Matelec FPC-36040 Owner'S Operation Manual Download Page 12

12

Block

Modbus Address

Register Data

Read/Write

Function Codes

Description

Input Reg

1

I/O States

R

1,3

0=Off,1=On

2

Alarm States

R

1,3

0=Off,1=On

3

System States

R

1,3

0=Off,1=On

4

Mute Alarm

W

5

0=Off,1=On

5

Reset Alarm

W

5

0=Off,1=On

17

4-20mA reading

R

3

4-20mA=40-200

18

APC6 Serial

number (2 characters per register)

R

3

-

19

R

3

-

20

R

3

-

21

R

3

-

22

R

3

-

23

APC6 Software rev 

2 characters per register)

R

3

-

24

R

3

-

25

ME16 Software rev

(2 characters per register)

R

3

-

26

R

3

-

27

Pump stop current

R

3

4-20mA=40-200

28

Pump start current

R

3

4-20mA=40-200

29

High level current

R

3

4-20mA=40-200

30

Antiseize period

R

3

0-65535 Hours

31

Antiseize run time

R

3

0-255 Seconds

32

Manual mode timeout

R

3

0-255 Minutes

33

Standard alternate period

R

3

0-255 Minutes

34

Recirc alternate period

R

3

0-65535 Minutes

35

Maximum idle period

R

3

0-65535 Minutes

36

High level alarm delay

R

3

0-65535 Seconds

37

Pump fault delay

R

3

0-255 Seconds

38

Prime fault delay

R

3

0-255 Seconds

39

Pressure mode start delay

R

3

0-255 Seconds

40

Pressure mode min run time

R

3

0-255 Seconds

41

Pressure mode alarm delay

R

3

0-255 Seconds

42

Alternate high level alarm delay

R

3

43

Single pump enable

R

3

0=Off,1=On

44

Inhibit trigger delay

R

3

0-255 Seconds

45

Inhibit fault enable

R

3

0=Off,1=On

46

Inhibit fault threshold

R

3

0-65535

47

Current loop invert

R

3

0=Off,1=On

48

Max run fault delay

R

3

0-65535 Minutes

Registers

65

Pump 1 mode

R/W

03, 06, 16

0=Off,1=Manual,2=Auto

66

Pump 2 mode

R/W

03, 06, 16

0=Off,1=Manual,2=Auto

67

Pump 1 run hours

R/W

03, 06, 16

0- Hrs

68

Pump 2 run hours

R/W

03, 06, 16

0- Hrs

69

Pump 1 start count

R/W

03, 06, 16

0- Number

70

Pump 2 start count

R/W

03, 06, 16

0- Number

71

Pump 1 fault count

R/W

03, 06, 16

0- Number

72

Pump 2 fault count

R/W

03, 06, 16

0- Number

73

High level count

R/W

03, 06, 16

0- Number

74

Low level count

R/W

03, 06, 16

0- Number

75

Power cycle count

R/W

03, 06, 16

0- Number

76

Low pressure alarm count

R/W

03, 06, 16

0- Number

77

Pump 1 prime loss count

R/W

03, 06, 16

0- Number

78

Pump 2 prime loss count

R/W

03, 06, 16

0- Number

2.5 Address Reference

The following tables list all valid Modbus coil and register addresses for the Controller and the data contained within:

MODBUS REGISTERS

Summary of Contents for FPC-36040

Page 1: ...PUMP 1 PUMP 2 AUTO AUTO Running Idle System OK No Alarms DUAL PUMP CONTROL MAIN ISOLATOR P U M P C O N T R O L MODEL FPC 36040 OWNER S OPERATION MANUAL Advanced Dual Pump Controller Installation and O...

Page 2: ...olated Power supply must be Circuit Breaker Protected Qualified Electrician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Ins...

Page 3: ...UMP 1 P2 P3 P1 COMMON FAULT BMS VOLT FREE COMMON INPUT SHIELDED TRANSDUCER CABLE HYDROSTATIC LEVEL TRANSDUCER SHIELD EARTH 4 20mA Level Transducer 12Vdc T1 T2 Pump 1 Pump 2 THERMAL SWITCH 415Vac MAINS...

Page 4: ...e to run until the Stop Float Contacts open Input functions are as follows Mode B Standard Configuration plus Low Level Alarm As per Mode A except it has an active Low Level input The Low Level input...

Page 5: ...n Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 seconds from close of Input contacts This run on occurs even if Lead...

Page 6: ...ton on the Keypad continuously for a period of 5 seconds the Strobe Siren and indicator Lights will be powered up for inspection Fault Reset To reset all faults on the controller press and old the Mut...

Page 7: ...Edit configuration settings 9 System information and serial number Lines marked with an asterisk require entry of a PIN number for access Note that many of the menu screens feature a prompt along the...

Page 8: ...ged Data screen allows the user to selectively reset logged data values to zero There are four options given reset all reset all excluding pump run hours reset pump 1 run hours and reset pump 2 run ho...

Page 9: ...the value The new value can be committed to the controller by pressing OK otherwise the operation can be canceled by pressing one of the left or right buttons As with the Logged Data Reset this scree...

Page 10: ...en and the opportunity to enter the PIN will again be presented 1 9 4 20mA Display Modes When the APC6 current loop mode is enabled the HMI is able to report the current 4 20mA reading this is shown o...

Page 11: ...d Periods as low as 250ms can be achieved but there can be no guarantee as to the HMI s ability to respond at this rate particularly with write commands Certain Modbus operations require the HMI to in...

Page 12: ...lay R 3 0 255 Seconds 40 Pressure mode min run time R 3 0 255 Seconds 41 Pressure mode alarm delay R 3 0 255 Seconds 42 Alternate high level alarm delay R 3 43 Single pump enable R 3 0 Off 1 On 44 Inh...

Page 13: ...t R 1 3 0 Off 1 On 0x10 18 Low level fault 0x10 19 Pump 1 fault 0x10 20 Pump 2 fault 0x10 21 Low pressure fault 0x10 22 Pump 1 prime loss 0x10 23 Pump 2 prime loss 0x10 24 Inhibit fault 0x18 0x1f 25 3...

Page 14: ...Circuit Breaker 2A CB1 240V 240N 12V 0V Transformer 12Vac T1 12Vac 0Vac A1 A2 Contactor 18A 240Vac C1 A1 A2 Contactor 18A 240Vac C2 95 96 NC Contact TOL1 95 96 NC Contact TOL2 Input 1 Low Level Input...

Page 15: ...Isolator 3P 32A I2 Circuit Breaker 2A CB1 240V 240N 12V 0V Transformer 12Vac T1 12Vac 0Vac A1 A2 Contactor 18A 240Vac C1 A1 A2 Contactor 18A 240Vac C2 95 96 NC Contact TOL1 95 96 NC Contact TOL2 Stro...

Page 16: ...hout notice PUMP 1 PUMP 2 AUTO AUTO Running Idle System OK No Alarms DUAL PUMP CONTROL The HMI AT A GLANCE OK MUTE A quick reference to the controller s HMI and Indicator functions and meanings Scroll...

Reviews: