AC Master 12/300, 12/500, 24/300, 24/500 – User and Installation Manual 

 

 

 

Step 3.   Select a location to install. 

•  Install the AC Master in a well-ventilated room protected against rain, snow, spray, vapour, bilge, 

moisture and dust.  

•  Ambient temperature: -20 to 40°C / -4 to 104°F. 
•  Never use the AC Master at a location where there is danger of gas or dust explosions. Mount 

the AC Master vertically with the cables hanging downwards and so that airflow through the 
ventilation openings is guaranteed. Mounting the AC Master in another position is possible but 
influences the ingress protection degree (IP)! 

•  No objects are to be located within a distance of 10 cm / 4 inch around the AC Master. 
•  Do not install the AC Master in the same compartment as the batteries. Do not mount the AC 

Master straight above the batteries because of possible corrosive sulphur fumes. 

Step 4.   Remove the fuse cover and DC fuse(s). 

 

Step 5.   Mount the AC Master with four screws to a solid surface. 

 

Step 6.   Connect the chassis ground terminal to the central grounding point of the vehicle/ship.

 

 

Summary of Contents for AC Master 12/300

Page 1: ...AC Master 12 300 12 500 24 300 24 500 PURE SINE WAVE INVERTER USER AND INSTALLATION MANUAL 1000014304 01 To download this manual in other languages please visit our website www mastervolt com...

Page 2: ...Installation Manual Table of contents 1 Safety instructions 3 2 Liability 3 3 Disclaimer 3 4 Warranty 3 5 Correct disposal of this product 3 6 Product description 4 7 Installation instructions 5 8 Ope...

Page 3: ...Disclaimer Our products are subject to continual development and improvement Therefore additions or modifications to the products may cause changes to the technical data and functional specifications...

Page 4: ...e wave inverter The AC Master converts DC power from the battery into AC output power Identification label Part number Serial number J821A0001 with device version A Important information required for...

Page 5: ...DC fuse s 3 DC input cables 1 5m 4 Chassis ground terminal M6 5 AC output socket IEC 7 Installation instructions This section provides a step by step instruction of the basic installation of the AC Ma...

Page 6: ...that airflow through the ventilation openings is guaranteed Mounting the AC Master in another position is possible but influences the ingress protection degree IP No objects are to be located within...

Page 7: ...tallation The neutral conductor N of the AC output of the AC Master must be connected to the safety ground PE GND Integrate a ground fault circuit interrupter GFCI RCD in the wiring of the AC output R...

Page 8: ...detected higher than the threshold value the inverter is switched on Switching OFF Move the main switch to the position O OFF Note that switching off the AC Master does not disconnect the batteries LE...

Page 9: ...attempts restarting 5 times If it still fails the AC Master remains in Overload Reduce the load and or check the AC wiring for possible short circuits Then reset the inverter manually by switching the...

Page 10: ...g Approvals CE E mark CE E mark Technical Technology High frequency High frequency DC input voltage range 10 0 15 5V 20 0 31 0V Low battery voltage switches off at 10 0V 3 20 0V 3 Low battery voltage...

Page 11: ...ls CE E mark CE E mark Technical Technology High frequency High frequency DC input voltage range 10 0 15 5V 20 0 31 0V Low battery voltage switches off at 10 0V 3 20 0V 3 Low battery voltage switches...

Page 12: ...0 3422100 Email info mastervolt com Web www mastervolt com Copyright 2018 Mastervolt All rights reserved Reproduction transfer distribution or storage of part or all of the contents in this document i...