![Mastervolt 81205100 User And Installation Manual Download Page 20](http://html1.mh-extra.com/html/mastervolt/81205100/81205100_user-and-installation-manual_1738961020.webp)
20
Mac Plus
–
User and Installation Manual
Value
Meaning
Factory setting
Adjustable range
Start bulk time
Start bulk timer
13.25 V
8-15 / 16-30 V
Bulk ret. volt
Return to bulk voltage
12.80 / 25.60 V
8-15 / 16-30 V
Bulk return time
Return to bulk time delay
30 s
0-240 s
Absorption
Abs. voltage
Absorption voltage
14.25 / 28.50 V
8-15 / 16-30 V
Max absorp. time
Maximum absorption time
240 min
0-1440 min
Min absorp. time
Minimum absorption time
15 min
0-240 min
Return amps
Return amps (% of maximum
charge current)
6 % or
10 %
0-50 %
Float
Float voltage
Float voltage
13.25 / 26,50 V
8-15 / 16-30 V
Constant
voltage
Constant voltage
Constant output voltage
13.25 / 26.50 V
8-15 / 16-30 V
Input alarm
High alarm on
High input voltage alarm on
16.00 / 32.00 V
8-16 / 16-32 V
High alarm off
High input voltage alarm off
15.50 / 31.00 V
8-16 / 16-32 V
Low alarm off
Low input voltage alarm off
11.00 / 22.00 V
8-16 / 16-32 V
Low alarm on
Low input voltage alarm on
10.00 / 20.00 V
8-16 / 16-32 V
Low alarm delay
Low input alarm delay time
5 s
0-300 s
Output alarm
High alarm on
High output voltage alarm on
15.25 / 30.50 V
8-16 / 16-32 V
High alarm off
High output voltage alarm off
14.75 / 29.50 V
8-16 / 16-32 V
Low alarm off
High output voltage alarm off
11.00 / 22.00 V
8-16 / 16-32 V
Low alarm on
High output voltage alarm on
10.00 / 20.00 V
8-16 / 16-32 V
Low alarm delay
Low output alarm delay time
30 s
0-300 s
DIP switch
12345678
DIP switch state 0=off, 1=on
0
0,1