12
Block
Modbus Address
Register Data
Read/Write
Function Codes
Description
Input Reg
1
I/O States
R
1,3
0=Off,1=On
2
Alarm States
R
1,3
0=Off,1=On
3
System States
R
1,3
0=Off,1=On
4
Mute Alarm
W
5
0=Off,1=On
5
Reset Alarm
W
5
0=Off,1=On
17
4-20mA reading
R
3
4-20mA=40-200
18
APC6 Serial
number (2 characters per register)
R
3
-
19
R
3
-
20
R
3
-
21
R
3
-
22
R
3
-
23
APC6 Software rev
2 characters per register)
R
3
-
24
R
3
-
25
ME16 Software rev
(2 characters per register)
R
3
-
26
R
3
-
27
Pump stop current
R
3
4-20mA=40-200
28
Pump start current
R
3
4-20mA=40-200
29
High level current
R
3
4-20mA=40-200
30
Antiseize period
R
3
0-65535 Hours
31
Antiseize run time
R
3
0-255 Seconds
32
Manual mode timeout
R
3
0-255 Minutes
33
Standard alternate period
R
3
0-255 Minutes
34
Recirc alternate period
R
3
0-65535 Minutes
35
Maximum idle period
R
3
0-65535 Minutes
36
High level alarm delay
R
3
0-65535 Seconds
37
Pump fault delay
R
3
0-255 Seconds
38
Prime fault delay
R
3
0-255 Seconds
39
Pressure mode start delay
R
3
0-255 Seconds
40
Pressure mode min run time
R
3
0-255 Seconds
41
Pressure mode alarm delay
R
3
0-255 Seconds
42
Alternate high level alarm delay
R
3
43
Single pump enable
R
3
0=Off,1=On
44
Inhibit trigger delay
R
3
0-255 Seconds
45
Inhibit fault enable
R
3
0=Off,1=On
46
Inhibit fault threshold
R
3
0-65535
47
Current loop invert
R
3
0=Off,1=On
48
Max run fault delay
R
3
0-65535 Minutes
Registers
65
Pump 1 mode
R/W
03, 06, 16
0=Off,1=Manual,2=Auto
66
Pump 2 mode
R/W
03, 06, 16
0=Off,1=Manual,2=Auto
67
Pump 1 run hours
R/W
03, 06, 16
0- Hrs
68
Pump 2 run hours
R/W
03, 06, 16
0- Hrs
69
Pump 1 start count
R/W
03, 06, 16
0- Number
70
Pump 2 start count
R/W
03, 06, 16
0- Number
71
Pump 1 fault count
R/W
03, 06, 16
0- Number
72
Pump 2 fault count
R/W
03, 06, 16
0- Number
73
High level count
R/W
03, 06, 16
0- Number
74
Low level count
R/W
03, 06, 16
0- Number
75
Power cycle count
R/W
03, 06, 16
0- Number
76
Low pressure alarm count
R/W
03, 06, 16
0- Number
77
Pump 1 prime loss count
R/W
03, 06, 16
0- Number
78
Pump 2 prime loss count
R/W
03, 06, 16
0- Number
2.5 Address Reference
The following tables list all valid Modbus coil and register addresses for the Controller and the data contained within:
MODBUS REGISTERS