Matan Barak Technical Note Download Page 4

 

9.  Verify that the original green connector is not burnt and that 

there are no black marks on it. 

10. Connect the original green connector to the new PLC. 

11. Reconnect the three wires to the 24v (white connector). 

12. Power up the printer.  

Replacing the Block PLC Hardware 

From the Replacing the Machine PLC Hardware section, repeat 

steps #1-12. 

Updating the Block/Machine PLC Software 

Burning a File into the PLC 

¾

 

Burn a File into the PLC: 

1.  Double click the ‘

DVPServer

’ application at 

C:\Program 

Files\Matan Barak FE\Drivers\Delta

 to enter the 

DVP_Tool

2. Click O

PEN

 to chose the desired 

*.DVZ

 

file (

BlockPLC.dvz

 

or 

MachinePLC.dvz

) by double clicking it, as shown below. 

 

3. Click W

RITE TO 

PLC to open the C

OMMUNICATION

 S

ETTINGS

 dialog 

box. 

4.  Configure the parameters in the C

OMMUNICATION

 S

ETTINGS

 dialog 

box, and note the S

TATION 

A

DDRESS

 and the COM

 

P

ORT

Both the Machine and Block PLC allocation is for the same 
COM Port and it is set according to the Barak FE in the 

E

NGINEERING

 dialog box (Currently set to COM8). 

10100142 - A

 

© Matan Digital Printers Ltd.    

Page 4 of 8 

Summary of Contents for Barak

Page 1: ...Replacing the PLCs Technical Note 10100142 Rev A 10100142 A Matan Digital Printers Ltd Page 1 of 8 ...

Page 2: ...ter Barak s PLCs There are two PLCs PROGRAMMABLE LOGIC CONTROLLERS installed on the printer The MACHINE PLC is installed to the left of the POWER SWITCH at the rear right corner of the printer as shown in the figure below The Machine PLC The Machine PLC The BLOCK PLC is installed at the top rear of the CARRIAGE as shown in the following two figures The Block PLC The Block PLC general view 10100142...

Page 3: ...om underneath the PLC you wish to replace 6 Remove the PLC from the printer by pulling the white clips and removing it from the rail If you are changing only one module make sure that you firmly connect the module s connectors as shown above 7 Make sure that the new PLC s switch is set to STOP 8 Attach the new PLC to the rail by lifting the white clip on top of the PLC and the one that is located ...

Page 4: ... the PLC 1 Double click the DVPServer application at C Program Files Matan Barak FE Drivers Delta to enter the DVP_Tool 2 Click OPEN to chose the desired DVZ file BlockPLC dvz or MachinePLC dvz by double clicking it as shown below 3 Click WRITE TO PLC to open the COMMUNICATION SETTINGS dialog box 4 Configure the parameters in the COMMUNICATION SETTINGS dialog box and note the STATION ADDRESS and t...

Page 5: ... Digital Printers Ltd Page 5 of 8 For Machine_PLC the STATION ADDRESS should be set to 2 as shown below Change this field from COM13 to COM8 5 Click UPDATE for PLC updating by the correct file The following message appears 6 Click YES to confirm The UPDATE starts When the UPDATE has finished the following message appears ...

Page 6: ... to close the COMMUNICATION dialog box 10 Choose another DVZ file by clicking OPEN again or click EXIT to close the DVP_Tool Machine PLC is located at the right side of the printer next to the UV power supplies and the main electric panel 10100142 A Matan Digital Printers Ltd Page 6 of 8 ...

Page 7: ...rinter S N Faulty Part Name Details of faulty part Remarks Signed Name Position in Company Date The Printer s Serial Number is displayed on the label located at the rear of the printer near the left end of the rollers as shown below 10100142 A Matan Digital Printers Ltd Page 7 of 8 ...

Page 8: ...ark Afek Rosh Ha ayin 48092 Israel Tel 972 3 9002720 Fax 972 3 9002721 Email support matanprinters com U S Office Matan USA Inc 90 Earhart Drive Suite 4 Williamsville NY 14221 Tel 1 716 631 3770 Fax 1 716 631 3576 Email for customer support support matanprinters com Europe Office Matan EU C Rosalia de Castro 21 08025 Barcelona Spain Tel 34 902 932825 Fax 34 902 932826 Email for customer support su...

Reviews: