background image

I-J

OIS

TS

 

 

Installing the Gas Fireplace 

Anchorage  of  fireplace  to  wood  floor  construction  is  required. 
Refer  to  Fig.  9-2  for  anchorage  locations.  Four  anchors  are 
required to attach to the sub-flooring framing. 
Crawl Space or Upper Floor: 

 

Fig.  10-1  
  I-Joist 

Anchoring  

bottom view 

 
 
 
 
 
 
 
 

Anchor 

Example only 

brackets 

 

For  installation  of  firebox  over  combustible  crawl  spaces  or  
upper  floors,  anchorage  of  the  firebox  is  required.  Illustrations  
of examples of possible anchorage methods are shown in Fig.  
9-2  thru  10-2  depending  upon  the  type of floor framing. Final  
method  of  anchorage  to  be  determined  by  licensed  design  
professional. 

For  conventional  framing  where  the  floor  joists  are  parallel  
with the sides of the firebox, the addition of floor joists  to align  
with  the  anchor  brackets  allows  the  brackets  to  be  directly  
connected  to  the  floor  joists.  Note  that  additional  floor  joists  
may be required to support the weight of the firebox and 

 

Fig. 10-2  Typical anchorage layout 

 

48-3/4

” 

2

” min 

Fireplace 

chimney. Where the floor  joists  run  parallel  to  the front of  the 
firebox,  anchorage  can  be  accomplished  in  like  manner  as 
shown in Fig. 10-1 using blocking between the floor joist. 

For floors supported by I-Joists, the method of anchorage is 
illustrated in Fig. 9-3 and 10-1. Fig. 10-2 illustrates the general 
arrangement of anchorage to floor framing. 

 

It is important to take into consideration that the load for the 
Mason-Lite Fireplace must be considered as additional dead 
load  that  will  have  to  be  supported  by  the  floor  framing. 
Additional floor joists or I-joists may be required as determined by 
the licensed design professional. 

The  weights  are  noted  in  Table I  for  each MASON-LITE 
unit  model.  It  is  the  task  and  responsibility  of  the  general 
contractor/installer  to  see  that  the  proper  reinforcement  for 
weight  loads  are  made  by  a  licensed  design  professional 
prior to the fireplace installation. 

As stated above, it is desirable to place additional framing for 

alignment  of  anchor  rods.  Refer  to  Fig.  10-2  for  anchor  rod 
dimensions. 

Attach the firebox side wall anchors to steel support frame by 

inserting  all-thread  rods  through  holes  on  the  bottom 
flange  on  the  steel  support  frame  as  shown  in  Fig.  10-2. 
Secure with two Ø 2

” o.d. x Ø 9/16” i.d. x 0.10” Washers and 

two 1/2-13 UNC Nuts. 

MASON-LITE Weight Determination 

The following  are  dead  load  weight  estimates for  the 
Mason-Lite

™ Fireplace. 

Table I 

MFPST43 

Fireplace 

845 lbs.  

clearance 

outline 

Damper/Anchor 
Plate, Firebrick & 

350 lbs. 

12

” 

Mortar 

Floor Area 

53

”  x  28”  

(10.3 ft²)  

 

Other Weight Considerations: 

1)   Fireplace finished facing 

(surround): This information 

needs to be obtained from the contractor. 

Example only 

2)   Weight of metal flue: See chimney manufacturer

’s weight 

specifications. Some chimney systems can weigh up to 
50 lbs per lineal foot. 

 

Note that MASON-LITE cannot accept responsibility for 
structural floor support details. All drawings are presented as 
mere illustrations to indicate the presence of the underlying 

SECTION VIEW 

floor system. It is the responsibility of the general contractor/ 

ROTATED 90CW 

installer to consult with a local licensed design professional 
for guidance in building a proper floor support system. 

REV 1 - 0907231405 

10 

L-A2-27509 

Summary of Contents for MGFPST-43

Page 1: ...is fireplace must be connected to a working flue meeting the requirements of the ANSI Z21 50 standard Solid fuels shall not be burned in this fireplace This appliance must be vented vertically through the roof This appliance is not for installation in manufactured or mobile homes The installation including provisions for combustion ventilation air and required minimum permanent vent opening must c...

Page 2: ... 15 16 16 16 16 16 17 17 17 18 19 19 19 20 20 20 20 20 20 21 21 22 22 22 22 22 22 23 23 23 23 23 23 Tested Listed By MFI 315 WEST 3RD ST SANTA ANA CA 92701 Industries LLC DATE OF MFG SERIAL No Report No TBD MODEL No MGFPST 43 GAS TYPE NG LP WARNING THIS FIREPLACE HAS BEEN TESTED FOR USE ONLY WITH APPROVED GLASS DOORS TO REDUCE THE RISK OF FIRE OR INJURY CONSULT OWNER S MANUAL THIS FIREPLACE IS DES...

Page 3: ...ting plate MFPST43 MFP16 11 4 3 Rebar Ø 3 8 x 36 MFP49 11 10 2 Dome front rear upper MFSTP 43 10 12 9 1 Dome top for 16 class A chimney MFPST 43 9 8 8 2 Dome side upper MFPST 43 8 7 2 Dome side lower MFP 43 7 6 6 2 Lintel MFP 43 6 15 3A 1 Side wall w 4 knockout MFP 43 3A 3 7 Side wall MFP 43 3 3 11 1 3A Refractory Firebox Liners Herringbone Pattern shown Also available in Running Bond MFP43STSHBL ...

Page 4: ...required up to header or top plate 1 2 MIN 0 MIN 57 I D FRAMING Fig 4 2 Framing dimensions 2 MIN 0 MIN 28 O D ZERO CLEARANCE TO COMBUSTIBLES BOTH SIDES AND BACK OF FIREPLACE WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury REV 1 0907231405 4 L A2 27509 ...

Page 5: ...it 4 1 Damper clamp 5 1 Lava Rock qty of 4 6 1 Front bottom log 30 7 1 Front bottom log 30 8 1 Top log 18 9 1 Top log 18 10 1 Top log 20 11 1 Top log 17 6 7 1 8 11 2 4 5 Photos not to scale Contact Mason lite for replacement parts and accessories as listed in these parts lists 9 10 3 REV 1 0907231405 5 L A2 27509 ...

Page 6: ...g code approvals and may cause property damage personal injury or loss of life The burner included with this gas fireplace is non convertible and only meant to be used with the gas listed on the rating plate Burner p n BTU x 1000 size top front Included in Nat LP MGFPST 43 P 90 23 45 44 55 MGFPST 43 Nominal BTU based on gas inlet pressure Nominal gas inlet pressure for natural gas is 5 W C Require...

Page 7: ...ding sizing and suitability for the installation into this Enclosure prior to installation Statement of Intended Use The Mason Lite Masonry Fireplace is a modular refractory masonry unit designed for field assembly The firebox is constructed using pre cast interlocking refractory blocks The blocks are then secured to each other using Mortar The system includes all parts necessary for the assembly ...

Page 8: ...allations Internal Wall Installation Island Installation Clearance to Combustibles The distance to be maintained from the surfaces of the fireplace to combustibles must be observed Below is a list of the most common combustible materials to name a few Drywall Wood flooring Plywood sub flooring Wood Framing Particle board Mill board Plywood paneling Maintain the following clearances Unit front side...

Page 9: ...n of the fireplace You must follow your chimney manufacturer s instructions Fireplace Heights When installed the maximum overall height of the Chimney System is 40 feet The minimum installed height of the completed Chimney System is 14 feet with a straight flue stack 17 feet if the chimney includes one or two offset sections Supporting Floor Systems It is the ultimate responsibility of the install...

Page 10: ...y the floor framing Additional floor joists or I joists may be required as determined by the licensed design professional The weights are noted in Table I for each MASON LITE unit model It is the task and responsibility of the general contractor installer to see that the proper reinforcement for weight loads are made by a licensed design professional prior to the fireplace installation As stated a...

Page 11: ...Four or more fasteners to attach metal base to floor joists 4 Mason Lite Mortar at least one 50 lb bucket two for MFP63 Tools needed for both above installations 1 One 4 level 2 Roto hammer with drill bit needed for concrete slab install only 3 Drill motor with mixer blade to mix Mason Lite Mortar 4 Two empty 5 gallon buckets to mix Mason Lite Mortar 5 One wheelbarrow and shovel to mix concrete 6 ...

Page 12: ...rebox side walls moving up keeping components moist mixing mortar as you need it and threading the mortar appropriately as you stack each section one onto the next Constantly check for squareness and levelness while building each course of block As you complete each section make certain that you adhere the mortar at each and every joint Fig 12 2 Setting Firebox sides Fig 12 3 Keep damp at all time...

Page 13: ...ssembly 17 As you are connecting each MASON LITE component be certain you are following the instructions given previously for using MASON LITE mortar Stop to look at the smoke dome side front and rear walls to see that they are aligning correctly and that the surfaces be smooth and uniform Make sure connections are covered with an adequate amount of mortar Remember that you have the option of usin...

Page 14: ...n Lite Firebrick Liners screws Existing Ceiling Frame framework to house the chimney system 22 Now that you have completed the smoke dome assembly all the components should stack up for a smooth transition into the flue components Setting the smoke dome completes the MASON LITE Firebox and Smoke Dome assembly You are now ready to begin the installation of the necessary firebrick lining and the flu...

Page 15: ...ern the proper instructions from the fireplace liner manufacturer and also understand the type of adhesive or cement he is to use Make sure the fireplace is installed with the finished firebrick floor of the fireplace so that it is at least 11 eleven inches above the combustible floor system Disclaimer Masonry Fireplace Industries wishes to express that as the manufacturer of Mason Lite Fireplaces...

Page 16: ...for outside combustible air It can go straight out through an outside wall or into a ventilated crawl space If crawl space is used check codes for proper termination 3 Be sure that you carefully check the source of the outside air before you choose the site for your air intake You don t want a place where snow will collect where bushes or trees will be growing or a location that is too close to an...

Page 17: ...ling holes into damper plate 5 Attach damper chain stop on center rear of lintel 3 three inch vertical from opening using 3 8 cement fasteners Fig 17 1 Return Return Elbow Elbow Elbow Elbow when building the framework for the chimney system Fireplace Door Accessory IMPORTANT Only Crown Breckinridge or McKenzie Pendelton Doors are approved for use with this fireplace For installation Instructions s...

Page 18: ...concrete slab The concrete strength and durability shall comply with Sections TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MINIMUM SPECIFIED COMPRESSIVE STRENGTH a f c TYPE OR LOCATION OF CONCRETE CONSTRUCTION Weathering Potential b Negligible Moderate Severe Basement walls foundations and other concrete not exposed to the weather 2 500 2 500 2 500C Basement slabs and interior s...

Page 19: ...d female for the spill switch wires connection The short spill switch wire is to be routed across and into the top hole on the opposite side of the fireplace Connect the wire to the opposite baffle assembly Fig 19 1 Owner s Operation Precautions Installers of the Mason Lite are urged to call the attention of fireplace owners to the following precautions The installer should hand deliver this owner...

Page 20: ...Pilot if neccessary 1 Follow the lighting instructions to light the pilot The pilot flame should encircle the generator tip which is preset at the factory Fig 20 2 Ordinarily the pilot will not require field adjustment 2 If adjustment is necessary remove the cap screw Fig 20 1 and turn the smaller gas adjustment screw inside counterclockwise to increase the pilot flame and clockwise to decrease th...

Page 21: ...th the burner pipe Repeat for the second front log on the opposite side of the see thru burner 2 Place the top logs across the two bottom logs in the order and positions shown below Fig 21 1 Fig 21 2 8 9 WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury 11 1...

Page 22: ...ay lit see the Troubleshooting section Lighting and Extinguishing the Burner System To turn on your gas log set with the pilot lit turn the safety valve knob to the ON position Switch the toggle switch control to the on UP position and the gas log set will light To turn off your gas log set switch the toggle switch control to the off DOWN position The pilot will remain lit See the instructions tha...

Page 23: ...No Gas to Burner 3 Fireplace Not burning properly 4 Fireplace will not shut OFF 5 Frequent pilot outage 6 Fireplace shuts down during operation 7 Excessive soot on logs CAUSE a Pilot generator may not be producing sufficient millivoltage b Pilot flame making a blowing sound c Generator wire leads attached to the wrong terminals on the valve d Defective thermomagnetic safety in valve a Safety valve...

Page 24: ..._________ Orifice Other __________ Leak Test ___________ Burn Test ___________ Gas Type NAT PROPANE Date ___________ Model ___________ Serial ___________ Air Shutter ___________ Inspector ___________ REV 1 0907231405 24 L A2 27509 ...

Reviews: