In pressure pump mode some of the optional features are disabled, including maximum run alternation, anti-seize and 

maximum idle timers

In order to activate current loop mode the enclosure must be opened and jumper J10 moved to the “current loop 

enabled” position (as shown in the following picture). By selecting current loop input mode the pump start input can 

be connected to a 4-20mA loop powered pressure transducer. The pump start, stop and high level signals can then 

desired. The start, stop and high level current set points will be pre-programmed into the software and therefore cannot 

be adjusted. The levels for a 0-4m transducer are Stop= 300mm, Start= 600mm and High= 1000mm.

 

 

 

Anti-Seize Timer

With DIP Switch 4 set to “On”, the Anti-seize timer will automatically run the pumps for 6 seconds, every 7 days. This 

pump operation will completely override all inputs including the low level (if enabled). This feature will only run pumps 

that are set in Auto. This “Pump Run”, will alternate between Pump 1 and Pump 2. A pump that has been locked out 

due to a fault will not run.

Manual Mode Timeout

With DIP Switch 5 set to “On” the pump will only remain in Manual Mode for 5 minutes, after which time, it automatically 

reverts to Auto.

High Level Alarm Reset

The controller will also use the alternate High Level Alarm Delay. Typically used for Storm Water applications. High 

Level Alarm delay in this mode is 15 minutes. Setting this DIP Switch to “On”, will cause the High level Alarm to

remain active until the controller is reset. The High Level Alarm will use the standard High Level Alarm activation delay.

Typically used for Sewerage applications. High Level Alarm delay in this mode is 5 minutes.

Audible and Visual Alarm Test

By pressing the 

Mute/Reset

 button on the Keypad continuously for a period of 5 seconds, the Strobe, Siren and

indicator Lights will be powered up for inspection.

Fault Reset

To reset all faults on the controller, press and old the Mute/Reset button on the Keypad continuously for a period of 3 

seconds until an acknowledgment beep is heard.

Pump Fault

A Pump Fault is indicated for two types of faults. A Thermal Overload will be indicated by way of a steady Fault

fault light slowly.

Level Alarms

A High Level Alarm is indicated by way of a steady Level Alarm Indicator Light.

A Low Level/Low pressure Alarm is indicated by way of a Flashing Level Alarm Light.

Auto Silencing Alarm Feature

The audible Alarm is programmed to sound for 5 minutes continuously, unless muted and will thereafter automatically 

Figure 1: APC6 PCB Layout and Current Loop Jumper 

 

 

Current Loop

Enable Jumper

 

Dip Switch Setting

Ensure dip switch 1 and 2 are down 

in mode A for transducer operation 

Summary of Contents for FPC-15007

Page 1: ...MAIN ISOLATOR DOC FPC 15007 VER 2 0 P U M P C O N T R O L OWNER S OPERATION MANUAL Single Pump Controller Installation and Operating Instructions MODEL FPC 15007 ...

Page 2: ...must be Circuit Breaker Protected Qualified Electrician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Instructions see page 3 Addition or modifications to the control panel are not permitted and will void warranty The controller is not intended for use by children or infirm persons without supervision Repairs to the Control...

Page 3: ... 415Vac Connections E P1 P2 P3 N E A1 A2 A3 Input 1 Low Level Input 2 Stop Level Input 3 Start Level Input 4 High Level INPUT SWITCHES T1 T2 THERMAL 12Vdc Connections COMMON FAULT BMS VOLT FREE PUMP REMOVE BRIDGE WIRE TO USE LOW LEVEL FLOAT ON STEADY A pump fault overload has occured FLASHING MOMENTARY PRESS To mute audible buzzer PRESS FOR 3 SECS To reset alarms and faults PRESS CONTINUOUS To tes...

Page 4: ... in Manual Mode after 5 minutes the pump will revert to Auto 6 Off High Level Alarm automatically resets upon open circuit of high level input High Level alarm has 15 minute delay On High Level Alarm can only be reset manually High Level Alarm has 5 minute delay Mode A Standard Configuration Start Stop High Level operation When the Pump Start input is closed contact triggered the Duty Pump will be...

Page 5: ...cts This run on occurs even if Pressure switch contacts open during this initial period If however run time exceeds 11 seconds the pump will stop immediately upon open circuit occurring If the Pressure Switch Input closes circuit as well as the Low Pressure Switch Input a low pressure timer will begin counting If this condition exists for a period of 60 seconds then both pumps are shut down and th...

Page 6: ...Reset The controller will also use the alternate High Level Alarm Delay Typically used for Storm Water applications High Level Alarm delay in this mode is 15 minutes Setting this DIP Switch to On will cause the High level Alarm to remain active until the controller is reset The High Level Alarm will use the standard High Level Alarm activation delay Typically used for Sewerage applications High Le...

Page 7: ...ACTOR COIL PUMP R O T C A T N O C MAIN ISOLATOR 2 Amp CIRCUIT BREAKER STROBE BUZZER TRANSFORMER 12Vac 415Vac 240Vac INPUT 1 SWITCH INPUT 2 SWITCH INPUT 3 SWITCH INPUT 4 SWITCH 12Vdc 12Vdc P1 P2 P3 E R1 COMMON FAULT BMS VOLT FREE R1 1 CIRCUIT DIAGRAM ...

Page 8: ...ALARM ON A high level alarm has been present for the preset time FLASHING A low level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime loss fault has occurred Silences the siren and if held down for 3 seconds clears all faults If selected the LED indicator will confirm if on the particular pump is set to Automatic Pumping Mode Turns p...

Reviews: