45
Blast Chiller Default List of configuration parameters
The following table illustrates the meaning of the configuration parameters.
PAR
Description
Unit
Range
ºC
ºF
CA1
Cabinet probe offset
°C/°F
-25 to 25
0
0
CA2
Need probe offset
°C/°F
-25 to 25
0
0
CA3
Evaporator probe offset
°C/°F
-25 to 25
0
0
CA4
Condensor probe offset
°C/°F
-25 to 25
0
0
CA5
Needle probe offset 2
°C/°F
-25 to 25
0
0
CA6
Needle probe offset 3
°C/°F
-25 to 25
0
0
P0
Probe type:
0 = PTC
1 = NTC
…
0 / 1
1
1
P2
Temperature unit of measurement
0 = ºC
1 = ºF
…
0 / 1
1
1
P3
Number of needle probe sensor
0 = 0; 1 = 1; 2 = 2; 3 =3
…
0 / 3
3
3
P4
Enabling the evaporator probe
…
0 / 1
1
1
P5
Enabling condenser probe
…
0 / 1
0
0
P8
Orientation of the display Visualization
0 = device located at the top as the unit
1 = device located at the bottom as to the unit
…
0, 1
1
1
Operation Parameters
PAR
Description
Unit
Range
ºC
ºF
r0
Temperature differential (r7 – r12)
°C/°F
1 – 15
5/7
5/7
r1
Duration of Time-Controlled blast chilling
Min
1 – 500
90
90
r2
Duration of Time-Controlled blast Freezing
Min
1 – 500
240
240
r3
Temperature-controlled blast chilling & soft deep freezing temperature
°C/°F
-99 – 99
3
37
r4
Temperature-controller deep freezing temp. (see also r6)
°C/°F
-99 – 99
-18
0
r5
Max duration of Temperature-controlled blast chilling (see also r3)
Min
1 – 500
90
90
r6
Max duration of Temperature-controlled deep freezing (see also r4)
Min
1 – 500
240
240
r7
Box temperature set-point for blast chilling & soft deep freezing
°C/°F
-99 – 99
0
32
r8
Box Temperature setpoint during deep freezing (see also r0)
°C/°F
-99 – 99
-26
-15
r9
Box Temperature setpoint during HARD blast chilling (see also r0)
°C/°F
-99 – 99
-4
25
r10
Box Temperature setpoint post blast chilling STORAGE (see also r0)
°C/°F
-99 – 99
2
36
r11
Box Temperature setpoint post deep freezing STORAGE (see also r0)
°C/°F
-99 – 99
-18
0
r12
Box Temperature setpoint during Pre-Cooling (see also r0)
°C/°F
-99 – 99
5
41
r13
Hard blast chilling end temperature setpoint (needle probe)
°C/°F
-99 – 99
15
59
r14
Time-control hard blast chilling & Soft deep freezing
%
10 – 100
60
60
r15
Temperature below which count the max blast chilling & deep freezing
°C/°F
-99 – 99
65
149
r16
Type of operating cycle that can be selected
0 = blast chilling & Storage only
1 = blast chilling & Storage or deep freezing & storage
2 = deep freezing & store only
…
0 – 2
0 / 2
0 / 2
r17
Min temperature difference between needle probe and box temperature
0 = Test will not be perform
°C/°F
0 – 99
5
5
r18
Duration of second phase test for correct insertion of needle probe
Second
1 – 99
60
60
r19
Reserved
…
…
…
…