HRH-5

8595188136396

Indication of supply voltage
Choice of function

Function PUMP UP                                                                     Function PUMP DOWN

Relay is designed for monitoring levels in wells, basins, reservoirs, tanks...
In one device you can choose the following confi gurations:
- one-level switch of conductive liquids (by connecting H and D)
- two-level switch of conductive liquids
One-state device monitors one level, two-state device monitors two levels (switches on one level 
and switches off  on another level)
Choice of function PUMP UP, PUMP DOWN
Adjustable time delay on the output (0.5 - 10s)
Sensitivity adjustable by a potentiometer (5-100kΩ)
Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes
Galvanically separated supply voltage UNI 24.. 240 VAC/DC
Output contact 1xchangeover/SPDT  8A/250V AC1
1-MODULE, mounting onto a  DIN rail

Level switch 

HRH-5

Monitoring of two levels    

2

A1 - A2

24... 240 V AC/ DC (AC 50 - 60 Hz)

max. 2 VA

-15 %; +10 %

adjustable in range 5 kΩ -100 kΩ

max. AC 3.5 V

AC <0.1 mA

max. 400 ms

800 nF (sensitivity 5kΩ), 100 nF (sensitivity 100 kΩ)

adjustable, 0.5 -10 sec

1.5 sec

± 5 %

1x changeover/ SPDT (AgNi / Silver Alloy )

8 A / AC1

2500 VA , 240 W 

250 V AC1 / 24 V DC

500 mW

1x10

7

1x10

5

-20 °C to +55 °C (-4 °F to 131 °F)

-30 °C to +70 °C (-22 °F to 158 °F)

3.75 kV (supply - sensors)

any

DIN rail EN 60715

IP 40 from font panel / IP 10 terminals

III.

2

AWG 10 (2.5 mm2)

90 x 17.6 x 64 mm (3.5˝ x 0.7˝ x 2.5˝)

72 g (2.5 oz.)                       

 EN 60255-6,  EN 61010-1

 see pg. 90-91

Functions:
Supply terminals:
Voltage range:
Input:
Toleration of voltage range:
Measuring circuit
Sensitivity ( input resistance):
Voltage n electrodes:
Current in probes:
Time response:
Max. capacity of probe cable:
Time delay (t):
Time delay after switching on (t1):
Accuracy
Accuracy in setting (mechanical):
Output
Number of contacts:
Current rating:
Switching voltage:
Switched voltage:
Min. switched output DC:
Mechanical life (AC1):
Electrical life:
Other information
Operational temperature:
Storing temperature:
Electrical strenght:
Operational position:
Mounting:
Protection degree:
Overvltage category:
Pollution degree:
Profi le of connecting wires (mm

2

):

Dimensions:
Weight:
Standards:
Recommended measuring probes:

Connection

Function

Device description

Technical parameters

Tank with

 monitored level

Relay is designated for monitoring of levels of conductive liquids with possibility of functions: PUMP UP 

or PUMP DOWN. To prevent polarization and liquid electrolysis of liquid, and undesirable oxidation of 

measuring probes, alternating current is used. For measuring use three measuring probes: H- upper level, 

D-  lower level, C - common probe. In case you use a tank made of a conductive material, you can use 

it as probe C. In case you require monitoring of one level only, it is neccessary to connect inputs H and 

D and connect them to one probe - in this case sensitivity is lowered by half  (2.5... 50kΩ). Probe C can 

be connected with a protective wire of supply  system (PE). To prevent undesirable switching out output 

contacts by various infl uences (sediment on probes, humidity...) it is possible to set sensitivity of the device 

according to conductivity of monitored liguid (corresponding to “resistance” of liquid) range 5 up to 100kΩ. 

To reduce infuences of undesirable switching of output contacts by liquid gorgle in tanks, it is possible to set 

delay of output reaction 0.5 - 10s.

Symbol

!

!

!

!

!

!

!

!

!

!

Monioring of one level   

Un

max

level

min

15-18

red LED

Un

max

level

min

15-18

red LED

Tank with 

monitored level

     Supply voltage terminals

Terminals for conection of 

probes H, D

Output indication

Choice of function

Adjustment of 

delay on output

  Terminal for connection of 

probe C

Output contacts

EAN code

HRH-5 /UNI

Summary of Contents for FPC-15007-CON

Page 1: ...Single Pump Controller Installation and Operating Instructions MODEL FPC 15007 CON MAIN ISOLATOR DOC FPC 15007 CON VER 1 0 P U M P C O N T R O L OWNER S OPERATION COMMISIONING MANUAL ...

Page 2: ...by a suitably qualified Electrician SAFETY WARNING All electrical connections must be carried out by a suitably qualified and registered electrician SAFETY 2 HRH 5 DATA SHEET 7 INSTALLATION 3 CIRCUIT DIAGRAM 10 Mounting Connection NOTES 11 AT A GLANCE 12 Indicators GETTING STARTED 4 Push Buttons Operations Features Your Single Pump Controller reflects the superior quality and attention to detail i...

Page 3: ...A1 PUMP P2 P3 E P1 T1 T2 Therm 12Vdc BRIDGE IF NOT REQUIRED Mounting Frame Wall INSTALLATION CONNECTION MOUNTING 1 Controller enclosure must be mounted in a vertical position 2 Ensure mounting method does not compromise enclosure weather proof rating 3 Ensure access to main isolator is not restricted 4 Ensure cables conduits entering the panel have mechanical protection and that the penetrations a...

Page 4: ... in Manual Mode after 5 minutes the pump will revert to Auto 6 Off High Level Alarm automatically resets upon open circuit of high level input High Level alarm has 15 minute delay On High Level Alarm can only be reset manually High Level Alarm has 5 second delay Mode A Standard Configuration Start Stop High Level operation When the Pump Start input is closed contact triggered the Duty Pump will be...

Page 5: ...cts This run on occurs even if Pressure switch contacts open during this initial period If however run time exceeds 11 seconds the pump will stop immediately upon open circuit occurring If the Pressure Switch Input closes circuit as well as the Low Pressure Switch Input a low pressure timer will begin counting If this condition exists for a period of 60 seconds then both pumps are shut down and th...

Page 6: ...larm will automatically reset once the High Level input opens circuit The controller will also use the alternate High Level Alarm Delay Typically used for Storm Water applications High Level Alarm delay in this mode is 15 minutes Setting this DIP Switch to On will cause the High level Alarm to remain active until the controller is reset The High Level Alarm will use the standard High Level Alarm a...

Page 7: ...ction PUMP UP Function PUMP DOWN Sensitivity adjustable by a potentiometer 5 100kΩ Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes Galvanically separated supply voltage UNI 24 240VAC DC Output contact 1xchangeover SPDT 8A 250V AC1 1 MODULE mounting onto a DIN rail Monitoring of two levels Ω Connection Function Device description Tank with monitore...

Page 8: ...sistance Voltage n electrodes Current in probes Time response Max capacity of probe cable Time delay t Time delay after switching on t1 Accuracy Accuracy in setting mechanical Output Number of contacts Current rating Switching voltage Switched voltage Min switched output DC Mechanical life AC1 Electrical life Other information Operational temperature Storing temperature Electrical strenght Operati...

Page 9: ...se a tank made of a conductive material you can use it as probe C In case you require monitoring of one level only it is neccessary to connect inputs H and D and connect them to one probe in this case sensitivity is lowered by half 2 5 50kΩ Probe C can be connected with a protective wire of supply system PE To prevent undesirable switching out output contacts by various influences sediment on prob...

Page 10: ...40N 12V 0V Transformer 12Vac T1 P1 P2 P3 A1 A2 Contactor 18A 240Vac Contactor 1 Strobe Light Buzzer Inline Relay 12Vdc R1 Common Fault BMS Volt Free 1 2 3 4 5 6 O N A1 A2 C D H Conductivity Relay CR1 A1 A2 C D H Conductivity Relay CR2 PROBE INPUT Low Voltage Stop Common Start High 95 96 NC Contact TOL1 Thermal Switch 18 15 NO Contact CR1 1 18 15 NO Contact CR2 1 R1 1 CIRCUIT DIAGRAM ...

Page 11: ...11 NOTES ...

Page 12: ... ALARM ON A high level alarm has been present for the preset time FLASHING A low level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime loss fault has occurred Silences the siren and if held down for 3 seconds clears all faults If selected the LED indicator will confirm if on the particular pump is set to Automatic Pumping Mode Turns ...

Reviews: