![Matsushima GRAPHIC COM4 Instruction Manual Download Page 7](http://html1.mh-extra.com/html/matsushima/graphic-com4/graphic-com4_instruction-manual_1741925007.webp)
6
4.5 Error display
①
Error code (E****)
When there is fault in the level meter or error occurs in
communication between level meter and adjustment
unit, then error code will be presented.
Refer to table below for error code details.
Table 4.5.1 Error code details
Error
code
Error type
Description
E8000
SRAM Error
SRAM failure
E4000
EEPROM Error
EEPROM failure
E2000
MIC Error
MIC unit failure
E1000
Trig Error
Trigger signal lost
E0800
LCD Error
LCD adjustment unit failure
E0400
Charge Error
Charge circuit failure
E0200
I2C Checksum error
Communication between level meter and LCD
adjustment unit failed
E0100
Loop Current Error
Loop Current failure
E0080
Lost echo
・
Reflection echo is currently being detected
・
There is no reflection echo
・
There is no reflection echo in the measurement
span
E0010
During Startup Processing
Startup Processing(Warning)
E0008
Min. meas. limit over
Measured distance is lower than "Min. meas. limit"
E0004
Max. meas. limit over
Measured distance is higher than "Max. meas. limit".
E0002
Upper range limit over
(100
%
over)
Measured distance exceeds "Upper
range limit over (100% over)".
E0001
Lower range limit over
(0
%
over)
Measured distance undergoes "Lower range limit over
(0% over)".
S.CPU
Level meter not responding
No response from level meter
S.I2C
I2C Checksum error
Communication between level meter and LCD adj.
unit failed
※
Refer to chapter 15, for troubleshooting details.
12.345m
Distance
E1000
①
Fig. 4.5.1 Error code presentation