30
10.3
EER VALUES FOR CALCULATING THE ENERGY PERFORMANCE OF BUILDINGS ACCORD
-
ING TO UNI/TS 11300-3
The cooling capacity values and EER coefficients under partial load conditions are shown.
The reference conditions at partial load specified by the UNI/TS 11300-3 standard are illustrated below.
EERs are also given for load factors lower than 25%.
Test
Load factor F%
Outside air dry bulb temperature [°C]
Chlled waterinlet/outlet temperature of fan
coil units [°C]
1
100%
35
12/7
2
75%
30
*)/7
3
50%
25
*)/7
4
25%
20
*)/7
*) temperature determined by water flow rate at full load.
10.3.1
Model i-32V5 MIDI 0121
Outside air dry bulb
temperature [°C]
Load factor
F%
EER
Cooling capacity
[kW]
35
100%
3,50
20,7
30
75%
4,28
15,5
25
50%
4,97
10,3
20
25%
5,72
9,30
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5
6,0
6,5
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
EER
F%
C
Load factor F%
EER @20°C xC
0,95
20%
5,43
0,94
15%
5,38
0,87
10%
4,98
0,71
5%
4,06
0,46
2%
2,63
0,29
1%
1,66
10.3.2
Model i-32V5 MIDI 0126
Outside air dry bulb
temperature[°C]
Load factor
F%
EER
Cooling capacity
[kW]
35
100%
3,21
25,8
30
75%
4,17
19,3
25
50%
4,96
12,8
20
25%
5,57
9,36
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5
6,0
6,5
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
EER
F%
C
Load factor F%
EER @20°C xC
0,95
20%
5,30
0,94
15%
5,24
0,87
10%
4,85
0,71
5%
3,96
0,46
2%
2,56
0,29
1%
1,62