- 11 -
8. Set example of parameter
8-1. Flow of parameter set
Parameter should set according to the flow as shown hereunder.
* In case setting up value over input range exceeding specification, setup value of
parameter will indicate [ERR] on indication LED, let you know setup value is
wrong and do not accept next operation.
* In this case, please change to correct set value again.
8-2. Example of parameter set
Following is a set example to set integral time at 15 second.
(Providing that set value was 0 second before change.)
(1) Push “MOD” button 1 time ················ move to parameter window and LED (orange).
written Range on the left will light on.
(2) Push “SEL” button 5 time ················· LED (orange) lit goes down in turn
and INTEGRATION TIME LED will light.
(3) By using both → button and ↑button,
set Indication LED at “15”.
(4) Push “MOD” button 1 time ················· return to measure window and start
measure again at integral 15 second.
You operate other parameters with same procedure, please.
In case setting other parameters continuously, at (4) above instead of “MOD” you push
“SEL” and can perform both setting parameter and moving to plural items at the same time.
Reference: Parameter and light up of corresponding LED
RANGE
: only RANGE LED light up
L1 ON
: only L1 ON LED light up
L1 OF
: only L1 OFF LED light up
L2 ON
: only L2 ON LED light up
L2 OFF
: only L2 OFF LED light up
INTEGRATION TIME : only INTEGRATION TIME LED light up
CORRECTION
: both RANGE LED and CORRECTION LED light up same time
Measure
window
Parameter mode
Value set
Parameter select
MOD button
Press down
(to parameter mode)
SEL button
Push down
Respective
parameter select
→ Move beam by
button
↑ Each button
push down change
value
Push down MOD button
(after parameter set, to measure window)
SEL button push down
(after set parameter move
to other parameter item)