emlight.com.au
1300 436 533
P.4
emlight.com.au
1300 436 533
P.5
Operational Overview
AutoFLEX autonomous lighting allows clients to have as much light as necessary when spaces
are occupied, and as little as possible when the spaces are unoccupied. Every AutoFLEX
luminaire has an occupancy sensor and wireless mesh network capability. This patented
communication technology allows the fixtures to grouped into convenient control groups and to
share operational commands and occupancy data.
Configuration and programming
Configuration and programming is provided by a handheld remote programmer (purchased
separately) and most functions controlled by connection to any fixture in the network. Each
programmer has the capacity for eight groups.
Installation
AutoFLEX luminaires have no special installation requirements. All they require is connection
to the power supply.
The AutoFLEX Handheld Remote Programmer
Allocation of groups
Group allocation is essential, or all the fixtures will be ON when there is any activity anywhere
in the areas covered by AutoFLEX. Creation of a grouping plan is recommended to facilitate
allocation of a group number to every luminaire (see simple examples pages 3 and 8 ).
Simply point the programmer at each fixture in turn and hold the relevant Group number until
the fixture flashes once to acknowledge receipt of the command. Repeat this with each fixture.
Fixtures can be members of multiple groups to better bridge transit spaces (see carpark
example page 8 ). To link to an additional Group the press SELECT and then the additional
Group number.
Operational Programming
There are five operational parameters than can be set for each group.
These are:
1. Operational Light level
2. Activity sensing range
3. Ambient light activation
4. Time until Standby
5. Standby Brightness
Where the factory default settings are not suitable, use a remote programmer to adjust via a
convenient fixture and then Sync and Save to the correct group ( see below).
The factory default settings are shown in the Table below.
Parameter
Variants
Default Se ng
Grouping
Brightness
Mo on Sensor
Sensing Distance
Ambient Light Sensor
Time un l Standby
Standby Brightness
1-8 Groups
12%-100%
Enabled / Disable
Near (1-3m)/ Medium (3-5m) / Far (5-8m)
OFF (no sensing) / Dusk/ Night
30 seconds / 3 minutes / 10 minutes
OFF / 10% / 30%
0 (no group)
100%
Enabled
Near (1-3m)
OFF
30 seconds
OFF
Identify group for action
Select
By MASTERTEC SUSTRALIA
By MASTERTEC SUSTRALIA