![Matsushima MSC-01 Instruction Manual Download Page 30](http://html1.mh-extra.com/html/matsushima/msc-01/msc-01_instruction-manual_1741933030.webp)
-
29
-
9.
Standard Factory Setting
Table 3. Standard Factory Setting
No.
Item
Description
Setting value
1
Display unit
( Menu
:
1-1-1 )
Select the unit to be displayed on LCD
「%」「
ton
」「
m
」「
ft
」「
Pa
」「
kPa
」「
MPa
」「
bar
」
「
kgf/cm2
」「
psi
」「
mg/m3
」「
µ
g/m3
」「
m3/h
」
「
ft3/h
」「
t/h
」「
kg/h
」「
lb/h
」「
mL/s
」「
°C
」「
°F
」
「
mA
」「
blank
」
%
2
Decimal point
( Menu
:
1-1-2 )
Set the decimal point of the value displayed
on the LCD screen
XXXX.X
3
Scaling
( Menu
:
1-1-3 )
Set the LCD display value corresponding to the
input signal ( 4mA / 20mA )
Range : -99999 ... +99999
4mA
=
+
0
.
0
20mA
=
+
100
.
0
4
No.1 Limit
( Menu
:
1-2-1 )
Set the ON/OFF operation point of the
No.1 limit relay by % value.
Range : 0.0% … 100.0%
ON
=
95
.
0
%
OFF
=
85
.
0
%
5
No.2 Limit
( Menu
:
1-2-2 )
Set the ON/OFF operation point of the
No.2 limit relay by % value.
Range : 0.0% … 100.0%
ON
=
95
.
0
%
OFF
=
85
.
0
%
6
Sensor failure relay
( Menu
:
1-2-3 )
Select and set the operation of the sensor error
relay at an error signal input to “Execution”
or “Non-Execution”.
Execution
7
Sensor failure mode
( Menu
:
1-3 )
Select the output signal mode at an error
signal input.
“Raw mode” / ”Hold mode” / ”Setting value”
Raw mode
Setting value
( Menu
:
1-3-3 )
Select the output signal when you select
“Setting value” in Sensor error
Range : 3 … 24mA ( 0.75 … 6V )
3.6 mA
( 0.90 V )
8
Damping
( Menu
:
1-4 )
Set the damping time
Range : 0 … 999s
0s
9
Failure setup. In
( Menu
:
1-5 )
Set the upper / lower limit of the current value
for the error condition of the input signal.
Upper limit range : 20.0 … 24.0mA
Lower limit range : 3.0 … 4.0mA
Upper
=
20.5 (mA)
Lower
=
3.8 (mA)
10
Language
( Menu
:
4 )
Select Japanese / English as the language
displayed on the LCD screen.
English