6
PRE-INSTALLATION INSTRUCTIONS
INSPECTION FOR SHIPPING DAMAGE
You are responsible for filing all freight claims with the delivering truck line. Inspect all cartons and crates for
damage as soon as they arrive. If damage is noted to shipping crates or cartons or if a shortage is found, note
this on the bill of lading (all copies) prior to signing.
If damage is discovered when the cabinet is uncrated, immediately call the delivering truck line and follow up
the call with a written report indicating concealed damage to your shipment. Ask for an immediate inspection of
your concealed damage item. Crating material must be retained to show the inspector from the truck line.
INSTALLATION INSTRUCTIONS
GENERAL INSTRUCTIONS
1. Be sure the equipment is properly installed by competent service people.
2. Keep the equipment clean and sanitary so it will meet your local sanitation codes.
3. Rotate your stock so that older stock does not accumulate. This is especially important for ice
cream. A "First-In, First-Out" rotation practice will keep the products in good salable condition.
4. Do not place product in the case when it is soft or partially thawed. Also, product should not be put in the
case for at least 6 hours after it is started.
5. Stock cases as quickly as possible, exposing only small quantities to store temperatures for short periods of
time.
6. When replacing burned out fluorescent tubes, be sure that the electrical power to the lighting circuit is
turned off.
MECHANICAL
Remove front grille and check refrigeration lines to see that they are free (not touching each other or
compressor). Spin condenser fan blade to see that it is free.
Check that all service valves (2) are open. Cut compressor
hold-down strap and remove. The springs are secured for
shipping by either tightening bolts or shipping strap. Remove the
strap or loosen the hold-down bolts so that the compressor
floats freely. Check all refrigeration lines and electrical conduit
for rubbing or chaffing, paying particular attention to area where
lines enter the cabinet.
Remove cabinet from crate base and slide into location. Cabinet
must be level from side to side and front to back for correct
draining of coil pan and for self-closing doors to operate
correctly. Allow minimum of 4” between back of cabinet and wall
and between top of cabinet and ceiling for proper condensing
unit air circulation.
To comply with Sanitation requirements the cabinet must be mounted on legs (6” high min.) or casters or the
base must be sealed to the floor with an N.S.F. listed silicone sealant.
To comply with UL requirements the cabinet must have a minimum clearance of 4” at the top, 6” at the rear
and 0” at each side.
Summary of Contents for TAF-27
Page 2: ...2 ...