9 Operation
Maschinenfabrik Reinhausen GmbH 2022
80
8595017/00 EN
TAPCON
®
250
TLS version
You can use this parameter to set the accepted TLS versions. If you would
like to establish an encrypted connection to the visualization, you must use
an accepted TLS version. You can select the following options:
Option
Accepted TLS versions
>= 1.0
▪ 1.0
▪ 1.1
▪ 1.2
>= 1.1
▪ 1.1
▪ 1.2
>= 1.2
1)
▪ 1.2
Table 14: TLS version
1)
This option can be selected only if the TLS version is supported by the
connected peripheral equipment.
9.1.3 Setting the device time
You can set the the device time manually or automatically via an SNTP time
server. The device must be connected to an SNTP time server via Ethernet
for this purpose.
1. Go to
Settings > Parameters > System > Time synchronization
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Time synchronization via SNTP
You can use this parameter to activate time synchronization using an SNTP
time server.
SNTP time server
You can use this parameter to enter the IP address of a SNTP time server. If
you are using a time server, the device uses the time of the time server as
the system time.
Be sure to enter a valid time server address that is not 0.0.0.0, otherwise it
will not be possible to connect to the device.