10

1.11 PIN Number

In order to modify anything other than the pump auto/off/manual settings, the operator must enter a 4-digit PIN number.

Once the PIN is correctly entered, the system remains unlocked for 15 minutes, after which the PIN will need to be 

entered once again. While unlocked the PIN number can be modified through the configuration settings edit menu.

Enter PIN number to

enable editing:

  

  0000

Press ‘OK’ to accept  

ENTER PIN NUMBER

PIN entry screen

The system information screen also facilitates changing the serial number – this is done by pressing the OK button.

Note that the PIN number is required to change the serial number.

To enter the PIN number, simply use the left and right buttons to select the digit and the up and down buttons to change 

the digit. The default PIN number is 1234.

Note that there is no penalty for entering an incorrect PIN – the HMI will simply return to the previous screen and the 

opportunity to enter the PIN will again be presented.

1.9   4-20mA Display Modes

When the APC6 current loop mode is enabled the HMI is able to report the current 4-20mA reading (this is shown on 

the inputs menu screen). In addition, it can convert this reading into one of two types of scale: metres or kPa. The 

metres scale can be adjusted for a maximum range of 0.1 to 25.0 metres (in 0.1m increments) and the kPa scale can 

be adjusted for a maximum range of 10 to 2500kPa in 10kPa increments.

DPC Serial no: 00000000

DPC firmware rev: 1.01

HMI firmware rev: 1.03

Press ‘OK’ to edit serial

SYSTEM INFORMATION

System information screen

1.10 System Information

The final screen in the list is the System Information screen, which reports serial number and firmware revisions for 

the controller and HMI. Note that the HMI does not include a serial number of its own - the serial number value here is 

supplied by the controller.

PUMP 1                               PUMP 2

AUTO

AUTO

Running

Idle

System OK. No Alarms

LEVEL  

 

     1.5m

Level analogue mode

PUMP 1                               PUMP 2

AUTO

AUTO

Running

Idle

System OK. No Alarms

PRESSURE   

400kPa

Pressure analogue mode

Summary of Contents for FPC-36040

Page 1: ...PUMP 1 PUMP 2 AUTO AUTO Running Idle System OK No Alarms DUAL PUMP CONTROL MAIN ISOLATOR P U M P C O N T R O L MODEL FPC 36040 OWNER S OPERATION MANUAL Advanced Dual Pump Controller Installation and O...

Page 2: ...olated Power supply must be Circuit Breaker Protected Qualified Electrician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Ins...

Page 3: ...UMP 1 P2 P3 P1 COMMON FAULT BMS VOLT FREE COMMON INPUT SHIELDED TRANSDUCER CABLE HYDROSTATIC LEVEL TRANSDUCER SHIELD EARTH 4 20mA Level Transducer 12Vdc T1 T2 Pump 1 Pump 2 THERMAL SWITCH 415Vac MAINS...

Page 4: ...e to run until the Stop Float Contacts open Input functions are as follows Mode B Standard Configuration plus Low Level Alarm As per Mode A except it has an active Low Level input The Low Level input...

Page 5: ...n Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 seconds from close of Input contacts This run on occurs even if Lead...

Page 6: ...ton on the Keypad continuously for a period of 5 seconds the Strobe Siren and indicator Lights will be powered up for inspection Fault Reset To reset all faults on the controller press and old the Mut...

Page 7: ...Edit configuration settings 9 System information and serial number Lines marked with an asterisk require entry of a PIN number for access Note that many of the menu screens feature a prompt along the...

Page 8: ...ged Data screen allows the user to selectively reset logged data values to zero There are four options given reset all reset all excluding pump run hours reset pump 1 run hours and reset pump 2 run ho...

Page 9: ...the value The new value can be committed to the controller by pressing OK otherwise the operation can be canceled by pressing one of the left or right buttons As with the Logged Data Reset this scree...

Page 10: ...en and the opportunity to enter the PIN will again be presented 1 9 4 20mA Display Modes When the APC6 current loop mode is enabled the HMI is able to report the current 4 20mA reading this is shown o...

Page 11: ...d Periods as low as 250ms can be achieved but there can be no guarantee as to the HMI s ability to respond at this rate particularly with write commands Certain Modbus operations require the HMI to in...

Page 12: ...lay R 3 0 255 Seconds 40 Pressure mode min run time R 3 0 255 Seconds 41 Pressure mode alarm delay R 3 0 255 Seconds 42 Alternate high level alarm delay R 3 43 Single pump enable R 3 0 Off 1 On 44 Inh...

Page 13: ...t R 1 3 0 Off 1 On 0x10 18 Low level fault 0x10 19 Pump 1 fault 0x10 20 Pump 2 fault 0x10 21 Low pressure fault 0x10 22 Pump 1 prime loss 0x10 23 Pump 2 prime loss 0x10 24 Inhibit fault 0x18 0x1f 25 3...

Page 14: ...Circuit Breaker 2A CB1 240V 240N 12V 0V Transformer 12Vac T1 12Vac 0Vac A1 A2 Contactor 18A 240Vac C1 A1 A2 Contactor 18A 240Vac C2 95 96 NC Contact TOL1 95 96 NC Contact TOL2 Input 1 Low Level Input...

Page 15: ...Isolator 3P 32A I2 Circuit Breaker 2A CB1 240V 240N 12V 0V Transformer 12Vac T1 12Vac 0Vac A1 A2 Contactor 18A 240Vac C1 A1 A2 Contactor 18A 240Vac C2 95 96 NC Contact TOL1 95 96 NC Contact TOL2 Stro...

Page 16: ...hout notice PUMP 1 PUMP 2 AUTO AUTO Running Idle System OK No Alarms DUAL PUMP CONTROL The HMI AT A GLANCE OK MUTE A quick reference to the controller s HMI and Indicator functions and meanings Scroll...