MAXA HI-T User'S And Installer'S Manual Download Page 26

 

 

 

Hi

T

 

Centralized

 

controller

 

25

 

4.

 

Enter

 

the

 

service

 

password

 

and

 

press

 

on

 

the

 

mark’s

 

confirmation;

 

5.

 

Enter

 

inside

 

the

 

“Addresses

 

configuration”;

 

6.

 

Enter

 

inside

 

the

 

Addresses

 

assigns

”;

 

7.

 

Change

 

the

 

address

 

with

 

the

 

arrows:

 

the

 

addresses

 

can

 

be

 

assigned

 

from

 

the

 

number

 

10;

 

8.

 

Push

 

on

 

the

 

confirmation

 

icon

 

next

 

to

 

the

 

word

 

“Start:”;

 

9.

 

After

 

a

 

few

 

seconds

 

you

 

will

 

see

 

"

Set

";

 

10.

 

Remove

 

power

 

supply

 

from

 

the

 

first

 

fan

 

coil

 

and

 

power

 

on

 

the

 

second;

 

11.

 

Perform

 

the

 

same

 

steps

 

7

 

through

 

9

 

for

 

each

 

fan

 

coil

 

units

 

connected

 

to

 

the

 

same

 

keyboard.

  

12.

 

It

 

is

 

important

 

to

 

assign

 

to

 

the

 

fan

 

coil

 

units

 

that

 

will

 

be

 

bound

 

to

 

the

 

same

 

zone

 

a

 

series

 

of

 

consecutive

 

addresses

 

(e.g.

 

whether

 

there

 

are

 

3

 

fan

 

coil

 

units

 

within

 

the

 

same

 

hall

 

and

 

if

 

you

 

want

 

to

 

associate

 

them

 

with

 

a

 

single

 

thermal

 

zone

 

that

 

we

 

call

 

HALL,

 

you

 

must

 

give

 

the

 

themselves

 

a

 

series

 

of

 

addresses

 

from

 

10

 

to

 

12,

 

etc..).

  

4.5.2

 

SCAN

 

NETWORK

 

Once

 

each

 

fan

 

coil

 

has

 

been

 

addressed

 

,

 

it

 

is

 

essential

 

to

 

perform

 

a

 

network

 

scan

 

to

 

check

 

whether

 

all

 

the

 

fan

 

coils

 

are

 

correctly

 

recognized.

 

To

 

do

 

this:

 

1.

 

restore

 

power

 

supply

 

to

 

all

 

the

 

fan

 

coil;

 

2.

 

enter

 

to

 

the

 

service

 

menu

 

following

 

the

 

same

 

procedure

 

described

 

in

 

the

 

previous

 

section

 

(points

 

2

4)

 

and

 

enter

 

"

Scan

 

network

";

 

3.

 

press

 

the

 

tick

 

confirmation

 

closer

 

to

 

the

 

word

 

"

Start

"

 

and

 

let

 

the

 

system

 

scans

 

the

 

network;

 

4.

 

after

 

scanning

 

the

 

system

 

should

 

find

 

all

 

of

 

the

 

chiller

 

(max.

 

7

 

in

 

cascade)

 

and

 

all

 

fan

 

coil

 

units

 

connected

 

to

 

the

 

same

 

network.

 

If

 

the

 

number

 

of

 

fan

 

coils

 

found

 

does

 

not

 

match

 

those

 

installed,

 

the

 

wiring

 

was

 

not

 

performed

 

properly.

  

If

 

one

 

or

 

more

 

fan

 

coil

 

properly

 

addressed

 

and

 

identified,

 

get

 

disconnected

 

from

 

the

 

network

 

(for

 

example,

 

due

 

to

 

a

 

failure

 

of

 

the

 

fan

 

coil

 

power

 

supply),

 

the

 

keyboard

 

proceed

 

with

 

the

 

updating

 

of

 

the

 

number

 

of

 

the

 

actually

 

working

 

fan

 

coils

 

in

 

the

 

system

 

with

 

a

 

delay

 

of

 

2

 

minutes

 

from

 

the

 

occurrence

 

of

 

the

 

event,

 

accompanying

 

the

 

update

 

with

 

a

 

an

 

error

 

message.

 

When

 

the

 

fan

 

coils

 

are

 

re

connected,

 

the

 

keyboard

 

recognizes

 

them

 

automatically,

 

saving

 

the

 

settings

 

previously

 

set.

 

 

4.5.3

 

AREAS

 

FAN

 

COIL

 

ASSIGNMENT

 

AND

 

CUSTOMIZING

 

THE

 

AREA’S

 

NAME

 

To

 

match

 

the

 

fan

 

coil

 

to

 

the

 

desired

 

areas

 

you

 

must

 

perform

 

the

 

following

 

steps:

 

1.

 

enter

 

the

 

"

Configuration

"

 

and

 

from

 

here

 

going

 

in

 

"

Service

 

menu

 

"

 

following

 

the

 

same

 

procedure

 

described

 

in

 

Paragraph

 

4.5.1

 

(steps

 

2

4)

 

and

 

select

 

the

 

Area

 

configuration

”;

 

2.

 

press

 

on

 

Zone

 

1

”;

 

3.

 

press

 

on

 

the

 

second

 

line

 

where

 

it

 

appears

 

the

 

current

 

name

 

"

Zone

 

1

"

 

and

 

change

 

the

 

zone

 

name

 

using

 

the

 

keyboard

 

that

 

appears

 

(you

 

can

 

enter

 

up

 

to

 

9

 

characters);

  

4.

 

to

 

confirm

 

the

 

new

 

name,

 

press

 

"

Enter

",

 

otherwise

 

press

 

on

 

"

Esc

";

  

5.

 

press

 

the

 

value

 

that

 

appears

 

at

 

the

 

words

 

"

From

"

 

(the

 

value

 

is

 

highlighted

 

in

 

red);

  

6.

 

use

 

the

 

arrows

 

to

 

select

 

the

 

address

 

of

 

the

 

first

 

fan

 

coil

 

units

 

in

 

the

 

area

 

that

 

you

 

are

 

configuring;

  

7.

 

press

 

the

 

tick

 

confirmation;

  

8.

 

press

 

the

 

value

 

that

 

appears

 

in

 

correspondence

 

of

 

"

To

"

 

(the

 

value

 

is

 

highlighted

 

in

 

red);

  

9.

 

use

 

the

 

arrows

 

to

 

select

 

the

 

address

 

of

 

the

 

last

 

fan

 

coil

 

units

 

in

 

the

 

area

 

that

 

you

 

are

 

configuring;

  

10.

 

press

 

the

 

confirmation

 

tick;

  

11.

 

repeat

 

steps

 

2

 

through

 

10,

 

using

 

the

 

procedure

 

to

 

other

 

areas

 

that

 

you

 

want

 

to

 

configure.

 

 

4.6

 

ASSOCIATES

 

UNIT

 

OPERATION

 

4.6.1

 

ON/OFF

 

Once

 

executed

 

the

 

zone

 

configuration

 

and

 

the

 

association

 

of

 

the

 

fan

 

coil,

 

you

 

can

 

proceed

 

to

 

the

 

"first

 

start"

 

of

 

the

 

connected

 

units.

 

You

 

can

 

turn

 

on

 

or

 

off

 

with

 

a

 

single

 

tap

 

the

 

whole

 

system

 

headed

 

by

 

a

 

single

 

keyboard

 

Hi

T;

 

otherwise

 

you

 

can

 

individually

 

turn

 

on

 

the

 

chiller

 

and

 

manage

 

individual

 

zones.

 

 
 

For

 

operate

 

the

 

entire

 

system:

 

 

1.

 

from

 

the

 

main

 

page

 

of

 

the

 

system,

 

go

 

to

 

"Status

 

setup

                    

;

  

 

2.

 

in

 

the

 

menu

 

that

 

appears

 

are

 

listed:

 

SYSTEM,

 

CHILLER,

 

ZONE

nth.

  

3.

 

Push

 

on

 

"System"

 

and

 

with

 

a

 

single

 

operation

 

you

 

can

 

turn

 

on

 

or

 

off

 

all

 

fan

 

coil

 

units

 

of

 

all

 

the

 

areas

 

connected

 

to

 

the

 

keyboard

 

Hi

T

 

and

 

all

 

the

 

chillers

 

that

 

are

 

part

 

of

 

the

 

same

 

system:

 

 

Summary of Contents for HI-T

Page 1: ...chillers and i HP i HP LT chillers A I R C O N D I T I O N I N G A86 USER S AND INSTALLER S MANUAL Serie Series Serie S rie Emissione Edition Au sgabeIssue Hi T LCD Touch Screen Centralized Controller...

Page 2: ...sed of according to law in accordance with the WEEE EU directives 2002 96 EC and 2003 108 EC as amended and inquire at the place of residence or at the retailer in the case where the product is replac...

Page 3: ...S PAGE CHRONOTHERMOSTAT 18 3 6 4 SPECIAL FUNCTIONS PAGE 19 3 6 5 CONFIGURATION PAGE 19 3 6 6 HELP PAGE 22 4 STATUS MACHINES AND FUNCTIONS 23 4 1 NEWTORK MANAGEMENT 23 4 2 REMOTE CONTROL CONNECTED WITH...

Page 4: ...IAL FUNCTIONS 35 4 12 1 SCREED FUNCTION 36 4 13 PASSWORD AND PROTECTIONS 36 5 REMOTE ACCESS 37 5 1 SECURITY 37 5 2 LOCAL WEB SERVER 37 6 FIRMWARE UPDATE 41 7 HNS SYSTEM DESCRIPTION 42 8 THE HNSBOX 44...

Page 5: ...ding synoptic 1 2 USE NOT PERMITTED Any use other than that permitted is PROHIBITED 1 3 TECHNICAL DATA Nominal Min Max Power supply voltage 12Vac 10Vac 14Vac Power supply frequency 50 60Hz Tip 5 Tip 5...

Page 6: ...on the sensitive areas of the screens Do not put the touch screen in contact with other electrical devices Electrostatic discharge may cause a malfunction 2 1 3 DISPLAY The display is a TFT LCD 16 9 f...

Page 7: ...2 Connections 2 1 INSTALLING The Hi T control is used for fixing to the wall according to the standard 503 In the rear part of the control some pre drilled holes are present to be detached pursuing a...

Page 8: ...ns on the different screens can be shown in full colours or de saturated as in the following example The colour saturation indicates that icon is usable when pressed the related function is performed...

Page 9: ...ayed resource The sensible areas indicated in the image by red boxes inside this page are 1 Heat pump chiller showing the working mode 2 Status system and mode system display 3 Fan coil with a status...

Page 10: ...aphically the presence of the chiller but inside the house do not appear other object in this case the appearance is the following Figure 6 Home screen only chiller is networked Figure 7 Chiller Heat...

Page 11: ...ch chiller present assigning each a name Figure 10 Chiller page information and sensitive areas The information in the chiller s page are 1 Temperature read in the chiller about to a specific chiller...

Page 12: ...ons about the operation compressor running of the chiller graphically displaying the fan rotation Pushing down on the area 5 you access to a further screen that shows a list of read data in real time...

Page 13: ...ere is a table with icons that may appear in the scroll side bar The presence or absence of the icon in the sidebar will be determined by the enable or disable of the function on the chiller ORDER OF...

Page 14: ...here you can access the information related to the operation of the individual fan coil identified by area of belonging and identification number of the individual fan coil Figure 12 Information fan c...

Page 15: ...gulation auto mode With the up and down arrows you choose the speed with the green button you confirm the value set 3 4 2 1 TOOLBAR OPERATION FANCOIL AREA In the left scroll sidebar there are icons th...

Page 16: ...TION Pressing in the sensitive area 7 of Figure 5 it appears the page Figure 14 Ethernet network configuration page On this page there are the addresses for the configuration of an Ethernet connection...

Page 17: ...t and outlet of the chiller and on the air temperature measured by the probes on board Field 4 shows the ambient temperature and the relative humidity measured by the sensors integrated in the Hi T pa...

Page 18: ...ons Figure 16 System main page Above from the left to right 1 STATUS SETUP 2 SET POINT SETUP 3 PROGRAMS AND CHRONO THERMOSTAT In the bottom from the left to right 4 SPECIAL FUNCTIONS 5 CONFIGURATION 6...

Page 19: ...he sanitary hot water set see Paragraph 4 6 2 the second set point see Paragraph 4 9 and the offset for the climatic compensation see Paragraph 4 10 3 6 3 PROGRAMS PAGE CHRONOTHERMOSTAT Pushing on the...

Page 20: ...shing on the icon above you enter into the page Configuration Figure 20 Configuration page From the configuration screen you can access to the User Setup menu to the service menu and to the manufactur...

Page 21: ...entered in Parameters use the up and down arrows to scroll through the pages of the parameters until you find the desired parameter press on the currently set value the present value turns red to indi...

Page 22: ...r compensation Text CHIL in heat with high temp Numb 0 0 10 0 10 0 17 44 Set Text comp FC Cool C 25 0 0 0 50 0 18 44 Set Text comp FC Heat C 15 0 20 0 35 0 19 44 m5 coeff for compensation Text Fan Coi...

Page 23: ...Cool Seconds 0 0 255 Table 5 Fan coil service s parameters To change a the value of a parameter entered in the parameter list of chillers fan coils or keyboard use the up and down arrows to scroll th...

Page 24: ...ding to the set point 4 2 REMOTE CONTROL CONNECTED WITH MORE CHILLER IN THE NETWORK In the each on board control panel set the chiller parameter H79 as described above Then connect the chiller and the...

Page 25: ...hiller Weekly programming in summer winter sanitary mode and of the legionella disinfection cycle 4 3 1 ENABLING THE INDIVIDUAL CHILLER FOR THE PRODUCTION OF SANITARY WATER Of all the chiller in the n...

Page 26: ...a delay of 2 minutes from the occurrence of the event accompanying the update with a an error message When the fan coils are re connected the keyboard recognizes them automatically saving the settings...

Page 27: ...water eco is activated they respectively correspond to the temperature of normal operation 1st set point and to the working temperature during the energy saving operation set point economy Once you ha...

Page 28: ...given on the production of domestic hot water therefore the system goes first in domestic hot water production when the sanitary is satisfied the system switches the mode to summer or winter operatio...

Page 29: ...of consideration 4 possible settings are Winter Summer Sanitary for the chiller Winter and Summer for the fan coil zones CHILLER ZONE n CHILLER WINTER SUMMER SANITARY Water set Water set eco Change th...

Page 30: ...ogramming of chillers in winter mode Summer Zone to set the weekly time programming of the zones in summer mode Winter Zone to set the weekly time programming of the zones in winter mode In addition i...

Page 31: ...od confirm the single time period pressing the green symbol of confirmation afterwards you can observe that correspondingly to the selected time period you will see a time line bar of the colour of th...

Page 32: ...ou can do are Normal Enable function Off Disabled function To set the programming go to Programs Sanitary the word Sanitary appears only if you have enabled the sanitary mode System Main Configuration...

Page 33: ...anguage 1 from the system main page go to Configuration 2 then go to User menu 3 enter the user password and press the confirmation tick The default password is 0 4 go to Language 5 select the desired...

Page 34: ...eters from System main page Configuration Service menu Parameters Chiller Chiller name H82 Enable second setpoint 2 ref chiller manual for allowable values Must also be set a digital output for contro...

Page 35: ...midity measured by the sensors built into the Hi T remote control are available to the chiller which can then use these values measured for their regulators where required 4 9 2 DEW POINT AND DEHUMIDU...

Page 36: ...onfigured Set Text m1 m2 parameters which can be set from Configuration Service menu Parameters Keyboard see parameters list in Table 4 To exclude the climatic compensation by the user you have to set...

Page 37: ...meter Screed function set which can be set among the service parameters Configuration Service menu Keyboard Par 36 44 Screed function Set The function has a duration given by the service parameter Con...

Page 38: ...nabled through a manual installation in the local network no DHCP services are forecasted The device can communicate through browsers compatible with HTML 4 01 and or TPFT services RFC 1350 compliant...

Page 39: ...m temperature and the relative humidity are the ones measured from the sensors integrated inside the current Hi T To shift to next available pages click on the links at the page bottom Figure 33 Hi T...

Page 40: ...Hi T Centralized controller 39 Figure 34 Command sent confirmation page Figure 35 Hi T Ethernet Set point page In the Set point page are available in read only mode the set point set by Hi T...

Page 41: ...Hi T Centralized controller 40 Figure 36 Hi T Ethernet Alarms page The Alarms page is related to all the active alarms inside the system at the moment when the page is shown...

Page 42: ...root of a USB pen drive insert the pen drive into the Hi T USB port enter into Configurations User s menu see Paragraph 3 6 5 1 after having inserted the user s password and entered into User s menu s...

Page 43: ...re already fitted and pre wired thus providing the customer with a terminal board for connecting the hydronic units In so doing it is not possible to locally adjust the temperature by means of the DRA...

Page 44: ...dronic units number in comparison with installed ones and respecting the number of running chillers connected in the network SANITARY HOT WATER FUNCTION the chillers can also provide sanitary water by...

Page 45: ...scribed in the wiring diagrams power and signal connections of this manual have to be realized only by QUALIFIED PERSONNEL Make sure to get the power supply disconnected before any intervention on the...

Page 46: ...Hi T Centralized controller 45 8 3 CONNECTING THE Hi T KEYBOARD THE CHILLER AND THE HYDRONIC UNITS...

Page 47: ...System type Electrical resistances NO Integration Setting NO Heating OUT 1 OUT 1 OUT 2 Cooling OUT 1 OUT 1 OUT 1 OUT 1 Outlets Electrical resistances NO OUT 2 OUT 2 NO To enter the DIP Switches follo...

Page 48: ...Hi T Centralized controller 47 8 6 AIR SENSOR Install the air sensor in the unit s finned battery inlet opening and fix it by means of an electrical type clamp...

Page 49: ...i T Centralized controller 48 8 7 WIRINGS Hydronic cassettes type See the user installer manual to get information as for the cassettes type wiring diagrams HCA B Picture 1 HNSbox connection with HCA...

Page 50: ...0 HNSbox terminal board PE U QF1 N 230V 50Hz SL1 KA1 TC1 24VAC KA1 KA1 KA1 KA1 ST1 U N FU1 RD1 EV1 E1 C 1 2 3 4 5 6 7 8 M M 1 1 As for the RS485 terminal board see the signal wiring connection section...

Page 51: ...S box out 2 terminal not used As for the RS485 terminal board see the signal wiring connection section Picture 3 HNSbox connection with HCN09 HCN09 with SBC module V2 valve V1 V2 Window contact Water...

Page 52: ...L HEATING SECTION BOARD R S T KMR1 TS TS 6 7 400V 3 N 50Hz Picture 5 HNSbox connection with HCN09 with SBC module HCN09 with SBE2 module R S N T YV1 Window contact Water sensor Air sensor med speed mi...

Page 53: ...Phase Ph1 Neutral L Low speed H Hight speed M Medium speed Picture 7 HNSbox connection with HCN13 43 HCN13 43 with SBC module V2 valve Window contact Water sensor Air sensor med speed min speed N L o...

Page 54: ...ht spee d M M ed ium spee d Power supply 400 3 N 50 60Hz Picture 9 HNSbox connection with HCN13 43 with SBE module HCN13 43 with SBE2 module R S N T YV1 Window contact Water sensor Air sensor med spee...

Page 55: ......

Page 56: ...facturer reserves the right to modify the data whenever it is considered necessary Via Gettuglio Mansoldo Loc La Macia 37040 Arcole Verona Italy Tel 39 045 76 36 585 r a Fax 39 045 76 36 551 r a www m...

Reviews: