the correct value always refer to the technical label on the unit 8 Sound power level heating mode condition 3 value determined based on measurements made in accorda...

Page 41: ...35 C 55 C Compressor Type Twin Rotary DC Inverter Number of compressors 1 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 0 67 1 1 1 4 1 4 Refrigerant circuits 1 1 1 1 1 Refrigerant Ty...

Page 42: ...of the antifreeze probe due to the lack of flow but does not guarantee the minimum water flow rate required for correct operation of the unit Model i 32V5 04 06 08 SL08 10 10T 12 SL12 12T SL12T 14 14T...

Page 43: ...ter Room temperature with water at maximum 39 C Minimum 20 C Maximum 40 C Room temperature with water at maximum 55 C Minimum 10 C Maximum 35 C Outlet water temperature Minimum 25 C Maximum 60 C The f...

Page 44: ...ete with a display located under a transparent hinged polycarbonate door with IP67 protection rating The interface consists of a variable text part and a series of icons identifying the operation of t...

Page 45: ...key In the parameter setting mode it allows you to move to a lower menu or to decrease the parameter value In standard operation the display shows the water outlet temperature in tenths of Celsius deg...

Page 46: ...C 35 0 25 Hea rCoo Mixing valve summer setpoint C 15 0 0 0 80 rHEA Mixing valve winter setpoint C 30 0 0 0 80 If the DHW function is enabled If Gi module is included access is only possible with insta...

Page 47: ...i 32V5 Air water inverter heat pumps with axial fansi 47...

Page 48: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Reviews: