CONDENSATE DRAINS
The condensate drain pan is 2
²
high with two drain locations. During conditions of high humidity, condensate may be produced
at a rate of up to two gallons per hour. With this in mind, it is important to route condensate drains downward to a sump pump.
Do not route condensate drains to the bilge. After the condensate drain installation is complete, test the installation by pouring a
quart of water into the pan and checking for good flow. See note below.
For installation of the condensate drain:
1. Remove the aft facing watertight plug from the base pan of the a/c unit.