MAINTENANCE 

 

US / WHISPER 15 ULTRA - Three Phase / December 2008 / Copyright © 2008 Mastervolt  

  

25

 

 

4 MAINTENANCE 

 

4.1 ALTERNATOR 

 

The alternator does not require any maintenance. Periodic 
inspection and cleaning is recommended, depending on 
environmental conditions.  
However when the alternator has been idle for a long 
period attention to winding condition is recommended.  
The condition of windings can be assessed by 
measurement of insulation resistance to earth. (See 0 
Meggering).  
The alternator bearing is greased for life and is therefore 
not regreasable 
 

4.2 ENGINE 

 

 

4.2.1 

Preliminary instructions  

All regular maintenance can be carried out when the 
enclosure is open. When oil and dirt has gathered in the 
enclosure measures have to be taken to avoid spilling oil 
and polluting the environment.  
The first service on the engine should be carried out after 
50 hours of its life and after a major overhaul. In the first 
50 hours the engine should receive special attention:  
 
Long periods of light or no load running in the first 50 
hours may lead to cylinder glazing and high oil 
consumption. 
 

For the same reason it is of the greatest 
importance to use the right oil specification  
 

 
The first time starting up or after running out of fuel it could 
be necessary to prime the fuel system.  
 

4.2.2 

Bleeding fuel lines   

Ensure there is sufficient fuel. The system is self bleeding. 
The first time starting up or after running out of fuel it could 
be necessary to prime the fuel system. Push the start 
button activating the electric system and activating the fuel 
pump. When more time is needed to bleed, push “start” 
and hold on the local control panel (so not on the remote 
panel) Hold as long as necessary to bleed the system. 
Retighten the bleed screw when no further air bubbles are 
expelled. 

Fig. 17: Bleeding fuel lines          1 = Fuel bleeding screw 
 

4.2.3 

Valve clearance  

When the engine is in cold condition both valves (inlet and 
outlet) should have a clearance between 0.25 mm. The 
adjustment has to be done at TDC (refer to § 5.4.2). 
 

4.2.4 

Replacing fuel filter  

Filter change depends on contamination of the fuel, but 
should be done however, at least every 300 running hours. 
Before changing the filter, clamp off the supply line. 
Remove the hoses from filter and attach them on the new 
filter again. The arrow on the filter housing indicates the 
direction of the flow. A clogged filter results in a lack of 
output of the generating set.  
 

4.2.5 

Replacing oil filter  

The oil filter is in front of the service side. Replacement 
has to be executed according to the schedule in this 
manual. Drain the oil using the sump pump and put some 
tissues under the filter. 

 

Fig. 18 

Summary of Contents for WHISPER 15 ULTRA

Page 1: ...RA Three phase 1800 RPM Marine diesel generating set 120 208V 60Hz Digital Diesel Control MASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www master...

Page 2: ...losion 8 2 1 7 Chemicals 8 2 2 Transport lifting and storage 9 2 3 The Whisper 15 ULTRA Three Phase 9 2 3 1 Features 9 2 3 2 Remote control 9 2 3 3 Documentation 9 2 3 4 Accessories included in the st...

Page 3: ...er 25 4 2 6 Readjustment V beltplacing oil filter 26 4 3 Regular maintenance 26 4 3 1 Maintenance schedule 27 4 3 2 Putting out of service 28 5 TROUBLE SHOOTING 29 5 1 Alternator electrical faults 29...

Page 4: ...ipment severe personal injury or loss of life DANGER This danger symbol refers to electric danger and draws attention to special warnings instructions or procedures which if not strictly observed may...

Page 5: ...be issued For example if a Printed Circuit Board is returned with clear damage caused by seawater guarantee will be refused Freight costs to deliver spares by normal mail or carriers is covered under...

Page 6: ...shows the maximum current that is acceptable at the specified frequency voltage and power factor When connected in tri phase the indicated current is the current between two phases that can be taken o...

Page 7: ...tection must be done in accordance with local standards Using the auto start stop interval mode the generator can start unexpectedly When working on the electrical system the 3 Amp fuse must be remove...

Page 8: ...er ventilation Do not smoke or allow sparks flames or other sources of ignition around batteries Keep a fire extinguisher on hand INCASEOFFIRE DONOTOPENSOUNDSHIELD TOAVOIDSERIOUSINJURYORDEATHFROM FIRE...

Page 9: ...an alternator in a sound attenuated capsule The set is mounted on a steel base frame and mounted securely on anti vibration mounting pads to the capsule base All cables and hoses are guided through th...

Page 10: ...ld watercooled 18 Alternator 12VDC 19 Engine coolant pump 20 V belt 21 Raw water pump 22 Cooling water injection bend 23 Rubber engine mounting 24 Starter motor solenoid 25 Starter motor 26 Heat excha...

Page 11: ...ilsafe 45 Temperature switch exhaust 46 Filler cap engine coolant 47 Rocker cover 48 Filler cap engine oil 49 Temperature switch coolant 50 Thermostat housing 27 Engine speed adjusting screw 28 Inject...

Page 12: ...controls and keeps constant the average voltage of one phase The voltage setting on the AVR can be adjusted with the help of a trimmer V between 100 and 140 Volts or 200 and 280V nominal voltage 230V...

Page 13: ...y a heat exchanger and raw water The heat exchanger and all other parts which are in direct contact with the raw sea water are made of seawater resistant material like naval brass and gunmetal The eng...

Page 14: ...cluding the oil filter it is 6 U S qts 5 7 l Note that the engine may contain some residual oil due to testing at the factory While filling check the lubricating oil level by means of the engine oil d...

Page 15: ...dependent Control Digital Diesel Control including automatic start stop ELECTRICAL SPECIFICATIONS Output voltage 120 240V 3x 120V or 3x 120 208V 60Hz alternating current AC Output rating 60Hz 15 kVA...

Page 16: ...m2 DDC fuel solenoid pull 20 pink 16 1 5 mm2 DDC fuel solenoid com 17 black 16 1 5 mm2 B terminal alternator starter motor 21 red 10 6 mm2 DDC R terminal alternator 18 white 16 1 5 mm2 DDC L terminal...

Page 17: ...INFORMATION US WHISPER 15 ULTRA Three Phase December 2008 Copyright 2008 Mastervolt 17 2 5 16 Lay out control wiring Fig 12 Electrical Diagram control wiring Whisper 15 Ultra Three Phase...

Page 18: ...INFORMATION 18 Copyright 2008 Mastervolt December 2008 WHISPER 15 ULTRA Three Phase US 2 5 17 Overview of AC terminal modes Whisper 15 Ultra Three phase Fig 13 Terminal modes Whisper 15U Three phase...

Page 19: ...15 ULTRA Three Phase December 2008 Copyright 2008 Mastervolt 19 2 5 18 AC wiring diagram 120 208 V AC 60 Hz three phase with AVR star configuration Fig 14 AC wiring diagram three phase 3 x 120 208 Vol...

Page 20: ...ght 2008 Mastervolt December 2008 WHISPER 15 ULTRA Three Phase US 2 5 19 AC wiring diagram Split Phase 120 240Volt 60Hz with AVR DOUBLE DELTA Figure 15 AC wiring diagram Split Phase 120 240Volt 60Hz w...

Page 21: ...voltage and more power The electronic governor system contains two parts 1 The actuator controls the engine speed This actuator replaces the standard hold solenoid that is on all other mechanical cont...

Page 22: ...Stopping generator 1 Switch off all electrical devices consumers If the generating set has been running under full load for a longer period do not shut it down abruptly Reduce the electrical load to...

Page 23: ...uainted with the generator you will be able to recognise the coolant flowing through the system by listening for the noise of the water which is expelled Be aware that especially in harbours the coola...

Page 24: ...er to cool the engine If the generator is operating in a hot environment and you do not act as given above the excessive heat in the engine can trip the high temp alarms In that case a restart of the...

Page 25: ...out of fuel it could be necessary to prime the fuel system 4 2 2 Bleeding fuel lines Ensure there is sufficient fuel The system is self bleeding The first time starting up or after running out of fuel...

Page 26: ...oil when necessary Check and tighten nuts bolts and unions paying particular attention to the fuel system Observe the exhaust at the normal full load The exhaust must be free from soot Do not allow t...

Page 27: ...ven impeller pump through the cooler elements in the generator housing All parts of the cooling system are of corrosion free and seawater resistant materials such as brass and gunmetal In case of gath...

Page 28: ...servation oil 4 Stop the engine and take loose the inlet of the raw water pump Drain the water from the water lock Crank the engine having the raw water inlet sucking anti freeze from a can until the...

Page 29: ...ces should the RPM under full load be below 1782 RPM 59 4 Hz When the problem is in the RPM refer to the engine fault finding paragraph Digital Diesel Control system will help to indicate failures and...

Page 30: ...R if necessary see special procedures Generator output voltage too high without load more than 125V between phase and neutral Over energising due to defective AVR or wrong AVR setting Check AVR readju...

Page 31: ...high OIL PRESSURE Oil pressure failure AC VOLTAGE Generator AC output voltage is either too high or too low HIGH CURRENT Generator is in overload FREQUENCY Output frequency of the generator is too lo...

Page 32: ...f electrical load is fluctuating Faulty fuel lift pump Check and repair Choked air filter Lack of air Check the air intake Choked exhaust system exhaust blocked rubber exhaust hose kinked Check the ex...

Page 33: ...air or fuel filter Check cooling water system flow water pump inlet water filter coolant flow Loss of compression by wear out or damage Repair by Mastervolt service V belt broken or loose Readjust or...

Page 34: ...iter the frequency can be calibrated by trimmer UF which is factory set at 56Hz 60Hz nominal 46Hz 50Hz nominal 1Hz On reaching this frequency the machine begins to reduce its voltage until it deactiva...

Page 35: ...nfinity in the reverse direction and a low resistance in the forward direction A faulty diode will give a full deflection reading in both directions with the test meter on the 10 000 ohms scale or an...

Page 36: ...First align the T D C mark for the No 1 cylinder Confirm that the valves do not move up or down when the crankshaft is turned about 20 degrees in normal and reverse direction of rotation If the rocke...

Page 37: ...ings and by removing the safeguards The easiest way to get the generator out of its capsule is by lifting the set using the lifting eyes 4 One can take off the complete alternator housing Before the a...

Page 38: ...SPARE PARTS LIST 38 Copyright 2008 Mastervolt December 2008 WHISPER 15 ULTRA Three Phase US Figure 29 exploded view sound shield Whisper 15 Ultra Three Phase...

Page 39: ...haft 50201811 Bearings 2 pcs 50209014 O ring 50209017 Seals 2 pcs 50209015 Clips 1 set 50209019 O ring 50201814 50209010 Pump repair kit B same as repair kit A excluding the shaft 5021811 and O ring 5...

Page 40: ...209011 Impeller kit Bearing 50209014 50209016 Circlip 50201811 Shaft Male hose connector 50221031 Pump housing 50201414 Seal 50209015 50209018 Screw cover Cover type M12 50201401 Gasket 50209012 Impel...

Page 41: ...MAINTENANCE LOG US WHISPER 15 ULTRA Three Phase December 2008 Copyright 2008 Mastervolt 41 MAINTENANCE LOG first service after 50 hours hour counter remarks next service every 150 hours hour counter...

Page 42: ...NOTES 42 Copyright 2008 Mastervolt December 2008 WHISPER 15 ULTRA Three Phase US NOTES...

Page 43: ...NOTES US WHISPER 15 ULTRA Three Phase December 2008 Copyright 2008 Mastervolt 43 NOTES...

Page 44: ...Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 Email info mastervolt com...

Reviews: