HT7S Series

 

 
 
The  following  guidelines  should  guarantee  good 
instrument performance: 

 

Select a representative location: install the probe where 
humidity,  temperature  and  pressure  conditions  are 
representative of the environment to be measured. 
Provide good air movement at the probe: air velocity of 
at  least  200  ft/  minute  (1  meter/second)  facilitates 
adaptation of the probe to changing temperature. 

 

Immerse  as  much  of  the  probe  as  possible  in  the 
environment to be measured. 

 

Prevent  the  accumulation  of  condensation  water  at  the 
level  of  the  sensor  leads.  Install  the  probe  so  that  the 
probe  tip  is  looking  downward.  If  this  is  not  possible, 
install the probe horizontally. 

 

The serial no. & calibration code of the sensor: 

 

The small PCB name called sensor extension card that 
is  placed  over  the  main  card  or  motherboard  or  signal 
conditioner  card  through  2-row  3-pin  connector.  The 
serial  number  and  calibration  code  of  the  PCB  can  be 
seen  at  the  backside  of  the  sensor  extension  card  that 
have  unique 6  digits code  for both  sensor identification 
and  easy  customer  calibration  of  transmitter  or  signal 
conditioner card. The first number is sensor serial code 
and second number is calibration code. 

 

Calibration  Code:  The  first  three  digit  number 
represents  code  for  0  %RH  value  and  last  three  digits 
number  represents  code  for  75.3  %RH.    For  eg: 
Calibration  code:  837136.  The  actual  sensor  output 
voltage at 0 %RH = 0.837 V (First three Digits: 837) and 
at 75.3 % RH = 3.136 V (Last Three Digits: 136). Based 
on  the  given  two  points,  you  can  calculate  the  sensor 
output  voltage  at  100  %  RH  it  is  approximately  3.891V 
by extrapolation technique  which is used  for calibration 
purpose only. The sensor output voltage will differ from 
sensor  to  sensor.  Please  call  factory  if  you  have  any 
doubts. 

 

O

RDERING 

C

ODE

 

**For other than standard duct size (150 mm) please contact factory

 

 

 

 

T

ROUBLE 

S

HOOTING

 

  O/P mA Fault 

 

Check the transmitter output connections. 

 

Check the connection between the sensor and the 
transmitter. 

 

Check  the  output  voltage  of  the  sensor  for  sensor 
open /short circuit. 

 

  O/P mA Not Matching to the Required Value 

 

Check  whether  the  sensor  is  having  the  same 
serial number as the transmitter have. 

 

If there is a wide difference, check for any damage 
on  sensor. If a reference sensor is available  check 
it with the transmitter working correctly or not. 

 

If  there  is  calibration  doubt,  apply  known  values  of 
Calibration 

Code 

and 

check 

the 

Output 

accordingly. 
 
If still problem persist contact Masibus

 

P

RECAUTION

 

Don’t  remove  the  sensor  card  from  the  signal      
conditioning  card.  Don’t  interchange  the  sensor 
card  form  one  unit  to  other  unit  directly.  Its  needs 
calibration.  Contact  Masibus  for  any  calibration 
purpose. Don’t touch the RH sensor. 
 

masibus

 

Automation& Instrumentation Pvt. Ltd

.

 

B/30, GIDC Electronics Estate, Sector- 25,   
Gandhinagar-382044, Gujarat, India 
Ph: 91-079-23287275 / 76 / 77 / 78 / 79 
Fax: 91-079-23287281/ 82 
Email: [email protected] 
Web: www.masibus.com

 

 

 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 

Model 

Transmitter Type 

Mounting Type 

Duct 

Mounting 

Flange 

HT7S 

XX 

XX 

00 

Humidity 

Transmitter 

W0 

Wall 

Mount 

No 

 

10 

Humidity 

Transmitter with 

Pt100 Passive 

Output 

D0 

Duct 

Mount 

Yes 

 

11 

Humidity 

+Temperature 

Transmitter 

DX 

Ex.Proof 

Duct 

Mount 

 

 

 

11-Y 

Humidity 

+Temperature 

Transmitter with 

common Power 

Rail 

WX 

Ex.Proof 

Wall 

Mount 

 

 