22
Description
Value
Maximum number of restarts/hours after high/low pressure alarm (manual
reset)
3
Antifreeze protection (standard version/ BT version)
3°C / -10°C*
Water circuit safety valve
6 bar
* Check that the antifreeze mixture concentration is suitable for the freezing temperature.
6.4
CORRECTION FACTORS DEPENDING ON ALTITUDE
The correction factors for performance as a function of altitude are calculated for cooling under the conditions (1) in the above technical data
tables and are given for altitudes of 500, 1000, 1500 and 2000 m.
Altitude [m]
500
1000
1500
2000
Correction factors cooling capacity
0,9888
0,9762
0,9618
0,9466
Correction factor for power input in cooling mode
1,0106
1,0235
1,0386
1,0560