background image

17

 

 

Mason-Lite Fireplace

 

Chimney System

 

MFPST43

 

UL103-

16” I.D. Class A

 

 

MASON-LITE Chimney Systems:

 

 

The Mason-Lite Fireplace requires the following chimney 
systems:

 

All  chimney  systems must be  installed  with  an  integrated 

damper/base  plate  installed  on  top  of  unit.  Installers  are 
cautioned  to  put  the  chimney  system  together  exactly  as 
instructed  and  shown  in  chimney  manufacturer

’s  guide. Any 

variations  may  have  serious  consequences  resulting  in  an 
accident  or  malfunction.  If  instructions  are  not  followed,  the 
warranty on the product will become null and void.

 

 

Figure 33

 

 

 
 

Elbow 

Return

 

Elbow

 

 

 
 
 

 
 

 

6' 
Max.

 

 
 

 

6' 
Max.

 

 

 

 

Return 
Elbow

 

 
 
 
 
 

 
 

 
 

Elbow

 

 

 
 
 

 

Elbow 

Return

 

Elbow

 

 

 

 
 
 

 
 
 
 
 
 

 
 
 

6' 
Max.

 

 

 
 
 

 
 

 

6' 
Max.

 

 

 
 
 

Return 
Elbow

 

Note  that the most important aspect of the installation is 
maintaining the minimum required clearances to combustible

 

 

Elbow

 

 
 

Ceiling

 

Return 
Elbow

 

materials  according  to  the  chimney  pipe  manufacturer

’s 

recommendations,  otherwise  a  potential  fire  hazard  may 
occur.

 

 

Warning:  do  not  interchange  chimney  manufacturer

’s  parts 

with  any  other  parts  except  those  specifically  required  by 
the  chimney  manufacturer

’s  recommendations  otherwise  a 

potential hazardous condition may be created.

 

 

Attention: When choosing a Chimney System it must meet the 
following requirements:

 

B

 

 
 
 

 

Elbow

 

Support 
Pipe 12S-
12DM

 

 

 

 

6' 
Max.

 

 

 
 

C

 

 

6' Max.

 

 

• 

Designed  for  installation  in  accordance  with  the  National 
Fire Protection Standard and UL 103.

 

• 

Meets the requirements of NFPA 211.

 

• 

Designed in accordance with ICC Codes.

 

 

 

Assuming you have sections of vertical pipe that are more than 
10’ (ten feet) measuring between elbows, you must insert – at 
midpoint 

– a chimney stabilizer. When installing the stabilizer, 

pull out the support straps with a good amount of tension and 
hammer to the frame.

 

 

Installing Damper and Chimney System

 

 

The  Damper  System/Anchor  Plate  assembly  is  required 

for  the  installation  of  these  chimney  systems.  Consult  the 
Chimney System manufacturer

’s instructions.

 

1.  Using  the  Damper/Anchor  Plate  Assembly,  apply  a 

1/4” 

(one-quarter  inch)  bead  of  gasket  cement  around  the 
base of the Anchor Plate. Apply ceramic blanket gasket to 
the gasket cement.

 

2.  Apply  balance  of  gasket  cement  in  a 

1/4”  (one-quarter 

inch) bead on top of smoke dome top approx. 

3” (3 inches) 

outside of outlet hole. Install damper on top of unit pressing 
damper into cement.

 

3.  Place  chimney  adapter  onto  top  of  damper  plate  and 

center in opening using gasket supplied with adapter.

 

4.  Attach  adapter  with  (12)  #8  cement  fasteners  supplied, 

carefully drilling holes into damper plate.

 

5.  Attach  damper  chain  stop  on  center  rear  of  lintel 

3” 

(three  inch)  vertical  from  opening  using  (3)  #8  cement 
fasteners.

 

 
 

 
 

 

Attention: 

Clearance to combustible construction cannot  be 

reduced during course of construction. For the safe operation 
of  the  finished  fireplace,  these  clearances  must  be  followed 
when building the framework for the chimney system.

 

 

 

Finishing Your Installation

 

To  complete  your  fireplace  installation,  a  fireplace  grate  will 

be  required  for  safe  operation.  The  fireplace  grate  must  be 
sized  to  50%  of  the  hearth  maximum.  Additionally,  a  fireplace 
screen  must  be  installed  for  safety.

 

 

Fireplace Door Accessory

 

IMPORTANT:  Only 

Crown-Breckinridge  or 

McKenzie- 

Pendelton Doors are approved for use with this fireplace.

 

For installation Instructions, see separate instructions included 
with doors.

 

Summary of Contents for MFPST-43

Page 1: ... OR LOSS OF LIFE REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION CONSULT A QUALIFIED INSTALLER OR LOCAL DISTRIBUTOR SAVE THIS BOOK This book is valuable In addition to instructing you on how to install and maintain your appliance it also contains information that will enable you to obtain replacement parts or accessory items when needed Keep with your other important papers Report No...

Page 2: ...This page has been left intentionally blank ...

Page 3: ...ons and installation specifications in your area DATE OF MFG SERIALNo Report No 08 154 ICC Evaluation Services Report No 2401 MODEL No WARNING THIS FIREPLACE HAS BEEN TESTED FOR USE ONLY WITH APPROVED GLASS DOORS TO REDUCE THE RISK OF FIRE OR INJURY CONSULT OWNER S MANUAL THIS FIREPLACE IS DESIGNED FOR USE ONLY WITH SOLID WOOD LOGS PLUMBED LPG OR NG LOG LIGHTERS OR PLUMBED ANSI Z21 60 DECORATIVE G...

Page 4: ...m ms s s C Co om mb bu us st ti ib bl le F F Fl l lo o oo o or r r S S Sy y ys s st t te e em m ms N No on n C Co om mb bu us st ti ib bl le e F F Fl l lo o oo o or r r S S Sy y ys s st t te e em m ms s s Figure 1 13 14 8 7 Figure 2 21 21 9 13 9 14 10 10 8 7 12 12 22 22 6 6 24 20 24 20 23 23 1 1 19 19 3 3 3A 17 3A 16 18 ...

Page 5: ...Ø3 8 x 36 8 20 MFP ARC LINTEL TRIM OPTIONAL 2 21 MFP116 16 COLLAR TENSION STRAP 16 1 22 MFP117 TENSION STRAP UPPER 2 23 MFP118 TENSION STRAP LOWER 2 24 MFP119 TENSION STRAP HARDWARE PACK 1 M MF FP PS ST 4 4 43 F F Fi i ir r re e ep p pl l la a ac c ce P P Pa a ar r rt t ts L L Li i is s st Optional Outside Ø4 Combustion Air Kit Model No MFP4 AK Ø4 Ducting not included MFP43SHBL Herringbone MFP43FR...

Page 6: ...OF THE DOME IF WOOD FRAMING IS UTILIZED IT MUST BE HELD 18 INCHES MIN FROM TOP OF LINTEL AND 2 INCHES MIN CLEARANCE MUST BE MAINTAINED ALL AROUND FIREPLACE DOME IF METAL FRAMING IS USED MAINTAIN A 1 2 INCH MIN AIR SPACE FROM TOP OF LINTEL 2 MIN CLEARANCE TO COMBUSTIBLES AROUND SIDES REAR AND TOP OF FIREPLACE DOME 57 I D FRAMING 28 O D WARNING Failure to position the parts in accordance with these ...

Page 7: ...AND 28 2 INCH CLEARANCE TO COMBUSTIBLES BOTH SIDES OF FIREPLACE If using a raised hearth or metal base plate note that a combustible wood header must be no closer than 2 to the top of the dome top Figure 6 Non Combustible Hearth Extension by others 2 ONLY NON COMBUSTIBLE MATERIAL WITHIN 18 OF TOP OF OPENING SEE FIG 26 2 AIRSPACE CLEARANCE TO COMBUSTIBLES FROM REAR AND SIDES 2 MIN 1 2 1 2 THICK CON...

Page 8: ...gs Plumbed LPG or Natural Gas Log Lighter Plumbed ANSI Z21 60 Decorative Gas Log DO NOT USE OR STORE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR GASES IN OR NEAR THE FIREPLACE ATTENTION A fire or an explosion could occur causing property damage injury or loss of life if you do not follow the information in this manual NOTE THIS MANUAL MUST BE REPRODUCED ONLY IN ITS ENTIRETY Before Beginning the Install...

Page 9: ...ible materials Familiarity of installation for all components The strength of the floor on which it rests Chimney system measurements Choice of materials and craftsmanship in fireplace and hearth finishing Island Installation Note that each of these topics will be covered in detail and that the installer is expected to understand each phase completely before going on to subsequent instructions Att...

Page 10: ...y heat source 3 It is the responsibility of the contractor installer not the manufacturer to ensure that adequate combustion air is provided for proper function of this fi replace Fireplaces take up a large volume of replacement air from outside the house and if the house is of airtight construction smoke spillage may occur if proper draft is not achieved 4 There are many conditions beyond a manuf...

Page 11: ... anchorage to be determined by licensed design professional For conventional framing where the floor joists are parallel with the sides of the firebox the addition of floor joists to align with the anchor brackets allows the brackets to be directly connected to the floor joists Note that additional floor joists may be required to support the weight of the firebox and chimney Where the floor joists...

Page 12: ...rs having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection resulting from L D Note that MASON LITE cannot accept responsibility for structural floor support details All drawings are presented as mere illustrations to indicate the presence of the underlying floor s...

Page 13: ...te with 1 4 or smaller aggregate Mason Lite Mortar one 50 lb bag Materials needed for combustible wood floor installation Hearth Ember Shields Eight 8 All Thread Rods are secured to the top flange of the Metal Base with sixteen 16 fl at washers 2 OD x 9 16 ID x 0 10 and sixteen 16 1 2 13 UNC Nuts Anchor Bracket All Thread Rods are secured to the bottom flange of the Metal Base with eight 8 fl at w...

Page 14: ...lds on the next If you have to make any kind of an adjustment do not try to do it by loading an opening with mortar this will only result in a fi replace that will not be plumb or level Use wood shims instead You will find these small wood shims supplied with the Mason Lite Fireplace and you can nudge them in between openings to achieve the precision you need in making component adjustments Once y...

Page 15: ...sing MASON LITE mortar Stop to look at the smoke dome side front and rear walls to see that they are aligning correctly and that the surfaces be smooth and uniform Make sure connections are covered with an adequate amount of mortar Remember that you have the option of using shims and covering them with mortar if you need to Make any adjustments to the fireplace alignment before continuing to the n...

Page 16: ...irebox and Smoke Dome assembly You are now ready to begin the installation of the necessary fi rebrick lining and the flue components Figure 26b eight 8 x 3 4 Screws Firestop Radiation Shields also provide complete separation from one floor space to another or attic space as required by most codes When the double wall pipe passes through a framed opening into an attic space the firestop must be pl...

Page 17: ...hes are used corner notching will be required on all four places Figure 29 Finished Height to Combustible Floor FINISHED FIREBRICK HEARTH LINER The following Firebrick Liners are available from MFI MFPST43SHBL Herringbone 11 INCHES MINIMUM TO COMBUSTIBLE FLOOR Disclaimer Masonry Fireplace Industries wishes to express that as the manufacturer of Mason Lite Fireplaces they cannot take any liability ...

Page 18: ... to heat However in almost all cases there is a solution to the problem either by making adjustments to airflow or the modifications to the room itself Installing Outside Combustion make up Air 1 The Mason Lite Fireplace needs enough make up air to function properly and some local building codes may require outside combustion air to be provided If no make up air is provided improper flue drafting ...

Page 19: ...n elbows you must insert at midpoint a chimney stabilizer When installing the stabilizer pull out the support straps with a good amount of tension and hammer to the frame Installing Damper and Chimney System The Damper System Anchor Plate assembly is required for the installation of these chimney systems Consult the Chimney System manufacturer s instructions 1 Using the Damper Anchor Plate Assembl...

Page 20: ...irewood at any given time Consider that this typical fuel load is three to four dry hardwood logs that are about 6 six inches to 8 eight inches in diameter 4 Without a grate for your firewood to rest on you cannot get the air flow you need under the fire which makes for a hotter more satisfying fire 5 Don t over burn Always remember your Mason Lite Fireplace is an elegant addition to your home It ...

Page 21: ... their residue could introduce a fire hazard after the task is completed Outside Inspection During your once a month inspection of the firebox and chimney make it a point to also check the outside of the chimney the metal flashing and weather seals that surround it If you find any cracks or openings around screws or nails seal them to avoid any roof or chimney chase leaks SURFACE CRACKS The MASON ...

Page 22: ...ed concrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE TYPE OR LOCATION OF CONCRETE CONSTRUCTION MINIMUM SPECIFIED COMPRESSIVE STRENGTHa f c Weathering Potentialb Negligible Moderate Severe Basement walls foundations and other concrete not exposed to t...

Page 23: ...ely b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in significant snowfall combined with extended periods during which there is little or no natural thawing causing deicing salts to be used extensively ...

Page 24: ... any labor costs or indirect costs incurred for the replacement of defective components MFI is not responsible for misuse or mishandling of component parts Nothing in this warranty makes MFI or any entity thereof liable in any respect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property therein arising out of the use misuse o...

Reviews: